Table of Contents

Advertisement

Cat. No. W464-E1-06
SYSMAC
CXONE-AL_C-V4/
CXONE-AL_D-V4
CS/CJ/CP/NSJ Series
CX-Integrator Ver. 2
OPERATION MANUAL

Advertisement

Table of Contents
loading

Summary of Contents for Omron CX-INTEGRATOR V2 - 12-2009

  • Page 1 Cat. No. W464-E1-06 SYSMAC CXONE-AL_C-V4/ CXONE-AL_D-V4 CS/CJ/CP/NSJ Series CX-Integrator Ver. 2 OPERATION MANUAL...
  • Page 3 CXONE-AL@@C-V4/ CXONE-AL@@D-V4 CX-Integrator Ver. 2.@ Operation Manual Revised December 2009...
  • Page 5  OMRON, 2008 All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of OMRON.
  • Page 7: Table Of Contents

    2-2-1 Overview ......................2-10 2-2-2 Procedures......................2-11 2-2-3 CPU Unit Troubleshooting ................. 2-22 Uploading Network Configurations and Checking for Communications Unit Errors..2-23 2-3-1 Overview ......................2-23 2-3-2 Procedure ......................2-23 2-3-3 Checking and Correcting Communications Unit Errors ........2-31 Switching the Target PLC ....................
  • Page 8 Network Conditions That Require Routing Tables..........3-4 3-1-3 Routing Table Setting Methods................3-5 3-1-4 Routing Table File Types Supported by the CX-Integrator........3-6 3-1-5 Transferring the Routing Tables ................3-6 3-1-6 Operating Procedures Prior to Routing Table Transfer ........3-7 Setting the Routing Tables....................
  • Page 9 Creating, Reading, and Writing CSV Files (Saving) .......... 4-26 4-3-10 Reading and Data Link Tables ................4-32 4-3-11 Transferring the Data Link Table ............... 4-34 4-3-12 Starting and Stopping Data Links (Including Status Displays) ......4-41 Automatically Set Data Links ..................4-43 4-4-1 Procedure Through Data Link Startup ...............
  • Page 10 Edit Device Parameters on CS1W-DRM21(-V1)/CJ1W-DRM21 ....... 6-22 6-7-2 Editing Device Parameters on CVM1-DRM21-V1 and C200HW-DRM21-V1 ... 6-24 6-7-3 Editing Device Parameters on 3G8F7-DRM21 DeviceNet PCI Board Scanner 6-26 6-7-4 Canceling Slave Registration with the Master ........... 6-28 6-7-5 Automatic Allocation with Registration............... 6-28 Manual I/O Allocations ....................
  • Page 11 7-5-1 Uploading Component Parameters to a Computer ........... 7-13 7-5-2 Comparing Component Parameters ..............7-14 7-5-3 Downloading the Component Parameters to the Components ......7-15 7-5-4 Resetting Component ..................7-17 Editing Master Unit Parameters ..................7-18 7-6-1 Master Unit Parameter Settings................. 7-18 7-6-2 Editing the Registration Table................
  • Page 12 10-2 Echoback Test between Nodes ..................10-22 10-2-1 Overview ......................10-22 10-2-2 Start Methods....................10-22 10-2-3 PLC Internode Echoback Test Dialog Box............10-22 10-2-4 Executing an Echoback Test between Nodes ..........10-23 10-3 Ethernet Ping Test ......................10-25 10-3-1 Overview ......................10-25 10-3-2 Start Methods....................10-25 10-3-3 Ping Test Dialog Box..................
  • Page 13 Please read this manual carefully and be sure you understand the information provided before attempting to use the CX-Integrator. Be sure to read the precautions provided in the following section. Precautions provides general precautions for using the CX-Integrator.
  • Page 14 Models Name Description W464 CX-Integrator Operation Describes CX-Integrator operating CXONE-AL@@C-V4 (this manual) Manual methods, e.g., for setting up and CXONE-AL@@D-V4 monitoring networks. W463 CX-One Setup Manual Describes installation and provides an CXONE-AL@@C-V4 overview of the CX-One FA Integrated CXONE-AL@@D-V4 Tool Package.
  • Page 15 Warranty and Limitations of Liability WARRANTY (1) The warranty period for the Software is one year from either the date of purchase or the date on which the Software is delivered to the specified location. (2) If the User discovers a defect in the Software (i.e., substantial non-conformity with the manual), and returns it to OMRON within the above warranty period, OMRON will replace the Software without charge by offering media or downloading services from the Internet.
  • Page 16 Application Considerations SUITABILITY FOR USE THE USER SHALL NOT USE THE SOFTWARE FOR A PURPOSE THAT IS NOT DESCRIBED IN THE ATTACHED USER MANUAL.
  • Page 17 The license fee of the Software does not include service costs, such as dispatching technical staff. ERRORS AND OMISSIONS The information in this manual has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical, or proofreading errors, or omissions.
  • Page 18 xviii...
  • Page 19 This section provides precautions for using the CX-Integrator. The information contained in this section is important for the safe and reliable application of the CX-Integrator. You must read this section and understand the information contained before attempting to use the CX-Integrator.
  • Page 20: Intended Audience

    As a countermeasure for all such errors, external safety measures must be provided to ensure safety in the system. • The PLC outputs may remain ON or OFF due to deposits on or burning of the output relays, or destruction of the output transistors.
  • Page 21 Safety Precautions and unit number of the mounted Unit (PLC CPU Bus Unit or Special I/O Unit) or the node address of the Component (DeviceNet Master/Slave or CompoWay/F Slave), and be sure that these operations can be performed safely for the current status of the node (Unit or Component): •...
  • Page 22: Application Precautions

    DeviceNet • Enable the scan list to before operating the system. • When adding a new node to the network, make sure that the baud rate is the same as other nodes. • Use specified communications cables.
  • Page 23 Not doing so may result in malfunction or damage. • When transporting a Board or Card, use the special box in which it was shipped to protect the LSIs and ICs from being damaged. Also do not subject the Board or Card to excessive vibration or shock.
  • Page 24 Application Precautions • If incorrect data link tables or parameters are set, injury may result due to unexpected operation of the system. Even if the correct data link tables and parameters have been set, do not start or stop data links before verifying that there will be no adverse influence on the system.
  • Page 25: Operating Environment Precautions

    !Caution Do not install in the following locations: • Locations subject to direct sunlight • Locations subject to temperatures or humidity outside the range specified in the specifications • Locations subject to condensation as the result of severe changes in temperature •...
  • Page 26: Guide To Version Upgrade

    Guide to Version Upgrades Guide to Version Upgrades The following table shows the changes in the upgrade from CX-Integrator Ver. 2.3 to Ver. 2.4. Item Previous (Ver. 2.3) Ver. 2.4 Not supported. Support for Windows 7 Supported. The following table shows the changes in the upgrade from CX-Integrator Ver.
  • Page 27 CompoWay/F network the CompoWay/F network transferred to address the PC, that network address will be displayed.) The following table shows the changes in the upgrade from CX-Integrator Ver. 1.1 to Ver. 2.0. Item Previous (Ver. 1.1) Ver. 2.0 System overview showing Not supported.
  • Page 28 Guide to Version Upgrades The following table shows the changes in the upgrade from CX-Integrator Ver. 1.0 to Ver. 1.1. Item Previous (Ver. 1.0) Ver. 1.1 Ethernet network PING test Not supported. Echoback test between nodes on Not supported. Yes. (Response time can be Ethernet, Controller Link, measured.)
  • Page 29: Section 1 Overview

    Communications Section 1 Overview This section provides an overview of the CX-Integrator and describes CX-Integrator menus and connections.
  • Page 30: The Cx-Integrator

    Overview The CX-Integrator is a Programming Device software package that enables reading the PLC's network and serial network configuration from a personal computer via an online connection. This enables easily performing many operations, such as monitoring the connection status of various networks, setting parameters, and diagnosing networks.
  • Page 31 The network/serial communications configuration of a PLC other than the one originally connected to online to can be set as the target. The PLC that was originally connected to online (called the relay PLC, see note 1), is relayed through to connect to another PLC (called the target PLC, see note 2) to switch the online connection.
  • Page 32: Functions According To Network

    PLC. When running the CX-Integrator on Windows Vista or Window 7, an online connection will not be possible to the relay PLC even if communications for one of these networks is selected. If FinsGateway is selected, connection will not be possible to a DeviceNet, CompoNet, or CompoWay/F network.
  • Page 33: Accessible Network

    1-1-4 Accessible Network 1-1-4 Accessible Network The network configuration of the target PLC (i.e., either the relay PLC or a PLC connected to the relay PLC) can be uploaded and monitored for each of the following networks. Accessible Networks Network...
  • Page 34 Note: As an exception, local network tables are not required even when more than one Network Communications Unit is mounted in the following situation: Access is possible without a local network table when connecting online to the target PLC...
  • Page 35: Communicating Across Network Layers

    1-1-5 Communicating Across Network Layers If relay network routing tables are set in the CPU Units of the PLCs, a PLC on a different network layer than the network of the PLC connected to the CX-Integrator can be set as the target PLC to enable uploading, saving, and comparing the network configuration of the target PLC.
  • Page 36: Specifications

    Note 1: To connect the computer running CX-Integrator directly as a CompoWay/F slave, set the Device type to CompoWay/F Device. Note 2: When using a pre-Ver. 1.1 CS1D-H CPU Unit, use it as if it were a CS1H-H CPU Unit.
  • Page 37 FinsGateway When running the CX-Integrator on Windows Vista or Windows 7, an online connection will not be possible to the relay PLC even if communications for one of these networks is selected. If FinsGateway is selected, connection will not be possible to a DeviceNet, CompoNet, or CompoWay/F network.
  • Page 38 Note: The CS/CJ-series PLC must have a lot number of 030201 or later (manufactured 1 February 2003 or later) to start the CX-Designer and transfer screen data to an NS-series PT from the CX-Designer through the PLC. The following PLCs can be used: CS1G-H, CS1H-H, CS1D-S, CJ1M, or CJ1H-H.
  • Page 39 Select “USB (Toolbus)”. Note: Accessing PLC Communications Across Network Layers If relay network routing tables are set, a PLC on a different network layer than the network of the PLC connected to the CX-Integrator can be set as the target PLC.
  • Page 40: Files Created By The Cx-Integrator

    Verification functions Verifying communications/network configurations Verifying component parameters Operations The following operations are possible for the CPU Unit at the target PLC. Creating, editing, and transferring I/O tables Displaying current errors and error logs Changing the operating mode Transferring or verifying a manually set data link table...
  • Page 41 FINS local routing Routing tables of the target PLC table files (.rtg, .rxg) Note 1: These are the same as the FINS local routing table files (.rtg, .rxg) (See note 2.) created with the CX-Net. Files created with the CX-Net can be imported.
  • Page 42: Installation

    Installation Installation The CX-Integrator is installed from the CX-One Installer. Refer to the CX-One Ver. 4. Setup Manual (W463) for details. 1-14...
  • Page 43: Plc Connecting Cables

