Sample Application
1,2,3...
Routing Table Settings and Transfer to Each PLC
Set the routing tables with CX-Integrator, and transfer them.
1. Using CX-Integrator, connect online, and select Routing table - Settings.
Then create FINS local routing tables (a local network table and a relay
network table).
Example: PLC 1 Routing Table Settings
• Local Network Table
Unit number
0
1
• Relay Network Table (None)
Example: PLC 2 and PLC 3 Routing Table Settings
• Local Network Table
Option port No.
Option port 1
14/20
30/40/60
Option port 2
30/40/60
• Relay Network Table
In order to relay from PLC2/3 to the final network number 2, it is neces-
sary to relay via node address 1 on relay network number 2.
Final network number
2
2. Save the routing table file (File - Save local routing table file).
3. Select New from the Project Menu, and save with a file name. Then select
Add Device from the Project Menu. For each PLC, register a PLC with a
direct serial connection (node address: 0), and select it.
4. With CX-Integrator, select Open from the PLC Menu.
5. Select Routing table - Setup, read the saved file, and select Options -
Transfer to PLC. Click Yes to transfer the routing tables to the connected
PLCs.
Local network number
1
2
I/O capacity
Unit address
252(0xFC hex)
253(0xFD hex)
252(0xFC hex)
Relay network number
1
Section 9-12
Local network
number
1
1
1
Relay node address
2
563