Omron CP1H CPU Operation Manual page 634

Cp1h cpu unit
Hide thumbs Also See for CP1H CPU:
Table of Contents

Advertisement

Replacing User-serviceable Parts
1,2,3...
!WARNING
!Caution You must complete this procedure within five minutes after turning OFF the
!Caution UL standards require that batteries be replaced by experienced technicians.
!Caution Turn ON the power after replacing the battery for a CPU Unit that has been
600
Procedure
1. Turn OFF the power to the CPU Unit.
or If the CPU Unit has not been ON, turn it ON for at least five minutes and
then turn it OFF.
Note If power is not turned ON for at least five minutes before replacing the
battery, the capacitor that backs up memory when the battery is re-
moved will not be fully charged and memory may be lost before the
new battery is inserted.
2. Open the compartment on the CPU Unit and carefully draw out the battery.
3. Remove the battery connector.
4. Connect the new battery, place it into the compartment, and close the cov-
er.
Never short-circuit the battery terminals; never charge the battery; never dis-
assemble the battery; and never heat or incinerate the battery. Doing any of
these may cause the battery to leak, burn, or rupturing resulting in injury, fire,
and possible loss of life or property. Also, never use a battery that has been
dropped on the floor or otherwise subject to shock. It may leak.
power to the CPU Unit to ensure memory backup. If the procedure is not com-
pleted within 5 minutes, data may be lost.
Always place an experienced technician in charge or battery replacement.
unused for a long time. Leaving the CPU Unit unused again without turning
ON the power even once after the battery is replaced may result in a shorter
battery life.
Note The battery error will automatically be cleared when a new battery is inserted.