    PLC Connecting Cables 1-4-1 Direct Serial Connections to a PLC When connecting the computer running the CX-Integrator directly to a PLC using a serial line, make the connection correctly using the following Connecting Cables and connection diagrams. Connecting Cables to CS/CJ-series PLCs...
  • Page 44 Connection to RS-232C Port XW2Z-@@@S-@@ RS-232C cable (listed above) CS1W-CN118 Peripheral port Note The following connection methods can be used when connecting an CQM1-CIF01/02 cable to a peripheral port on a CS/CJ-series PLC. Network type Computer (serial Unit Unit port Computer...
  • Page 45 Connecting the PLC Using a USB Port on the Computer A USB port on the computer can be used to connect the computer running the CX-Integrator to a CS/CJ-series PLC. To do so, connect the computer to the PLC as shown below using a CS1W-CIF31 USB-Serial Conversion Cable.
  • Page 46 USB A-plug connector, male CS1W-CIF31 D-sub connector (9-pin male) ● CS/CJ-series PLCs (See note.) D-sub connector C peripheral connector CS/CJ peripheral connector (9-pin female) Peripheral port Recommended cable: CQM1-CIF02 CS1W-CN114 Note: Only a Host Link connection is possible for CS/CJ-series PLCs. 1-18...
  • Page 47 XW2Z-200S-CV/500S-CV D-sub connector CS/CJ peripheral XW2Z-200S-V/500S-V (See note.) (9-pin female) connector CS1W-CN118 Note: Only a Host Link connection is possible for CS/CJ-series PLCs. • Using the XW2Z-200S-CV/500S-CV or XW2Z-200S-V/500S-V Connecting Cable for RS-232C USB A-plug connector, male CS1W-CIF31 D-sub connector...
  • Page 48 PLC Connecting Cables 1-4-1 Direct Serial Connections to a PLC Connecting Cables for CP-series PLCs Connecting to USB Port in CPU Unit Using Commercially Available USB Cable Unit Port at Computer Port at Network type Model Length Remarks Unit computer...
  • Page 49: Connecting Cj-Series Cj2 Cpu Units, Cp-Series Plcs And Nsj-Series Controllers Using Commercially Available Usb Cable

    A computer running the CX-One can be connected to the peripheral USB port on a CJ-series CJ2 CPU Units or a CP-series PLC or to the USB connector (SLAVE) on an NSJ-series Controller using commercially available USB cable. The procedures are provided in this section.
  • Page 50 Connecting CJ-series CJ2 CPU Units, CP-series PLCs and NSJ-series Controllers Using Commercially Available USB Cable CP-series PLCs The peripheral USB port (conforming to USB 1.1, B connector) is a dedicated port for connecting Support Software, such as the CX-One (e.g., CX-Programmer). NSJ-series Controllers...
  • Page 51 Windows 2000, Vista, or 7 1. Turn ON the power supply to the PLC and connect the peripheral USB port on the PLC to the personal computer using a USB cable. The USB driver will be automatically installed when the cable is connected.
  • Page 52 If the software cannot be installed automatically, refer to Installing a Specified USB Driver later in this section. If the installation media is not inserted or the USB device driver is installed for another port, a Driver List Dialog Box will be displayed. Make sure that the newest driver is selected and click the Next Button.
  • Page 53 If the USB driver cannot be installed automatically, use the following procedure to install it. Windows Vista or Windows 7 1. Turn ON the power supply to the PLC and connect the peripheral USB port on the PLC to the personal computer using a USB cable. 1-25...
  • Page 54 Connecting CJ-series CJ2 CPU Units, CP-series PLCs and NSJ-series Controllers Using Commercially Available USB Cable 2. The following dialog box will be displayed. Select Locate and install driver software (Recommended). 3. The following dialog box will be displayed. Select I don’t have the disc. Show me other options. 1-26...
  • Page 55 Next Button. C:\Program Files\OMRON\CX-Server\USB\wind2000_XP\inf 5. Ignore the following dialog box if it is displayed and select Install this driver software anyway. 6. The following dialog box will be displayed when the driver software has been installed successfully.
  • Page 56 Using Commercially Available USB Cable Windows XP 1. In the Found New Hardware Wizard Dialog Box, select the Install from a list or specific location (Advanced) Option and click the Next Button. 2. The following dialog box will be displayed. Click the Browse Button for the Include this location in the search Field, specify C:\Program Files\OMRON\CX-Server\ USB\win2000_XP\Inf, and then click the Next Button.
  • Page 57 Click the Finish Button. Windows 2000 1. Turn ON the power supply to the CPU Unit, and connect USB cable between the USB port of the computer and the peripheral (USB) port. After the cable has been connected, the computer will automatically recognize the device and the following message will be displayed.
  • Page 58 3. The following dialog box will be displayed. Select the Search for a suitable driver for the device (recommended) Option and then click the Next Button. 4. The following dialog box will be displayed. From the list in the dialog box, select the Specify location Checkbox and then click the Next Button.
  • Page 59 Connecting CJ-series CJ2 CPU Units, CP-series PLCs and NSJ-series Controllers Using Commercially Available USB Cable 7. After the driver has been successfully installed, the following dialog box will be dis- played. Click the Finish Button. Checking after Installation (Reference Information) 1.
  • Page 60 Connecting CJ-series CJ2 CPU Units, CP-series PLCs and NSJ-series Controllers Using Commercially Available USB Cable Re-installing the USB Driver If the USB driver installation fails for some reason or is cancelled in progress, the USB driver must be reinstalled. Checking USB Driver Status 1.
  • Page 61 Connecting CJ-series CJ2 CPU Units, CP-series PLCs and NSJ-series Controllers Using Commercially Available USB Cable 2. Click the Reinstall Driver Button. The Hardware Update Wizard Dialog Box will be displayed. Install the driver software using the procedure described in Installing the USB Driver.
  • Page 62: Window Descriptions

    One of the following windows will appear when the CX-Integrator is started. Offline Window Workspace Window Network Configuration Window Note: The Component List Window and Output Window are not displayed by default. They can − be displayed using the View Windows Menu.
  • Page 63 The Online Connection Information Window displays the online/offline status and the Relay PLC’s communications settings. When online, the target PLC will be displayed in a tree structure with all of the Communications Units and ports that belong to it. Online Operation The target PLC and Communication Units/ports mounted to the target PLC will be listed below the relay PLC.
  • Page 64 Communications Unit and Port Information for Target PLC The following CPU Unit built-in serial ports, Inner Boards, and Communications Units (referred to here as Communications Units/Ports) that are part of the target PLC are displayed under TargetPLC in directory tree format.
  • Page 65 Communications Unit name (CPU Unit for CPU Unit built-in serial ports) Note: If an online connection is made to the relay PLC, that PLC will be both the relay PLC and the target PLC. The Communications Units mounted in the relay PLC will be displayed in the Online Connection Information Window.
  • Page 66 Unit/port only when it is connected. Access is not possible when disconnected. Note: To connect the computer (CX-Integrator) directly to a CompoWay/F Slave through a serial connection, select CompoWay/F Device as the PLC model. Offline Displays Relay PLC Communications Settings Network Type COM Port No., Baud Rate, Parity, Data...
  • Page 67 For direct network connections, any FINS destination network (1 to 127) and node addresses can be set. (If routing tables are registered in the PLCs on the networks, specifying a PLC on any network other than the network that is directly connected to is also possible.
  • Page 68 2. Executing online operations except for “connect” (see note) in a window other than the Network Configuration Window: A dialog box will be displayed to notify of a display update. Click the OK Button to update the Online Connection Information Window display. Then execute the online operation again.
  • Page 69 Network type Network name The icon to the left of the network that is currently connected and can be accessed will be either With the CX-Integrator, only one Communications Unit/port can be accessed at any one time.) To enable accessing a network, right-click on it and select Connect.
  • Page 70 Network Configuration Window When the network configuration is uploaded online from the target PLC, the network configuration will be displayed in this window. If a network is inserted offline, the new network will be displayed in the Network Configuration Window.
  • Page 71 (See note.) Other component No border Note: The relay PLC will remain the target PLC with the green border until another node (PLC) is specified as the target PLC by selecting Connect to this PLC. Offline (for DeviceNet or CompoWay/F Only)
  • Page 72 Note The same functions can be performed by right-clicking in the window and selecting from the Edit or Component Menu. If the mouse pointer is moved to a component, a description of the component will be displayed in a pop-up.
  • Page 73 System Overview and selecting Network View Setting. Select a network and click the Up and Down Arrows to change the display order. You can also clear the Hide CompWayF and NTLink Networks Option so that serial communications for CompoWay/F and NT Links are displayed as networks.
  • Page 74 Window Descriptions 1-5-2 Main Window Property Window The Property Window displays the properties of the selected component, network, or project. Components Select existing components from the pull-down list. Component Information. • Model Name: Unit model No. • Category: PLC, etc.
  • Page 75 Components are listed in the Parts List. A component can be added to the network just by selecting the component in the Parts List and then dragging and dropping it in the Network Configuration Window. There are lists on the CPS, EDS (DeviceNet), and DTM (CompoNet) Tab Pages.
  • Page 76 The Parts List Pane shows components installed in DTM. The components are organized by both vendor and device type in a directory tree format. Select the device in whichever directory is easier to use. A component can be added by selecting the desired component from the Parts List Pane and then dragging and dropping it in the CompoNet Network Configuration Window.
  • Page 77: Menus

    Comment Saves I/O comments in a DeviceNet Component list CSV-format file. only Export Network As V1.0 Exports the data to a file that can All networks be read by CX-Integrator version except 1.0. DeviceNet Print Preview Displays a printing preview.
  • Page 78 Properties Displays the properties of the selected project, network, component, or EDS file. Insert Network Adds a new virtual network to the Network Configuration Window offline. Component Adds the component selected in the Component List Window to the Network Configuration Window offline.
  • Page 79 Transfer [PC to Downloads all component Network] parameters or network parameters from the virtual network on the computer to the actual network. Transfer Uploads the network configuration [Network to PC] and all component parameters or...
  • Page 80 Start Routing Table Starts the Routing Table Component. NT Link tool Auto online setting Automatically detects an NT Link only NS-series PT connected serially via an NT Link to a CS/CJ-series PLC. DeviceNet Generic parameter Sends an explicit message. DeviceNet tool setting...
  • Page 81 Deletes an EDS file from the EDS DeviceNet list. only Save Saves an EDS file from the EDS DeviceNet list in a file with a different name. only Find Searches for the specified EDS DeviceNet file in the EDS list. only...
  • Page 82: Pop-Up Menus

    Pop-up Menus Online Connection Information Window Pop-up Menu for the Relay PLC's Communications Settings The following pop-up menu will be displayed if you right-click the relay PLC’s communications settings line (starting with Offline) in the Online Connection Information Window. Pop-up menu item...
  • Page 83 Menus 1-6-2 Pop-up Menus Pop-up Menu for Communications Units/Ports under TargetPLC Online Online Pop-up menu Description Offline Connected connected Transfer [Network to PC] Uploads the communications configuration of the selected Communications Unit/port. Connect Enables accessing the selected Communications Unit/port. Start Data Link Starts the Data Link Component.
  • Page 84 (Unit) with the unit version supported by the software on the computer. Also changes the unit version of the component on the computer to match the unit version of the actual component (Unit). Add To Network Add the selected PLC to another network.
  • Page 85 Load Reads the selected PLC’s parameters from a file. Save Saves the selected PLC’s parameters. Toggle Position Moves a component’s icon above or below the network line. Copy Copies the selected PLC. Paste Pastes the selected PLC in the network.
  • Page 86 Resets a device on the network. Maintenance information Displays the maintenance information for the selected device. Resister to another Registers the current device to the scan list in component another device. Export Exports I/O comments in CSV format Comment list (supported devices only).
  • Page 87 Loads parameters from a device parameter file. Save Saves device parameters to a file. Add To Network (master only) Adds the PLC to which the selected master is connected to another network. Jump to Other Network Switches the display to another network to...
  • Page 88 Menus 1-6-2 Pop-up Menus Workspace Window Pop-up Menu for the Project Name or Network Online Pop-up menu Selected Description Offline Connected connected Open Network Displays the network configuration of the selected network in the Network Configuration Window. Insert Network Project name Adds a new network on the computer.
  • Page 89 Parameter Edit Network Edits the network parameters of a virtual Controller Link network on the computer (Controller Link or SYSMAC Link only). Load Reads the network parameters from a network parameter file to the selected network. Save Writes the selected network’s network...
  • Page 90: Toolbars

    Menus 1-6-3 Toolbars 1-6-3 Toolbars The most commonly used functions are provided as icons on toolbars. The following menu commands are allocated to these icons. Icon Description Actual menu command Creates a new project. File - New Opens a project file.
  • Page 91 Adds new EDS files. Tools - EDS file - Install EDS Deletes EDS files. Tools - EDS file - Delete Saves a new EDS file with a new EDS file Tools - EDS file - Save name. Inserts components. Insert - Component Searches for EDS files.
  • Page 92 Menus 1-6-3 Toolbars 1-64...
  • Page 93: Section 2 Basic Operations

