Omron CP1H CPU Operation Manual page 459

Cp1h cpu unit
Hide thumbs Also See for CP1H CPU:
Table of Contents

Advertisement

Analog I/O Units
Note
+
Analog
device
with
voltage
output
V OUT
Analog
I OUT
I/O Unit
COM
Note
Terminal Arrangements
NC
NC
I OUT
V IN0 COM0
NC
NC
V OUT COM
NC
NC
For current inputs, short V IN0 to I IN0 and V IN1 to I IN1.
V OUT
Voltage output
I OUT
Current output
COM
Output common
V IN0
Voltage input 0
I IN0
Current input 0
COM0
Input common 0
V IN1
Voltage input 1
I IN1
Current input 1
COM1
Input common 1
Wiring for Analog Inputs
V IN
Analog
I IN
I/O Unit
COM
Wiring for Analog Outputs
Analog
+
device
with
voltage
input
(1) Use shielded twisted-pair cables, but do not connect the shield.
(2) When an input is not being used, short the + and − terminals.
(3) Separate wiring from power lines (AC power supply lines, high-voltage
lines, etc.)
(4) When there is noise in the power supply line, install a noise filter on the
input section and the power supply terminals.
I IN1
AG
I IN0
V IN1 COM1
Analog
+
V IN
device
I IN
with
current
COM
output
V OUT
Analog
I OUT
I/O Unit
COM
Section 7-4
Analog
I/O Unit
+
Analog
device
with
current
input
425