Number of Units CP1H-X40DR-A
Input words
---
Output words
---
Current
5 V
0.420 A
consump-
tion
24 V 0.070 A
5 V × 0.762 A = 3.81 W
Power con-
sumption
24 V × 0.394 A = 9.46 W
The following restrictions apply to the CP-series Expansion Units, CP-series
Expansion I/O Units, and CJ-series Units that can be connected to CP1H
CPU Units.
Number of Expansion Units and Expansion I/O Units Connected
A maximum of seven Units can be connected. If eight or more Units are con-
nected, an I/O UNIT OVER error will occur and the PLC will not operate.
Number of Words Allocated
The total number of either input or output words allocated to Expansion Units
and Expansion I/O Units must be no more than 15. Even if no more than
seven Units are connected, an I/O UNIT OVER error will be generated if 16 or
more input or output words are allocated.
Current Consumption
The total combined current consumption of the CP1H CPU Unit, Expansion
Units, Expansion I/O Units, and CJ-series Units must be no more than 2 A for
5 V and 1 A for 24 V and the total power consumption must be no more than
30 W. For CPU Units with AC power supply, the current consumption from
external 24-VDC power supply output must be included.
Number of CJ-series Units Connected
No more than two CJ-series Special I/O Units or CPU Bus Units can be con-
nected to the CP1H via a CJ Unit Adapter. No CJ-series Basic I/O Units can
be connected.
Example: Calculating the Limit on the Number of Connected Units
In this example, because each CPM1A-TS002 Temperature Sensor Unit is
allocated four input words, no more than three of these Units can be con-
nected. (Three Units × four words = 12 words.) After these have been con-
nected, there remain unallocated three input words and 15 output words. The
following table provides an example of Units that can be mounted in combina-
tion without exceeding these limits.
Combination Example
TS002 × 3
+ TS001 × 1
4 words × 3 Units
2 words × 1 Unit
= 12 words
= 2 words
0 words
0 words
0.040 A × 3
0.040 A × 1
= 0.120 A
= 0.040 A
0.059 A × 3
0.059 A × 1
= 0.177 A
= 0.059 A
Restrictions on the number of simultaneously ON output points
CP1W-32ER/32ET/32ET1's maximum number of simultaneously ON points is
24 (75%).
+ 20EDT × 1
+ 8ER × 2
1 word × 1 Unit
0 words
= 1 word
1 word × 1 Unit
1 word × 2 Units
= 1 word
= 2 words
0.130 A × 1
0.026 A × 2
= 0.130 A
= 0.0520 A
0.044 A × 2
0 A
= 0.088 A
Section 1-2
≤ 7 Units
Total: 7 Units
Total: 15 words ≤ 15 words
≤ 15 words
Total: 3 words
≤ 2 A
Total: 0.762 A
≤ 1 A
Total: 0.394 A
Total: 13.27 W ≤ 30 W