    Communications Section 2 Basic Operations This section describes the basic operations used for the CX-Integrator.
  • Page 94: Basic Procedures

    PLC can be uploaded. PLCs with Only One Network Communications Unit If the relay PLC (which is the target PLC when the online connection is first made) has only one Network Communications Unit (see note), it is not necessary to create and transfer a local network table.
  • Page 95 CPU Unit. An EtherNet/IP Unit, built-in EtherNet/IP port, or Ethernet Unit can be used. Note 2: The local network table is one of the routing tables. It lists the unit numbers and net- work addresses of the network Communications Units.
  • Page 96 Network Communications Unit, except in the case outlined below. Even if an online connection is made to a PLC, it will not be possible to upload or download the network configurations unless a local network table is registered.
  • Page 97 • Always create local network tables and transfer them to the relay PLC and target PLC. • When specifying a target PLC in another network, register both local network tables and re- lay network tables in all of the PLCs on the path between the relay PLC and target PLC. Overall Procedure Start the CX-Integrator.
  • Page 98 Reading Network Configurations and Parameters from Actual Networks and Saving Them to Files Online To simplify maintenance, the target PLC’s actual network configuration and component parameters can be uploaded and saved in a project file (.cin) for each network. Overall Procedure Start the CX-Integrator.
  • Page 99 Basic Procedures Designing DeviceNet, CompoNet, and CompoWay/F Networks Offline Networks can be designed on the CX-Integrator even before they have been installed. Parameters for individual DeviceNet and CompoNet masters and slaves can be set. Parameters for individual CompoWay/F slaves can be set.
  • Page 100 Reading Saved Parameters and Downloading Them Online to DeviceNet, CompoNet, or CompoWay/F Components All of the component parameters on a network can be downloaded to the actual components from a previously saved project file (.cin) after the network has been installed.
  • Page 101 Directly Connecting the Computer Running CX-Integrator to CompoWay/F Components without Going Through a PLC Uploading the CompoWay/F network configuration is possible through a direction connection from the CX-Integrator to CompoWay/F protocol components using RS-232C or RS-485 communications without going through a PLC. Component parameters can also be set.
  • Page 102: Connecting Online To The Relay Plc

    Note: If an online connection is made to the relay PLC, the same PLC will be both the relay PLC and the target PLC. Once the relay PLC has been connected to online, the network con- figuration can be uploaded or the target PLC can be changed to a different PLC.
  • Page 103: Procedures

    An online connection to the relay PLC can be established automatically or manually. Automatic Online Connection For automatic connections, the communications settings are automatically set to those of the PLC (i.e., the user does not have to make any communications settings on the computer). −...
  • Page 104 PLC are the same, the Unit that was connected immediately before will be auto- matically connected again the next time online. Note 3: When connecting online for the first time after opening a project, the target Unit will be determined in the following order.
  • Page 105 Connecting Online to the Relay PLC 2-2-2 Procedures Manual Online Connections For a manual connection, the communications settings of the relay PLC on the computer are set first before an online connection is made. Communications Settings − Select Network Communication Settings from the menu bar, click the communications setting icon.
  • Page 106 Note: The Toolbus (peripheral) protocol is faster than the SYSMAC WAY protocol. Serial connections are generally made using this network type. Toolbus Select to directly connect the computer to a CJ2 CPU Unit (USB port) with a USB cable. (See note 1.) SYSMAC WAY Select to connect the computer with a direct serial (See note 4.)
  • Page 107 (USB port)”. Note 2: CJ2 CPU Unit cannot select this network type. Note 3: When connecting online with a SYSMAC CS1 Board, specify one of the device types in parentheses. CS1 Board can be selected as the network type only when one of these device types is selected.
  • Page 108 For automatic baud rate detection with the Toolbus protocol, the baud rate setting on the computer is used and the serial port on the CPU Unit is set to the same value. For automatic online connections, the communications settings (device type, serial...
  • Page 109 Set the network address of the Ethernet network connected to the computer. Set the node address of the connected Ethernet Unit. Set the network address of the Ethernet network connected to the PLC to which the connected Ethernet Unit is mounted. 2-17...
  • Page 110 Click the Driver Tab and set the following settings as required. Select whether FINS node addresses are to be automatically generated from IP addresses on the computer. This option is selected by default. Clear this selection to enable using an IP address table or combined method.
  • Page 111 IP conversion for any node on Ethernet (i.e., an Ethernet Unit or personal computer) is set for either the IP address table method or the combined method, the IP address table at the CX-Integrator (personal computer) must be preset. (For details on IP conversion, refer to the Ethernet Units Construction of Networks Operation Manual.)
  • Page 112 It need not be input for nodes for which the conversion is set for automatic generation (either dynamic or static). Note If the IP address table is not set correctly, the target node may not be displayed when network uploads are executed. 2-20...
  • Page 113 The Online Icon will be displayed in the Online Connection Information Window. The following will appear in the status bar at the same time: With the CX-Integrator version 2.1 or higher, the CX-Integrator can be directly...
  • Page 114: Cpu Unit Troubleshooting

    Right-click the desired target PLC in the Online Connection Information Window and select Error Log. Refer to 2-4 Switching the Target PLC for details. The PLC Errors Dialog Box will be displayed. Check the errors that have occurred in the CPU Unit and perform any required error processing.
  • Page 115: Uploading Network Configurations And Checking For Communications Unit Errors

    Information Window and select Connect from the pop-up menu. Accessing the Communications Unit or port will be enabled and the icon to the left will change to (If the network has been uploaded but a network address is not displayed (Net(-) displayed), it will be necessary to select the desired network in the Workspace Window, right-click, and select Connect.)
  • Page 116: Nt Link Connection Auto-Detect Function

    Port baud rate: Same as NS-series PT Maximum unit number in NT Link Mode: Same as NS-series PT unless it is set to 0, in which case 1 will be used. Uploading the Network Configuration Connected to a Communications Unit...
  • Page 117 1) For networks other than Ethernet: The dialog box for selecting the data to be transferred will be displayed. The selection is fixed for DeviceNet. When using CompoNet, the following dialog box will be displayed.
  • Page 118 If nodes in the specified range do not exist, it will take 20 seconds per node to search for it. If All (1 to 254) is selected, it will take up to approximately 85 minutes for the transfer to be completed. The transfer will also take longer if a maximum address is entered that is higher than any of the existing node address.
  • Page 119: Overview

    2-3-2 Procedure upload is executed, an OMRON FINS command is sent to all nodes in the segment. Therefore, if a node exists for something other than an OMRON Ethernet Unit or FinsGateway, the FINS command will not be received at that node and unexpected operation may occur.
  • Page 120: Procedure

    If different networks are uploaded when connected to different PLCs, a single PLC can sometimes be registered as different PLCs in the Network Configuration Windows. If this happens, the Combine two PLCs menu item can be used to combine the two PLCs into the same PLC.
  • Page 121 • As PLC3 in the N1 (Ethernet) network • As PLC4 in the N2 (Controller Link) network Here, for example, PLC4 can be eliminated and combined with PLC3 as the same PLC. The procedure is as follows: 1. Go offline after uploading the networks, right-click PLC3 in network N1 (Ethernet), and select Combine two PLCs.
  • Page 122: Procedure

    The following Combine two PLCs Dialog Box will be displayed. • Other networks registered in the project will be display at the top of the dialog box. • All PLCs with the same model of CPU Unit on the selected network will be dis- played at the bottom of the dialog box.
  • Page 123: Checking And Correcting Communications Unit Errors

    Right-click the target PLC in the Network Configuration Window and select Status/Error of Communication Unit from the pop-up menu. The PLC Unit Status Dialog Box will be displayed. In this example, a Controller Link Unit is selected. Note: The Communications Unit’s status and error information can be saved as a CSV file by clicking the Save Button, so the Communications Unit’s status at that point can be read...
  • Page 124 Error. Refer to the Communications Unit’s Operation Manual or details on individual errors. Note: The Communications Unit’s error log can be saved as a CSV file by clicking the Save Button, so the Communications Unit’s error log at that point can be read from the CSV file later and analyzed.
  • Page 125: Switching The Target Plc

    When an online connection is made from the CX-Integrator to the relay PLC, initially the same PLC will be both the relay PLC and the target PLC and the Communications Units and ports of the relay PLC will be displayed in the Online Connection Information Window.
  • Page 126 Switching the Target PLC 2-4-2 Procedure 3. Right-click a PLC on the network and select Connect to this PLC from the pop-up menu. Network Configuration Window Right-click the PLC for which the network structure is to be uploaded and select Connect to this PLC from the pop-up menu.
  • Page 127: Creating Virtual Network Configurations Offline

    2. Select CompoWay/F and click the Next Button. 3. Enter the name of the network and click the Finish Button. 4. Select a component from the CPS Tab Page in the Component List Window and drag and drop it in the Network Configuration Window.
  • Page 128 Creating Virtual Network Configurations Offline 2-5-2 Procedure Drag and drop 5. The following Component Settings Wizard will be displayed. 6. Enter the component name and click the Next Button. 2-36...
  • Page 129 Creating Virtual Network Configurations Offline 2-5-2 Procedure 7. Enter the node address and click the Next Button for a PLC click the Finish Button for a CompoWay/F Slave (e.g., Temperature Controlled. 8. For a PLC, select the port to connect.
  • Page 130 2-5-2 Procedure Select the unit number of the Unit that was selected click the Next Button. Select the port to connect to CompoWay/F and click the Finish Button. • To connect CompoWay/F to a serial port on a Serial Communications Board, select the Board with the port to connect CompoWay/F and click the Next Button.
  • Page 131 Click the Next Button. Click the port to connect to CompoWay/F and click the Finish Button. 9. The component will be registered in the Network Configuration Window as shown below. In this example, a PLC CPU Unit and two Temperature Controllers have been...
  • Page 132 Creating Virtual Network Configurations Offline 2-5-2 Procedure DeviceNet Networks Adding the Master − 1. Offline, select Insert Network. The Network/Component Settings Wizard will be displayed. 2. Select DeviceNet and click the Next Button. 2-40...
  • Page 133 2-5-2 Procedure 3. Enter the name of the network and the network address and click the Finish Button. 4. Select a device (component) from the EDS (DeviceNet) Tab Page in the Component List Window and drag and drop it in the Network Configuration Window.
  • Page 134 Creating Virtual Network Configurations Offline 2-5-2 Procedure Adding Slaves Slaves are added just like the master was, by dragging and dropping them from the Component List Window. Drag and drop Example of Devices Registered by Dragging and Dropping Note Devices can also be added to the network by right-clicking the device in the Compo- nent List Window and selecting Add To Network from the pop-up menu.
  • Page 135 3. Enter the name of the network and click the Next Button. 4. Select the Master Unit and CPU Unit to use, select the Machine Number (i.e., the unit number) of the Master Unit, and then click the Next Button.
  • Page 136 If a slave that is not allowed is added when the Master Unit is in Communications Mode 0 (a Bit Slave or a Word Slave at node address 8 or higher), the dialog box shown be- low will be displayed requesting that the user check the communications mode.
  • Page 137: Changing Node Addresses

    Change Node Address from the pop-up menu. The Change Node Address Dialog Box will be displayed. 3 Change the node address to a value between 0 and 63 and click the OK Button. The node address will be changed.
  • Page 138: Editing Components (Devices)

    4 The following dialog box will be displayed to confirm deletion. Click the Yes Button to delete the selected component. If a slave device that is registered in the master device is deleted, the registration in the master device will be deleted and the slave will be deleted from the scan list automatically.
  • Page 139 Network Configuration Window. 1 Right-click the device to be moved and drag it. 2 Drop the device at the new location where it is to be displayed. 3 The new device will be moved to the new display location.
  • Page 140 Device comments can be displayed by moving the mouse pointer to the locations of devices in the Network Configuration Window. Note Device comments will be displayed when devices are pointed at on a network. In the detailed display, comments are displayed in the Comment column. 2-48...
  • Page 141: Manipulating Component Parameters

