Omron CP1H CPU Operation Manual page 683

Cp1h cpu unit
Hide thumbs Also See for CP1H CPU:
Table of Contents

Advertisement

Auxiliary Area Allocations by Address
Address
Name
Words
Bits
A283
A283.00 PWM Output
0 Output In-
progress Flag
A283.08 PWM Output
1 Output In-
progress Flag
A294
All
Task Number
when Program
Stopped
A295
A295.08 Instruction
Processing
Error Flag
A295.09 Indirect DM
BCD Error
Flag
A295.10 Illegal Access
Error Flag
Function
ON when pulses are being output
from PWM output 0.
Cleared when operation starts or
stops.
OFF: Stopped
ON: Outputting pulses.
ON when pulses are being output
from PWM output 1.
OFF: Stopped
ON: Outputting pulses.
This word contains the task number
of the task that was being executed
when program execution was
stopped because of a program error.
(A298 and A299 contain the program
address where program execution
was stopped.)
This flag and the Error Flag (ER) will
be turned ON when an instruction
processing error has occurred and
the PLC Setup has been set to stop
operation for an instruction error.
CPU Unit operation will stop and the
ERR/ALM indicator will light when
this flag goes ON.
(The task number where the error
occurred will be stored in A294 and
the program address will be stored in
A298 and A299.)
This flag and the Access Error Flag
(AER) will be turned ON when an
indirect DM BCD error has occurred
and the PLC Setup has been set to
stop operation an indirect DM BCD
error. (This error occurs when the
content of an indirectly addressed
DM word is not BCD although BCD
mode has been selected.) CPU Unit
operation will stop and the ERR/ALM
indicator will light when this flag goes
ON.
(The task number where the error
occurred will be stored in A294 and
the program address will be stored in
A298 and A299.)
This flag and the Access Error Flag
(AER) will be turned ON when an
illegal access error has occurred and
the PLC Setup has been set to stop
operation an illegal access error.
(This error occurs when a region of
memory is accessed illegally.) CPU
Unit operation will stop and the ERR/
ALM indicator will light when this flag
goes ON.
The following operations are consid-
ered illegal access:
1) Reading/writing the system area
2) Indirect DM BCD error (in BCD
mode)
(The task number where the error
occurred will be stored in A294 and
the program address will be stored in
A298 and A299.)
Settings
Status
Status
after
at star-
mode
change
---
---
Cleared
---
---
Cleared
Normal tasks:
Cleared
Cleared
0000 to 001F
(task 0 to 31)
Interrupt
tasks: 8000 to
80FF (task 0
to 255)
ON: Error
Cleared
Cleared
Flag ON
OFF: Error
Flag OFF
ON: Not BCD
Cleared
Cleared
OFF: Normal
ON: Illegal
Cleared
Cleared
access
occurred
OFF: Normal
condition
Appendix D
Write
Related
timing
flags, set-
tup
tings
Refreshed
---
when pulse
output
starts or
stops.
---
When pro-
A298/
gram error
A299
occurs.
When pro-
A294,
gram error
A298/
occurs.
A299
PLC
Setup
(Opera-
tion when
instruc-
tion error
has
occurred)
When pro-
A294,
gram error
A298/
occurs.
A299
PLC
Setup
(Opera-
tion when
instruc-
tion error
has
occurred)
When pro-
A294,
gram error
A298/
occurs.
A299
PLC
Setup
(Opera-
tion when
instruc-
tion error
has
occurred)
649