Analog I/O Units
420
1 to 5 V
The 1- to 5-V range corresponds to the hexadecimal values 0000 to 1770 (0
to 6000). The entire data range is FED4 to 189C (−300 to 6300). Inputs
between 0.8 and 1 V are expressed as two's complements. If the input falls
below 0.8 V, open-circuit detection will activate and converted data will be
8000.
Converted Data
Hexadecimal (Decimal)
189C (6300)
1770 (6000)
0000 (0)
FED4 (−300)
0 to 20 mA
The 0- to 20-mA range corresponds to the hexadecimal values 0000 to 1770
(0 to 6000). The entire data range is FED4 to 189C (−300 to 6300). A negative
voltage is expressed as a two's complement.
Converted Data
Hexadecimal (Decimal)
189C (6300)
1770 (6000)
−1 mA
0000 (0)
4 to 20 mA
The 4- to 20-mA range corresponds to the hexadecimal values 0000 to 1770
(0 to 6000). The entire data range is FED4 to 189C (−300 to 6300). Inputs
between 3.2 and 4 mA are expressed as two's complements. If the input falls
below 3.2 mA, open-circuit detection will activate and converted data will be
8000.
Converted Data
Hexadecimal (Decimal)
189C (6300)
1770 (6000)
0000 (0)
FED4 (−300)
0.8 V
5 V 5.2 V
1 V
20 mA 21 mA
0 mA
FED4 (−300)
3.2 mA
0 mA
20 mA 20.8 mA
4 mA