    Overview With the CX-Integrator, the parameters on components in the Network Configuration Window can be set. They can also be uploaded from, downloaded to, and compared with the parameters of the components on the actual network. Applicable Components and Parameters The components and parameters that can be manipulated are listed in the following table.
  • Page 142: Procedure

    Select the appropriate value for each item from the pull-down lists and click the OK Button to change the settings. Note 1: The items displayed here are the same ones as displayed on the Peripheral Port, Host Link Port, and FINS Protect Tab Pages of the PLC Setup in the CX-Programmer.
  • Page 143 Transfer [PC to Unit] in the Edit Parameter Dialog Box. The parameters will be downloaded to the actual component. Depending on the Unit, it may be necessary to restart in order to make the downloaded Note settings effective. Click the OK Button in the verification dialog box, and restart the Unit.
  • Page 144 2-6-2 Procedure 3. The results of comparing the unit version of the component on the computer to the unit version of the actual component will be displayed as shown below. •The following display will appear if the unit version of the component on the computer is newer than the unit version of the actual component.
  • Page 145 Manipulating Component Parameters 2-6-2 Procedure A list will be displayed of the Units to which the parameters will be downloaded. Clicking the OK Button will start the transfer. Clicking the Cancel Button will cancel the transfer. For DeviceNet, the following dialog box will be displayed.
  • Page 146: Uploading, Downloading, And Comparing Network Parameters

    Workspace Window and select Parameter - Compare from the pop-up menu. The parameters set for the virtual network on the computer will be compared with those set in the actual network with the same network address.
  • Page 147: Comparing Network Configurations

    1. Right a network in the Workspace Window and select Connect from the pop-up menu. Accessing the network will be enabled and the icon to the left will change to If the network has been uploaded but a network address is not displayed (Net(-) displayed), it will be necessary to select the desired network in the Workspace Window, right-click, and select Connect.
  • Page 148: File Operations

    20 relay routing tables can be registered. Note: A project file that contains a CompoNet Network cannot be used with CX-Integrator version 2.1 or lower. Upgrade to CX-Integrator version 2.2 or higher. 2-56...
  • Page 149: Procedures

    The Network Structure (npf). Export DeviceNet List (CSV) Dialog Box will be displayed. 3. Select the type of file to be saved (.npf or .csv) and click the Save Button. Project Files in the CX-Integrator Version 1 Format (*.cin) 1. Select File – Export – Export Network As V1.0.
  • Page 150 2. Select Component Parameter Save from the menu bar. A dialog box to specify the folder and file name in which to save the component parameters will be displayed. 3. Specify the folder and file name and click the Save Button.
  • Page 151 Scan list information in ONC master parameter setting file format 4 If valid devices are registered in the scan list, a dialog box will be displayed to specify the folder and file name. 5 Specify the folder and file name and click the Save Button.
  • Page 152: Target Plc Online Operations

    Starts the Routing Table Component. Echoback test Starts an echoback test to check the network communications between PLC nodes status. I/O Tables (Online Only) If IO table is selected, the PLC I/O Table Dialog Box (I/O Table Component) will be displayed. 2-60...
  • Page 153 If Error Log is selected, the PLC Errors Dialog Box will be displayed. Errors Tab: All current errors are displayed. Error Log: A total of 20 error records will be registered in the error log (or up to the maximum number of error records supported by the PLC).
  • Page 154: Starting Specified Applications

    Start Only from the pop-up menu. 2. The following dialog box will be displayed. Select any of the applications to display an explanation of that application. 3. To start a special application, select it and click the OK Button. 2-62...
  • Page 155: Printing

    This section describes the procedure for printing device parameters and comments from the currently displayed network configuration. Use the following procedure to print. 1 To print only part of the device parameters or comments, select the devices for which to print. −...
  • Page 156 2-12 Printing 2-64...
  • Page 157: Section 3 Routing Tables

    Communications Section 3 Routing Tables This section describes how to set the routing tables.
  • Page 158: Routing Table Overview

    • The network address must be greater than zero. (See note.) Note: Setting a network address of 0 indicates to the computer that a local network table is not set in the PLC. In this manual, network address 0 is called the local network address.
  • Page 159 Note: The extended table format is supported only for CS/CJ-series CPU Units with unit version 4.0 or later. Example: In this case, the tables have been set to route communications from network address 1 (local node: PLC1) to network address 3 (destination node: PLC4).
  • Page 160: Network Conditions That Require Routing Tables

    3-1-2 Network Conditions That Require Routing Tables Setting Example The following example shows the routing tables that route communications from PLC1 (network address 1, node address 1) to PLC4 (network address 3, node address 2). Relay node PLC2 Node address 3 (Unit number 0)
  • Page 161: Routing Table Setting Methods

    3-1-3 Routing Table Setting Methods Local Network Table Settings Required • A local network table is required when there is even one other node in the same network in which routing tables have been set already. • A local network table is required when there are two or more Network Communications Units (see note) mounted to a single CPU Unit.
  • Page 162: Routing Table File Types Supported By The Cx-Integrator

    Routing Table File Types Supported by the CX-Integrator The following two kinds of routing tables can be set in the CX-Integrator. When the routing tables have been set, they can be saved to a file and retrieved later. File name...
  • Page 163: Operating Procedures Prior To Routing Table Transfer

    Operating Procedures Prior to Routing Table Transfer This section describes the operating procedures necessary to create the routing tables for the first time up to the point where the files are transferred to the PLCs. Note When constructing the network, set FINS local routing tables in all nodes (CPU Units)
  • Page 164 Create the relay network table. Set the gateway counter. (CS/CJ-series CPU Units must be unit version 3.0 or later.) Click the SIOU Tab when the PLC routing tables are displayed, right-click the local PLC's icon, and select Set Gateway Counter from the menu.] Check the routing tables for errors.
  • Page 165 Create the relay network table. Set the gateway counter. (CS/CJ-series CPU Units must be unit version 3.0 or later.) Click the SIOU Tab when the PLC routing table is displayed, right-click the local PLC's icon, and select Set Gateway Counter from the menu.
  • Page 166 Read the routing tables from the network (from a PLC on network to the computer). Select Options –Transfer from PLC from the PLC routing table menu. Edit the FINS local routing tables (in the PLC routing tables) of each PLC in the network. Check the routing table for errors.
  • Page 167: Setting The Routing Tables

    PLC connected directly by a serial connection. 3-2-1 Routing Table Setting Example This section explains how to create and transfer the FINS local routing tables for the following network structure. Example: Routing from PLC1 to PLC3...
  • Page 168: Creating The Fins Local Routing Tables

    3-2-2 Creating the FINS Local Routing Tables 3-2-2 Creating the FINS Local Routing Tables This section shows how to set the routing tables (FINS local routing tables) for PLC1, which is connected directly to the CX-Integrator. Creating the Local Network Table Create PLC1's local network table online.
  • Page 169 Indicates the current node address and the Communications Unit’s name. 4. Click the Table View Tab at the bottom of the PLC Routing Table Window to switch to the Table View format. 5. Input the corresponding unit number and network address and click the OK Button.
  • Page 170 Displays the Routing Table Component's version information. Note 1: The Enable/Disable function is supported by C-series PLCs (Controller Link) only. Note 2: This command is supported only when connected to PLC with CS/CJ-series CPU Units with unit version 4.0 or later. 3-14...
  • Page 171 Creating the Serial Port's Local Network Table: A local network table can be created for the serial port in the CPU Unit or a Serial Communications Board or Unit (Version 1.2 or later) so that the serial port can be specified instead of the Communication Unit's unit number.
  • Page 172 Communications Unit's unit number. Click the SIOU Tab Note: For an Inner Board, the Special I/O Unit number of the Board itself is 225, but the Special I/O Unit numbers of the ports are 228 for port 1 and 229 for port 2.
  • Page 173 FD hex (253 decimal) RS-232C port FC hex (252 decimal) A Unit and the Unit's serial port cannot be registered in the local network table at the same time. Setting the Relay Network Table Set the relay network table for PLC1.
  • Page 174 When setting the relay network table in extended mode, set the table in the Table View Tab Page. A relay network table with more than 20 entries cannot be set in the Main View Tab Page or Overview Tab Page.
  • Page 175 2. The Enter SIOU Details Dialog Box will be displayed. Input the CPU SIOU (unit number) and local network address. Input the relay node address. Input the remote network address. The relay network table will be added to the PLC Routing Table (Main View). 3-19...
  • Page 176: Setting The Gateway Counter

    When GCT = 02 hex, up to 3 network layers can be crossed. When GCT = 07 hex, up to 8 network layers can be crossed. (The network must be configured for PLC models with the GCT set to 07 hex.)
  • Page 177 Overview Table View CS/CJ-series Units Version 2.0 The GCT (gateway counter) is fixed at 07 Hex. The GCT cannot be set for a maximum of 3 network layer crossings. The maximum number of network crossings is always 8 layers max.
  • Page 178 Version 2.0 and later CS/CJ-series Units cannot be included.) If other models are used, a routing error (end code 0501 to 0504 Hex) may occur in a relay PLC or the response may not be returned properly to the source node.
  • Page 179: Checking Routing Tables For Errors

    8 network layers (see note), including the local network. Applicable Networks: Not all networks can be crossed up to 8 times. Only the following two kinds of networks can be crossed up to 8 times. (The networks can be crossed in any combination.)
  • Page 180: Transferring Routing Tables To A Directly Connected Plc

    1. Verify that PLC1 is connected directly to the CX-Integrator and online, display the PLC Routing Table Window, and select Options – Transfer to PLC. 2. The following dialog box will be displayed to confirm the transfer. To proceed with the transfer to the PLC, click the Yes Button.
  • Page 181 If routing tables are transferred to the PLC from a Programming Device, the CPU Bus Unit will be reset. The Unit is reset in order to read and enable the routing tables that were transferred. Before executing the routing table transfer, verify that no equipment will be damaged and it is safe for the CPU Bus Unit to be reset.
  • Page 182: Saving Routing Tables

    Saving Routing Tables Use the following procedure to save the created FINS local routing tables. The FINS local routing tables are saved in a file with the ".rtg" filename extension or the ".rxg" filename extension (see note). 1. Select File – Save Local Routing Table File in the PLC Routing Table Window.
  • Page 183: Printing Routing Tables

    3-2-9 Printing Routing Tables 3-2-9 Printing Routing Tables Use the following procedure to print the created routing tables. 1. Select File – Print in the PLC Routing Table Window. Example Printout (PLC1 Table View) Example Printout (PLC1 Main View) 3-27...
  • Page 184: Transferring Routing Tables To A Network Plc Through

    The PLC must have a CS/CJ-series CPU Unit with unit version 4.0 or later. Note 2: The FINS local routing tables can be transferred only to a PLC in the same network as the PLC connected directly by a direct serial connection. The transfer cannot cross a network level to another network.
  • Page 185 3-2-10 Transferring Routing Tables to a Network PLC through a Direct Serial Connection 3. The PLC Routing Table Window will be displayed in the Main View format. 4. Select File – Open Local Routing Table File to read the saved FINS local routing table file.
  • Page 186 Select 2. 7. Select Options – Transfer to PLC. 8. The following dialog box will be displayed to confirm the transfer. Verify that it is all right to proceed with the transfer to the PLC, click the Yes Button. Note If routing tables were previously set in the target PLC, those tables will be overwritten with the routing table that is being edited.
  • Page 187 PLC. The output window is displayed if the PLC is connected online. Also, the output window can be displayed by selecting Window – Output in the PLC Routing Table Window. Display Example (When the Target PLC is Changed) Unit No.
  • Page 188: Maintenance After Network Configuration

    This capability allows the FINS local routing table set in each PLC to be read and edited through the network. In addition, the FINS local network tables set in each PLC can be saved together in a FINS network routing table file.
  • Page 189 3-3 Maintenance after Network Configuration 3-3-2 Editing the FINS Local Network Tables Note When the PLC is connected online, the display will show green and red indicators on the Units that indicate errors with Units registered in the routing tables. Green Indicator: Unit exists in routing tables.
  • Page 190 Tab and checking the node's icon in the project workspace. When the CX-Integrator is connected to a PLC on an Ethernet network, it may not be possible to read the routing tables from nodes other than the connected PLC. In this case, directly connect the CX-Integrator to the PLC to read and edit the local routing table.
  • Page 191 Save Button. Note When transferring the routing tables to a PLC, all CPU Bus Units in that node will be reset except for SYSMAC BUS/2 Masters. Verify that there will be no adverse effects on the system's equipment before transferring the routing tables.
  • Page 192 3-3 Maintenance after Network Configuration 3-3-2 Editing the FINS Local Network Tables 3-36...
  • Page 193: Section 4 Data Links For Controller Link And Sysmac Link

    Communications Section 4 Data Links for Controller Link and SYSMAC LINK This section describes how to set data links for Controller Link and SYSMAC LINK networks.
  • Page 194: Overview

    Automatic Settings Automatic settings can be used for simple data exchanges involving fixed allocations, when all nodes are set for the same send size and the same data is to be shared among all nodes in order of node address.
  • Page 195: Overview Of Procedure By Data Link Setting Method

    Online - Automatic Data Link Setup from the Data Link Component. 2) Directly set the software switches in the allocated DM Area words. Note: The settings in the DM Area can also be made from the Special I/O Unit settings in the I/O Table Window for CX-Programmer Ver.6.0 or higher.
  • Page 196: User Interface Overview

    Start Data Link cannot be selected if there is not a Controller Link Unit or SYSMAC LINK Unit mounted in the PLC that is connected online. Method 2: While offline, select Tools - Start Data Link from the menu bar and then select Controller Link or SYSMAC LINK.
  • Page 197 Downloads online data link tables from the computer to a PLC. Verify Node Compares data link tables generated by CX-Integrator with data link tables stored in the PLC. If they do not match, an error dialog box is displayed. Data Link Displays the operation and data link status of manually set data links.
  • Page 198 Delete Deletes data link tables. Verify Node Compares data link tables generated by CX-Integrator with data link tables stored in the PLC. If they do not match, an error dialog box is displayed. (10) Data Link Operation/Status Displays the operation and data link status of manually set data links.
  • Page 199 F8: Delete Node Deletes a node or communications area. To delete a node or link area from a node list, select the item from the list and then click F8: Delete Node. To delete a node or link area from a table, select the item from the table and then click F8: Delete Node.
  • Page 200: Manually Setting Data Links

    2) Select File - Open from the Data Link Component Window to read the data link tables. 3) Select Online - Transfer to PLC to transfer the data link tables from the computer to the PLC. Start the data links from the Data Link Component Window.
  • Page 201: Creating Data Link Tables

    Creating Data Link Tables 4-3-2 Creating Data Link Tables Create a data link table for each node registered in the CX-Server file that is read. Make the settings for (1) to (8) below. (1) Participating data link nodes (7) Receive...
  • Page 202 2. Node Editing Window Settings (7) Set receive sizes from remote nodes. (8) Set offsets. Note 1. It is possible to add or delete nodes from the participating data link nodes (1) using the Datalink Wizard. Select Table - Add Source Link.
  • Page 203: System Configuration Example

    DM700 DM800 The refresh sequence for nodes 1 and 2 is as follows: #1, #2, #3. For node 3, the order is #2, #1, #3. Node address 03 does not receive all of the data sent from node address 02. Rather, data from the 20 words (CIO 1240 to CIO 1259) beginning from the start address +10 words (i.e., the offset) is received in IR 300 to IR 319.
  • Page 204: Creating Data Link Tables Offline

    Datalink Wizard Operations 1 While offline, select Tools - Start Data Link. The Select Network Dialog Box will be displayed. 2 Select either Controller Link or SYSMAC LINK, and then click the OK Button. The Datalink Component Window will be displayed. 4-12...
  • Page 205 5 Set the addresses of the nodes that are to participate in the data links. In this case, input 1-3 to set node addresses 01 to 03. (To set node addresses 01, 02, and 04, for example, input 1,2,4.)
  • Page 206 Controller Link Units Operation Manual (W309). Data link status The data link status is contained in the 16 words (fixed) from CIO 1500 + 25 × unit CS/CJ Series number + 7 to 22 in the CPU Bus Unit Area.
  • Page 207 Sets CIO 1300 as the data link status start address start address. Start address 1300 9 Set node address 03 as shown in the following table, and then click the Next Button or press the Enter key. Item Data set Description −...
  • Page 208 Fast Datalink Wizard Settings Note It is possible to generate a table with all nodes set for the same PLC type and the same areas (using Fast Default Table Generation), and then to modify individual nodes in the Node Editing Window as required.
  • Page 209 : The arrows indicate the direction of data transfer. Send areas are indicated by ovals in order of the addresses of nodes participating in the data links. The same color indicates that data is shared among nodes. Therefore, with the number of participating nodes represented by n, one oval and n-1 rectangles are shown for each node.
  • Page 210 Note: The areas and start addresses that can be set for Controller Link data link status depend on the model of CPU Unit. If the start address is not set correctly, a data link table error will occur and the LNK indicator on the Controller Link Unit will flash. Refer to the Controller Link Unit Operation Manual for details.
  • Page 211 Setting Size (Send or Receive) and Offset • The send size can be set for the local node row by double-clicking in the Size cell. (The default is the size set by the Datalink Wizard.) For remote node rows, the receive size can be set.
  • Page 212 Specify send size. Offset cannot be changed. Note: With SYSMAC LINK, the send size can be set, but the receive size and the reception offset cannot. Therefore, the Area Specify Dialog Boxes are as shown in the following example diagrams.
  • Page 213 The node refresh sequence set for each node by the Datalink Wizard can be changed in the Node Editing Window. In the Node Editing Window, select the node for which the refresh sequence is to be changed. Change the node refresh sequence by either clicking F4: Move Up Area or F5: Move Down Area in the Function Bar, or pressing the F4 or F5 function keys.
  • Page 214 Deleting Nodes Added to the Data Links Select the node to be deleted from the Node Editing Window. Delete the node by clicking the F8: Delete Node Button in the Function Bar. !Caution If the node is deleted by clicking the Button in the Toolbar, the deletion will be executed immediately.
  • Page 215: Procedure Using Setup Example

    The data link data for the selected node address is displayed here. The data link table for node address 01, the node to be edited, is displayed as a list in the Node Editing Window on the right. Sends 30 words from the local node (node address 01), starting with CIO 01000 (i.e., CIO...
  • Page 216 F4 or F5 function keys. F5: Move Down Area 3 Double-click on the Offset cell, and input the data size to be offset. In this example, set the offset size to 10 words. With this setting, 20 words sent from node 01 will be received, starting from CIO 1000, and with an offset of 10 words (i.e., CIO 1010 to CIO 1030).
  • Page 217: Checking Data Link Tables

    Checking Data Link Tables 4-3-6 Checking Data Link Tables 1 Select Table - Validate Table in the Data Link Editor (Controller Link or SYSMAC LINK). The results of the check will be displayed as shown in the following illustration. 4-3-7 Printing Data Link Tables Follow the procedure below to print data link tables that have been generated.
  • Page 218: Saving Data Link Tables

    2 Input the file name (“Sample” in this example), and specify the location where the file is to be saved. Then click the Save Button. The data will be saved to a file with a .cl2 extension added to the file name (i.e., “Sample.cl2” in this case).
  • Page 219 Reading CSV Files Files in CSV format can be read to data link tables. 1 While offline, select Tools - Start Data Link from the CX-Integrator menu bar. The Select Network Dialog Box will be displayed. 2 Select Controller Link or SYSMAC LINK and click the OK Button. The Datalink Component Dialog Box will be displayed.
  • Page 220 4-3-9 Creating, Reading, and Writing CSV Files (Saving) 3 Select File - Open menu bar, and then select *.csv from the File of Type Field. Writing CSV Files (Saving) Once data link tables have been created, they can be written to CSV-format files.
  • Page 221 Creating, Reading, and Writing CSV Files (Saving) Tag name Description Set value <node- The node No. for the link. 1 to 62. An error will be generated <node> param> if an out-of-range value is set (Node No.) when a file is loaded.
  • Page 222 Manually Setting Data Links 4-3-9 Creating, Reading, and Writing CSV Files (Saving) Tag name Description Set value <area1> <start-type> Specify the area type for Link Same as for status area type. (Link Area 1 Area 1. type) <start-ch> The beginning word for Link...
  • Page 223 Manually Setting Data Links 4-3-9 Creating, Reading, and Writing CSV Files (Saving) An example text data configuration for a CSV file is shown below. Note: Commas are used for delineation. (They are added when there are blank cells.) 4-31...
  • Page 224: Reading And Data Link Tables

    Datalink Component (Controller Link) or Datalink Component (SYSMAC LINK) Window will be displayed. Note: Start Data Link cannot be selected if there is not a Controller Link Unit or SYSMAC LINK Unit mounted in the PLC that is connected online.
  • Page 225 Reading and Data Link Tables The data link tables will be read as shown below. Note: Be careful of the following point when reading a SYSMAC LINK data link table file (.slk extension) created by SYSMAC LINK Support Software. With SYSMAC LINK data link table files created by SYSMAC LINK Support Software (SLK files), there is no distinction made between C200H and CV-series PLC models.
  • Page 226: Transferring The Data Link Table

    3 Click the Yes Button. An error list will be displayed. 4 If there are no errors, click the OK Button. The data link tables will be transferred to all PLC nodes and then the transfer results will be displayed.
  • Page 227 The data link mode setting will be read from all nodes on the network. Note: If a local network table has not been registered (i.e., if the network address is 0), a Unit Selection Dialog Box will be displayed. If that occurs, select the Controller Link Unit on the required network.
  • Page 228 • The following dialog box shows that not all nodes have the same setting. 3 If the mode settings are mixed, the Yes Button can be clicked to set all nodes to manual data links. In this example, the node set for automatic data links will be changed to manual data link mode.
  • Page 229 Transferring the Data Link Table Note: As long as all the data link tables can be transferred to all of the PLCs attempted, Set All Nodes for Network Operation can be selected to transfer the data link tables simultaneously to multiple PLCs. If there are any PLCs with the power turned OFF, or with disconnected cables, use the following method to transfer the data link table to one PLC at a time.
  • Page 230 • 3G8F7-CLK52-V1(-EV1) • CJ1W-CLK21-V1 Note: Refer to the Controller Link Operation Manual for the procedure to add nodes and details on changing data link tables while data links are running. Use the following procedure to transfer data link tables while data links are running.
  • Page 231 Clear the selection and repeat the procedure. Comparing Data Link Tables 1. In the node list in the Data Link Component, select the node address of the PLC for which data link tables are to be compared with those in the computer.
  • Page 232 Size, and Area 2 Offset. The size of this dialog box can be changed. The data for the PLC is display on top and that for the computer (i.e., the data being edited on the CX-Integrator) is displayed on bottom. Inconsistencies are displayed between pointed brackets <...
  • Page 233: Starting And Stopping Data Links (Including Status Displays)

    Before performing the operations described below, connect online to a node where the data link table has been transferred. As long as the data link table is stored there, data link starting and stopping can be executed from any node.
  • Page 234 With manual setting the links, it is necessary to set, for the startup node, the data link table and the data link mode (manual setting) in the DM parameter area. If these are not set correctly, the data links will not start.
  • Page 235: Automatically Set Data Links

    First make the settings for data link operation at PLC startup, and for the automatic data link setup parameters, and then transfer the data to the startup node. When using automatically set data links, there is no need to create data link tables with the Data Link Editor.
  • Page 236: Controller Link Automatic Setup

    Datalink Component (Controller Link) or Datalink Component (SYSMAC LINK) Window will be displayed. Note: Start Data Link cannot be selected if there is not a Controller Link Unit or SYSMAC LINK Unit mounted in the PLC that is connected online.
  • Page 237 Select Start or Stop. Select Start to automatically start the data links when power is turned ON without performing a specific startup operation. If Start is set, it will be set in the Controller Link startup node. Automatic Data Link Area Set the area, start word, and size for area 1.
  • Page 238 Automatically Set Data Links 4-4-2 Controller Link Automatic Setup Equality Layout (Previous Method) This is the previous automatic data link type where all nodes are allocated the same sizes of data links. Settings Common to All Automatic Data Link Types Item...
  • Page 239 (1) Area and Start Word • The master node receives all data sent by the slaves. The reception size Area 1 for the master node is thus the node send data size times the number of (2) Master size slave nodes. •...
  • Page 240 • Master node Slave node All slave nodes receive part of the data sent by the master node (1a in figure). (1) Area and Start Word • The master node receives all data sent by the slaves. The data sizes are fixed for all nodes.
  • Page 241: Sysmac Link Automatic Setup

    Start Data Link from the popup menu. The SYSMAC LINK Datalink Component Window will be displayed. Note: Start Data Link cannot be selected if there is not a Controller Link Unit or SYSMAC LINK Unit mounted in the PLC that is connected online.
  • Page 242: Transferring Automatic Data Link Setup Parameters To The Startup Node

    Transferring Automatic Data Link Setup Parameters to the Startup Node The automatic data link parameters that have been set are then sent to the connected startup node PLC. It is also possible to read the automatic data link parameters that have been set for the PLC.
  • Page 243 • The data link mode (manual/automatic) and data link operation are determined by the Note data link setup at the startup node. With automatic setup, it is necessary to set, for the startup node, the data link mode (automatic) and the number of data link words in the Automatic Datalink Setup Dialog Box.
  • Page 244: Monitoring Data Link Status

    1 Select Network - Work Online from the menu bar to connect online. 2 Select Tools - Start Data Link. 3 Select Controller Link or SYSMAC LINK, and then click the OK Button. The Datalink Component Dialog Box will be displayed.
  • Page 245 Furthermore, if the data link tables that were read are then downloaded to a PLC, the data link tables that were originally in the PLC will be overwritten. To prevent these problems, use the following method to check automatically set data link tables.
  • Page 246 5. Place the CX-Integrator online with the data link start node displayed above. 6. Reconnect the CX-Integrator online and open the Data Link Component. 7. Select Online - Start Data Link from the Data Link Component menu bar. The Automatic Datalink Dialog Box will be displayed and the settings will be automatically uploaded.
  • Page 247: Section 5 Ethernet

    Communications Section 5 Ethernet This section describes the operations specific to Ethernet.
  • Page 248: Broadcast Node Search

    The IP broadcast function can be used to search for all OMRON nodes within the same segment of an Ethernet network, and to display them in a list. Any of the OMRON nodes displayed on the list can be selected for online connection.
  • Page 249 When the IP conversion for any node on Ethernet (i.e., an Ethernet Unit or personal computer) is set for either the IP address table method or the combined method, the IP address table at the CX-Integrator (personal computer) must be preset. (For details on setting IP address tables, refer...
  • Page 250: Ping Test

    5-2-1 Overview The connection status of a target PLC can be checked by executing a ping test from a PLC node connected on an Ethernet network. In the example shown here, PLC1 is serially connected and a ping test is executed to check whether PLC3 is connected to the Ethernet network.
  • Page 251 3. The Ping Test Dialog Box will be displayed. Input 192.168.200.185 as the target IP address, and then click the Ping Button. 4. The test result will be displayed in the Status field. In this case, “Node pinged successfully” is displayed to confirm that PLC3 is connected to the Ethernet...
  • Page 252 Ping Test 5-2-2 Procedure...
  • Page 253: Section 6 Devicenet

    Communications Section 6 DeviceNet This section describes the settings and operations unique to DeviceNet networks, including registering slaves in the master, I/O allocations, and device monitoring.
  • Page 254: Devicenet Setting Procedures

    DeviceNet Setting Procedures This section describes the setting operations that are unique to DeviceNet networks. Refer to Section 2 Basic Operations for operation that are the same as those for other networks. The following flowcharts show the overall flow of DeviceNet settings.
  • Page 255: Saving The Parameters For The Entire Existing Network

    6-1-3 Saving the Parameters for the Entire Existing Network 6-1-3 Saving the Parameters for the Entire Existing Network The parameters for all of the devices on the network can be saved for use in maintenance. Start the CX-Integrator. 2-2 Connecting Online to the Relay PLC Connect to the network (online).
  • Page 256: Setting Slave Parameters

    Editing Slave Parameters Component - Parameter - Edit The parameters of some slaves can be set. However, doing so may cause the I/O size to change. Because of this, the slave parameters must all be set before setting the master’s parameters.
  • Page 257 6-2-1 Editing Slave Parameters 4. Select the parameter and press the Enter Key or double-click the parameter. If a push-pin icon is displayed next to a parameter name, it is a read-only parameter and cannot be edited. The set value will be changed as shown below according to the parameter input type.
  • Page 258: Checking And Setting I/O Size

    Checking I/O Size View - Property - I/O Information The I/O size of this slave can be checked with the I/O Information Tab Page of the Property Window. Check to make sure that the I/O size listed is correct. To change it, use the following procedure.
  • Page 259 Note If the function to automatically update the I/O size is enabled and there is no EDS file, some operations will cause the I/O size in the master scan list to be updated to zero.
  • Page 260: Adding Slaves To The Master

    When a slave is registered to the master, it can automatically be allocated to the memory block set for I/O allocation. The allocation, for both Out Size and In Size, will be made in the order of registration beginning with the unoccupied area of memory block 1. When memory block 1 is filled, the allocation will be made to memory block 2.
  • Page 261 4. Set the area, start word, and the number of words for the block. 5. Set Memory Block 2 in the same way. 6. Click the I/O Allocation (IN) Tab, and make the memory block settings in the same way as for the I/O Allocation (OUT).
  • Page 262: Adding Slaves

    The following three methods are supported for adding slaves. Dragging and Dropping Select the slave from the Network Configuration Window on the right and drag and drop it on the master icon. When slaves are registered with the master, I/O words will be automatically allocated to the slaves in the order they are registered.
  • Page 263 The menu will appear on the right-hand side. At the time of I/O allocation, the registered slave can be deleted or settings can be made for the registered slave by using the Parameter Wizard or by editing the parameters of the master.
  • Page 264 6-3 Adding Slaves to the Master 6-3-2 Adding Slaves Registering in the Edit Device Parameters Window Slaves can be added and I/O areas allocated in the Edit Device Parameters Window. Refer to 6-7 Master Parameter Editing Details (Tab Descriptions) for details. 6-12...
  • Page 265: Setting Master Properties

    6-4 Setting Master Properties 6-4-1 CS1W-DRM21(-V1) and CJ1W-DRM21 Setting Master Properties This section describes how to set properties for OMRON masters. The Master Unit is right-clicked and Property is selected from the popup menu. 6-4-1 CS1W-DRM21(-V1) and CJ1W-DRM21 To set the master and slave functions, use the following procedure.
  • Page 266: Cvm1-Drm21-V1 Or C200Hw-Drm21-V1

    6-4-2 CVM1-DRM21-V1 or C200HW-DRM21-V1 To set the PLC model on which the Unit is mounted, use the following procedure. 1. Right-click the Master Unit in the Network Configuration Window and select Property from the popup menu. The following dialog box will be displayed.
  • Page 267: Editing Master Parameters

    Communications Explicit Message (See note 2.) Communications Note 1. The same function can be achieved with the setting to enable/disable the master function. 2. Explicit message communications is possible whether or not registration has been made on the scan list.
  • Page 268: Parameter Wizard

    2. Each block consists of a maximum of 100 words. Note It is not possible to go to the next step if there is any duplication between blocks or the first word is not within the permissible set range.
  • Page 269 6-6 Parameter Wizard 5. The Scan list Wizard-Set How to Allocate I/O Date to PLC Memory Block Dialog Box will be displayed. Specify the allocation method and click the Next Button. 6-17...
  • Page 270 Example: High Node address order : Not used If there are slaves that require just one byte of I/O memory, Allocate so that total number of they are allocated the rightmost seven bits or leftmost seven allocated words is minimized.
  • Page 271 6-6 Parameter Wizard 6. Slave Registration/Deletion The following Scan List Wizard - Set Memory Block’s Start Word Dialog Box will be displayed. Specify the slave to be registered with the master and click the Next Button. The devices on the network are shown in the Registered Device List.
  • Page 272 6-6 Parameter Wizard 8. If the CX-Integrator is online, the following dialog box will be displayed. Click the Yes Button and edit the master parameters. Remote I/O communications according to the new settings will start. Note Device parameters set with the Parameter Wizard can be edited by individually if necessary.
  • Page 273: Master Parameter Editing Details (Tab Descriptions)

    I/O size in the scan list will take priority. If an EDS file has not been installed in the slave, obtain the EDS file and install it. Also, set the correct I/O size in all slaves that require changes in the I/O size.
  • Page 274: Edit Device Parameters On Cs1W-Drm21(-V1)/Cj1W-Drm21

    Edit Device Parameters on CS1W-DRM21(-V1)/CJ1W-DRM21 Note When the CS1W-DRM21(-V1)/CJ1W-DRM21 DeviceNet Unit is used, select the device and then select Component - Property and turn ON Enable Master Function in the Properties Dialog Box. The following dialog box will be displayed when the CS1W-DRM21(-V1)/ CJ1W-DRM21 is selected.
  • Page 275 Register/Unregister Buttons Click this button to unregister the I/O allocation of the selected slaves or to make the I/O reallocation of the slaves in the order of earlier addresses. Advanced Setup Button Click this button to set the connections or display the device information.
  • Page 276: Editing Device Parameters On Cvm1-Drm21-V1 And C200Hw-Drm21-V1

    Allocates the output data and sets the output memory block the CPU Unit with the advanced setup function. I/O Allocation (IN) Allocates the input data and sets the input memory block in the CPU Unit with the advanced setup function. Communication Cycle Sets the communication cycle time.
  • Page 277 : By pressing this button, the device will move from the Registered Device List to the Unregistered Device List. Auto allocation as is Check this box when registering the slaves with the master in the Edit registered Device Parameters Window so that the slaves will be allocated to an unoccupied area in blocks of words in order of registration.
  • Page 278: Editing Device Parameters On 3G8F7-Drm21 Devicenet Pci Board Scanner

    Board Scanner The following dialog box will be displayed when the 3G8F7-DRM21 DeviceNet PCI Board Scanner is selected. The Edit Device Parameters Dialog Box consists of the following four tab pages. Description General Registers the device with the scan list and makes I/O allocations automatically.
  • Page 279 Buttons from the Unregistered Device List to the Registered Device List. : By pressing this button, the device will move from the Registered Device List to the Unregistered Device List. Advanced Setup Button Click this button to set the connections or display the device information.
  • Page 280: Canceling Slave Registration With The Master

    1 of the corresponding memory block. • It is possible to unregister the I/O allocation of the selected slaves or to make the I/O reallocation of the slaves in the order of earlier addresses anytime by clicking on Register/Unregistered Button.
  • Page 281: Manual I/O Allocations

    I/O Allocation Tab Page Make the following settings on the I/O Allocation Tab Page. 1. I/O allocation of each OUT/IN memory block (1/2) to the I/O memory area of the CPU Unit 2. Click the I/O Allocation (OUT) or I/O Allocation (IN) Tab. The following dialog box will be displayed.
  • Page 282: Changing The First Address Of Output/Input Block

    08 of word CIO 3300. Therefore, the product name for 3300:Bit08 is left blank. No words in the CPU Unit will be displayed for any memory block that is not in use. 6-8-2 Changing the First Address of Output/Input Block...
  • Page 283 •Words refers to the number of words in the block displayed on the CX-Integrator. This value is not downloaded to the master. • If the occupied area of the block is less than 100 words when uploaded, Words will be set to 100 and displayed as such.
  • Page 284: Allocating I/O

    Device List as shown below if connections settings have been made for the devices. To allocate the I/O data on the left-hand side with the mouse, drag and drop the I/O data with the left mouse button. To allocate the I/O data on the right-hand side, drag and drop the I/O data with the right mouse button.
  • Page 285 Specify the first word to allocate and the number of allocated words. The MSB (high) or LSB (low) position can be set for the first word to allocate. The user must set the byte position to LSB if the number of bytes allocated is 2 or more.
  • Page 286 To unregister the allocations of slaves, select the slaves in the Registered Device List, and click the Delete Button. Note To register in units of words the slaves in the order of earlier addresses, select the slaves in the Registered Device List, and click the Auto Button.
  • Page 287: Slave Information

    I/O Allocation Tab - Information Button Device information on registered slaves, such as I/O comments, can be checked with the I/O Allocation Tab Page. The I/O comment is set to the I/O data of a slave by selecting Edit I/O Comment from the Device Menu.
  • Page 288: Advanced Settings

    6-9-1 Advanced Settings Select Component - Parameter - Edit, and click the General Tab. Select the slave and click the Advanced Setup Button. Make advanced setup settings (such as device information display/compare and connections settings) for remote I/O communications.
  • Page 289 4. Set the COS/Cyclic heart beat timer. 5. Click the OK Button. An asterisk (*) will be displayed in the C column at the right edge of the Registered Device List. If the connections of a device already allocated with I/O are changed, the previous I/O allocations will be canceled.
  • Page 290: Communication Cycle Time Settings

    • Both COS and Cyclic settings cannot be made at the same time. Note •If Poll and COS settings or Poll and Cyclic settings are used in combination, check that the output settings of the both connections are the same.
  • Page 291: Setting Message Timers

    Component - Parameter - Edit - Message Timer Tab Note: This procedure is supported by the CS1W-DRM21(-V1) and CJ1W-DRM21 only. A message timer is by default set to 2 s (2000 ms). They can be set 1-ms increments to between 500 and 30,000 ms.
  • Page 292 If the response of a destination device is slow, the timer value must be set to a larger value. The response may be slow for multilevel FINS message communications. The next message cannot be sent to the same device until the response is returned.
  • Page 293: Slave Function Settings

    User Setup Button. 3. Set the output and input areas used for remote I/O communications. Set each area type for IN (the slave to the master) and OUT (the master to the slave), start words, and allocated sizes. If the user’s connections settings are used, make all connections settings.
  • Page 294: Setting/Canceling Explicit Message Communications

    For the CS1W-DRM21(-V1) and CJ1W-DRM21, remote I/O communications upon start-up can be disabled by disabling the master function. Select Component then click the Unit Function Tab of the Property Window, and remove the check mark from Enable Master Function. 6-42...
  • Page 295: Creating And Editing I/O Comments

    The I/O comments can be checked while making I/O allocations to the master. Note No I/O comments can be created or edited for a device if the device is not designed to have I/O data. To edit I/O comments, use the following procedures.
  • Page 296 6-10 Creating and Editing I/O Comments 3. Select the bit where the I/O comment should be set and press the Enter Key (or click the bit position). Data can be input into the comment area as shown below. 4. Input the comment and press the Enter Key.
  • Page 297: Displaying Device Properties

    Property Dialog Box Common to All Devices The following window will be displayed for device properties. This dialog box has the name of the vendor of the device and the device type. By clicking the Change Icon Button, the icons displayed by the CX-Integrator can be customized.
  • Page 298: I/O Information Inherent To Each Slave Device

    I/O connections in the EDS file. Setting I/O Sizes If there is no EDS file or the slave’s I/O size is variable, the I/O size can be changed using the following procedure. 1. Click the Edit Button. The Edit I/O Size Dialog Box will be displayed.
  • Page 299 Note If the function to automatically update the I/O size is enabled and there is no EDS file, some operations will cause the I/O size in the master scan list to be updated to zero.
  • Page 300: Information For Master

    The number of actual I/O bits for remote I/O communications devices. Communication Cycle The communication cycle time based on the device information in the Time scan list. If the user has set the communication cycle time, the user’s set value will be displayed. 6-48...
  • Page 301 6-11-3 Information for Master • PLC Information The name of the PLC model in use and the unit number of the master will be displayed as PLC Information. The operating mode of the PLC will be displayed online. To change the PLC mode, click the Change Button.
  • Page 302 6-11-3 Information for Master • PLC Information The name of the PLC model in use and the unit number of the master as PLC Information will be displayed. To change the PLC model, click the Change Unit Button. If the network configuration is read from the actual network, the PLC model cannot be changed.
  • Page 303: Downloading The Network Configuration/Device Parameters To Devices

    Click the Continue Button to continue the process. Click the Abort Button to cancel the process. The downloading of the network configuration will be automatically continued if the user does not click the Abort Button for 15 s after the above window is displayed. 6-51...
  • Page 304 For this reason, do not download the network configuration while the master-side PLC (CPU Unit) is operating. • Parameters cannot be downloaded to the master unless the CPU Unit is in Program Mode. If the message Device state conflict. Going to change PLC Mode. OK? is displayed, check the operation mode of the CPU Unit.
  • Page 305: Downloading Device Parameters

    Note When downloading parameters with the Edit Device Parameters Dialog Box, the following dialog box will appear if the operation mode of the CPU Unit is set to anything other than PROGRAM Mode. Click the Yes Button to change the operation mode of the CPU Unit to PROGRAM Mode and start downloading.
  • Page 306 The downloading of the network configuration will be automatically continued if the user does not click the Abort Button for 15 s after the above window is displayed. The following dialog box with information on device errors or missing devices will be displayed after the parameters have been downloaded.
  • Page 307: Resetting The Device

    Parameters cannot be downloaded to the master through the Network Configuration Window unless the CPU Unit is in Program Mode. If the message Device state conflict. Going to change PLC Mode. OK? is displayed, check the operation mode of the CPU Unit.
  • Page 308: Uploading And Verifying Device Parameters

    If the DeviceNet network configuration was being uploaded with the CX-Integrator version 2.1 or higher, and the upload was cancelled or failed, the following dialog box will be displayed the next time that the same network configuration is uploaded. This feature allows you to upload the configuration only for the nodes where the upload failed.
  • Page 309 •When parameters are uploaded from the Network Configuration Window, an asterisk may be display to the lower left of some devices. This indicates that the I/O size of the device is not consistent with the I/O size in the scan list in the Master Unit. Either select View - Property, click the I/O Information Tab, click the Edit Button, and correct the I/O size, or click the Get from Scan List Button and correct the I/O size.
  • Page 310: Verifying The Network Configuration

    1. Select the Network Configuration Window to be verified. 2. Select Network - Compare. The progress window will be displayed and the comparison will begin. 3. If there are any comparison errors, the following dialog box with the details of the errors will be displayed. Note This function compares only the network configurations.
  • Page 311: Verifying Device Parameters

    4. Click the Yes Button. The progress dialog box will be displayed and the parameters will be compared for verification. If there are any comparison errors, the following dialog box with the details of the errors will be displayed. 6-59...
  • Page 312 6-13-4 Verifying Device Parameters Using the Edit Device Parameters Dialog Box Component - Parameter - Edit-Compare Button To compare the parameters through the Edit Device Parameters Dialog Box, use the following procedure. 1. Place the CX-Integrator online. 2. Select the device.
  • Page 313: Monitoring Devices

    6-14-1 Setting Monitor Refresh Timer Tools - DeviceNet tool - Setup Monitor Refresh Timer Set the interval to refresh the device monitor display. This setting will be applied to the monitoring of any network device. Note If the refresh timer is set to too small a value, the DeviceNet network will be overloaded and the CX-Integrator may experience timeout errors (device access errors).
  • Page 314: Monitoring Devices

    2. Select the device. 3. Select Component - Monitor. A monitor dialog box for the device will be displayed. • A Slave can be monitored only if the slave has parameters that can be monitored in Note the EDS file.
  • Page 315 6-14 Monitoring Devices 6-14-2 Monitoring Devices Status Tab Page The Status Tab Page displays the status of the master and slaves in remote I/O communications. Master status Starts remote I/O Stops remote I/O communications. Slave status Node address for detailed...
  • Page 316 6-14 Monitoring Devices 6-14-2 Monitoring Devices Unit Status Tab Page The Unit Status Tab Page displays the status of the Unit, master, and slave functions. Communication Cycle Time Tab Page The Communication Cycle Time Tab Page displays the present, maximum, and minimum values of communication cycle time.
  • Page 317 6-14 Monitoring Devices 6-14-2 Monitoring Devices Error History Tab Page The Error History Tab Page displays the error history recorded in the master. The following error history items will be displayed. Item Description Time of Error The time the error occurred.
  • Page 318 6-14 Monitoring Devices 6-14-2 Monitoring Devices Status Tab Page The Status Tab Page displays the status of the master and slaves in remote I/O communications. Master status Starts remote I/O communications. Stops remote I/O communications. Slave status Stops remote I/O for...
  • Page 319 The Communication Cycle Time Tab Page displays the present, maximum, and minimum values of communication cycle time. The maximum or minimum value can be cleared by clicking the Clear Button. Error History Tab Page The Error History Tab Page displays the error history recorded in the master.
  • Page 320 6-14 Monitoring Devices 6-14-2 Monitoring Devices Slaves Devices can be monitored if the parameters of the devices are specified in EDS files to allow monitoring. Some OMRON Slaves provide detailed monitoring windows. Refer to the manual for the specific Slave for details.
  • Page 321: Using General-Purpose Tools To Set Devices

    6-15-1 Setting Device Parameters with Class Instances Tools - DeviceNet Tool - Setup Parameters Device parameters for devices that have no corresponding EDS files can be set by specifying the following items. • Service code • Class (object class), instance (class instance) and attribute (instance attribute) Before setting the device parameters, it is also necessary to obtain the data setting information on attributes other than the above from the manufacturer of the device.
  • Page 322 2) Designate the class and instance of the parameter to be set. 3) Input Data Area for the Attribute of the parameter to be set. 4) Input the attribute followed by the value to be set for the parameter in the Data area.
  • Page 323: Optional Functions

    To install the expansion module, use the following procedure. 1. Select Tools - DeviceNet tool - Install Plugin Module. A window to specify the name of expansion module set file will be displayed. 2. Input the file name and click the Open Button.
  • Page 324 3) Input the new vendor name and click the OK Button. 4. To add or change the device type, click on the Device Type Tab. The method of adding or changing the device type is the same as that of adding or changing vendor information.
  • Page 325 Communications Section 7 CompoNet This section describes the basic usage of CompoNet networks and how to set CompoNet parameters.
  • Page 326: What Is Componet?

    I/O information through a CompoNet Master Unit, refreshing I/O in sync with the PLC execution cycle. Message communications can also be used from host computers or the CPU Unit of the PLC to read and write CompoNet Slave Unit data. The following CompoNet monitor and settings are set using the CX-Integrator.
  • Page 327: Basic Procedures

    The network is connected, the power supplies wired, the CompoNet settings configured, and the serial port of the PLC to which the CompoNet Master Unit is mounted is connected to a personal computer. The Unit can then be monitored. The Unit parameter settings may be adjusted as required.
  • Page 328: Optional Settings

    7-2 Basic Procedures 7-2-2 Optional Settings 7-2-2 Optional Settings Use the following steps to set the parameters according to the application or network environment. Step Section Set and transfer Master Unit parameters. Master Unit parameter settings Refer to 7-6-1 Master Unit Parameter Settings.
  • Page 329: Uploading, Downloading, And Comparing Network Configurations

    Uploading, Downloading, and Comparing Network Configurations The configuration of the actual network can be written to a virtual network on the CX-Integrator running on the computer. Network configurations will also be compared. This section describes how to perform each task.
  • Page 330: Comparing Network Configurations

    7-3-2 Comparing Network Configurations Use the following procedure to compare the network configuration of an actual network with the network configuration of a virtual network created with the CX-Integrator. 1. Select the networks to be compared from the Network Configuration Window.
  • Page 331: Component Monitor

    The Component Monitor Window will be displayed. Information about the Network Status, Slave Status, Unit Status, Error History, and Error Counter will be displayed in the Monitor Window on the Master Unit. 3. To quit the monitor function, click the Close Button.
  • Page 332: Master Unit Monitor Window

    Master Unit Monitor Window Various types of monitoring functions are supported to enable quickly isolating errors that occur in connected devices and on the network, and to enable rapid recovery from errors and predictive maintenance. This section describes the information that can be monitored for OMRON Master Units.
  • Page 333 7-4 Component Monitor 7-4-2 Master Unit Monitor Window Slave Status Tab Page The Slave Status Tab Page shows the status of Slave Units and Repeater Units connected to the network. Network Participation Status of Slave Units and Repeater Units Indicator color...
  • Page 334 7-4 Component Monitor 7-4-2 Master Unit Monitor Window Individual Slave Status Check Select the Slave Unit or Repeater Unit from the pull-down menu to check the status. The check box for each applicable status will be selected. Status Description Remote I/O Comms Communications are operating normally.
  • Page 335 Communication Running Communications The slave has left the network. Error Node Address The address of a Slave Unit attempting to participate in the Duplication Error network is the same as the address of another Slave Unit. Structure Error Slave Units...
  • Page 336 To refresh the display, click the Update Button. To clear the display contents, click the Clear Button. To save the file, click the Save Button. The file can be saved in CSV format. Refer to the Master Unit manual for details on errors.
  • Page 337: Uploading, Downloading, And Comparing Component Parameters

    Network Configuration Window. 2. Right-click and select Parameter – Edit from the menu. 3. Click the Transfer [Unit to PC] Button located on the General Tab Page for the Master Unit or Slave Unit. If the Master Unit is selected, a confirmation dialog box will be displayed.
  • Page 338: Comparing Component Parameters

    2. Select the components to compare from the Network Configuration Window. 3. Right-click and select Parameter - Edit from the menu. 4. Click the Compare Button located on the General Tab Page for the Master Unit or Slave Unit. The compare progress dialog box will be displayed, and then the comparison results will be displayed.
  • Page 339: Downloading The Component Parameters To The Components

    4. Click the Transfer [PC to Unit] Button located on the General Tab Page for the Master Unit or Slave Unit. Note: The settings in the Unit will be returned to their default values if the Default Setting Button is clicked. Nothing will change in the dialog box, so do not click this button carelessly.
  • Page 340 3. Select Transfer [PC to Network (No network address)] from the Network Menu. The Transfer [PC to Network (No network address)] Dialog Box will be displayed. 4. Click the OK Button. When the download has been completed, a dialog box will be displayed saying 5. Click the OK Button. 7-16...
  • Page 341: Resetting Component

    3. Right-click and select Parameter – Edit from the menu. 4. Click the Reset Button (see note) in the Parameter Edit Dialog Box. Note: The Reset Button does not appear for components that do not require a reset to enable new settings.
  • Page 342: Editing Master Unit Parameters

    Parameter - Edit from the Component Menu.) Double-click, or right-click and select Parameter – Edit. The Master Unit Parameter Settings Dialog Box will be displayed. The contents of each tab page are shown next. For details on parameter settings, refer to the Master Unit manual. 7-18...
  • Page 343 7-6-1 Master Unit Parameter Settings General Tab Page Name Function Function Choice Communications When this option is selected, all input data for the Error Input Data Slave Unit will be cleared to zeros if a Zero Clear communications error occurs in the Slave Unit. This will prevent operation that is triggered by IN data in Slave Units that have a communication error.
  • Page 344 • While connected to the network online, if the network configuration has been uploaded to the computer, all unregistered Slave Units connected to the network will be displayed. (If only the Master Unit data has been uploaded to the computer while connected to the network, no Slave Units will be displayed.)
  • Page 345 Slave Active Timer Sets the time to detect that registered Slave Units are participating in the network, starting from the time that the power is turned ON or the Remote I/O Communications Start Switch is turned ON. This setting is set when changing the default setting.
  • Page 346 Used to set the memory areas from which words will be allocated to the Slave Units. You can select from Word IN the CIO, WR, HR, and DM Areas. Also used to set the Bit OUT addresses of the first words to allocate and the Bit IN numbers of nodes to which words will be allocated.
  • Page 347: Editing The Registration Table

    • When comparing the Slave Units that are participating in the network and the Slave Units that have been set up. • When an unregistered Slave Unit or a Slave Unit with a different node address or model must not be permitted to participate in the network.
  • Page 348 Unregistered Device List. 7. Click the Apply Button. The Registration Table will be saved. 8. Click the Transfer [PC to Unit] Button on the General Tab Page for the Master Unit to download the settings to the components.
  • Page 349 Setting the Slave Active Timer and Enabling Waiting for All Slaves The Slave Active Timer and Enable Waiting All Slave Active Function are set to control operation when a slave joins the network. The Slave Active Timer, Enable Waiting All Slave Active Function, and Registration Table Check Type are set as follows: 1.
  • Page 350: Editing The Software Setting Table

    WR, and HR Areas, in addition to the Special I/O Unit Area. The Software Setting Table is used in the following situations. • When allocating words in an area other than the Special I/O Unit Area to Slave Units • When setting the number of words allocated, e.g., when words after those allocated to the Slave Units will be used for another purpose.
  • Page 351 Flags (32 words) 7. Click the Apply Button. The settings will be saved. 8. Click the Transfer [PC to Unit] Button on the General Tab Page for the Master Unit. The settings will be downloaded to the Master Unit. 7-27...
  • Page 352: Editing Slave Parameters

    7-7 Editing Slave Parameters 7-7-1 Setting Slave Parameters Editing Slave Parameters By editing Slave Unit parameters, the Slave Unit operating time (bit I/O interval) can be set, and Unit and bit comments can be input. 7-7-1 Setting Slave Parameters Use the following procedure to edit Slave Unit parameters.
  • Page 353: Checking The Slave I/O Size

    Use the following procedure to check the slave I/O size. 1. Right-click the Slave Icon in the Network Configuration Window and select Additional Functions - Property. 2. The Property Dialog Box will be displayed. The input size and output size can be checked in this dialog box. 7-29...
  • Page 354: Other Componet Functions

    Reset the components. Channel Allocation Displays the I/O allocation status. The additional functions depend on the Unit. Functions that cannot be selected are grayed out in the menu, and cannot be selected. For details, refer to the Unit manual. Use the following procedure to display component information.
  • Page 355: Installing Expansion Modules

    7-8-2 Installing Expansion Modules When a new model of CompoNet Unit is released, the new component can be used by installing an expansion module for the CX-Integrator that supports the new component. There are two methods to install expansion modules depending on the format of the information file for the new component.
  • Page 356 7-8 Other CompoNet Functions 7-8-2 Installing Expansion Modules 7-32...
  • Page 357 Communications Section 8 CompoWay/F This section explains the settings and operations specific to the CompoWay/F system.
  • Page 358: Compoway/F System Configuration

    8-1-1 Overview CompoWay/F System Configuration 8-1-1 Overview The CompoWay/F communications configuration (including slave parameters) can be uploaded using any one of the following three system configurations. CompoWay/F Slaves that are Communications configuration uploaded 1) CompoWay/F Slaves connected to a Computer (CX-Integrator)
  • Page 359: Compoway/F Slaves Connected To A Plc

    Use the following procedures to transfer network information of CompoWay/F Slaves connected to a serial port of a CS/CJ-series CPU Unit or Serial Communications Board/Unit, or serial port C on the Controller Section of an NSJ-series NSJ Controller. Example: In the following example, an E5CN Temperature Controller is connected to port 1 (RS-422/RS-485 port) of a CJ1W-SCU41-V1 Serial Communications Unit with the CompoWay/F protocol.
  • Page 360 Select CompoWayF as the Port 1 (RS-422A/RS-485 port) protocol and click the OK Button. Note: The CompoWay/F protocol communications will be enabled when CompoWayF is selected in the dialog box above and Serial Gateway is selected for port 1 in the Serial Communications Unit’s Unit parameters. 4. The icon will be displayed next to the Serial Communications Unit to indicate that the Serial Communications Unit’s serial port (port 1) can be accessed through...
  • Page 361 The search will take about 20 seconds for each node that is not actually connected, so it will take about 35 minutes for the transfer to be completed if the All(0-99) Option is selected. For the same reason, the transfer will take longer if the Selection Option is selected and the maximum node address is higher than the node address of the nodes actually connected.
  • Page 362 The CompoWay/F Slave upload starts when the OK Button is clicked. 8. The following dialog box will be displayed when the CompoWay/F Slave transfer is completed. Click the OK Button. The following dialog box will be displayed if no CompoWay/F Slaves could be found.
  • Page 363 Workspace Window. Note: With CX-Integrator 2.1 or higher, the network address of the CompoWay/F network will be displayed when uploading the CompoWay/F network if it is registered in the PLC’s routing tables (uploaded CompoWay/F network address display function).
  • Page 364: Setting The Compoway/F Slave's Parameters

    Use this procedure to set the parameters of the CompoWay/F Slave after the node’s parameters have been uploaded to the computer (CX-Integrator). Temperature Controller 1. Right-click the icon of the Temperature Controller (an E5CN in this example) in the Network Configuration Window and select Start Special Application – Start with Settings Inherited.
  • Page 365 Setting the CompoWay/F Slave’s Parameters Note When a K3SC Serial Converter is connected to the PLC’s RS-232C port and a Temperature Controller is connected to the K3SC by RS-485, make an RS-232C cable with the following wiring to connect the PLC’s RS-232C port to the K32-23209 Attachment Adapter.
  • Page 366: Compoway/F Slaves Connected To A Computer

    1. Select Network – Communication Settings from the menu bar. The Change PLC Dialog Box will be displayed. 2. Select CompoWay/F Device from the Device Type List. Click the Settings Button and select the Driver Tab to display the Network Settings. 8-10...
  • Page 367 After completing the network settings, click the OK Button. 3. Select Network – Work Online from the menu bar. (CompoWay/F Slaves cannot be connected online by selecting Auto Online, so be sure to select Work Online.) 4. When the CompoWay/F Slave is connected online, the Slave will be displayed in the Online Connection Information Window.
  • Page 368 Slave’s node address. The CompoWay/F Slave upload starts when the OK Button is clicked. 7. The following dialog box will be displayed when the CompoWay/F Slave transfer is completed. Click the OK Button. The following dialog box will be displayed if no CompoWay/F Slaves could be found.
  • Page 369 Network Configuration Window. The CX-Thermo application will receive the Temperature Controller model number and start. After the parameter settings are completed, download the set values to the E5ZN. Refer to the CX-Thermo Help function for details on setting parameters and downloading parameter settings to components.
  • Page 370 If a standard RS-232C cable with D-SUB connectors is being used, connect with connected devices and set the unit numbers. an optional K32-23209 Adapter (sold separately), which is 5 cm long and has a D-SUB 9-pin male connector on one end.
  • Page 371 Communications Section 9 NT Links This section explains the settings and operations specific to the NT Link system.
  • Page 372 1. With the CX-Integrator online, right-click the CPU port listed below the target PLC in the Online Information Window and select Connect from the pop-up menu. 2. A dialog box will be displayed to select one of the CPU Unit’s serial ports. Select Serial Port (the RS-232C port) and click the OK Button.
  • Page 373 Note If the PLC is operating, the following warning dialog box will be displayed. Check the system to be sure that it is safe to change the PLC’s operating mode to PROGRAM mode and click the Yes Button. If the mode is changed to PROGRAM mode, the PLC will stop operating so be sure...
  • Page 374 7. The following dialog box will be displayed when an NS-series PT is connected to the CPU Unit’s RS-232C port. Verify that the pin 5 of the CPU Unit’s DIP switch is OFF and then click the OK Button. 8. The NT Link Connection Auto-detect Function will be executed.
  • Page 375 NT Link Connection Auto-detect Function 9-1-2 Procedure 10. If the PLC’s operating mode was changed from RUN mode, the following dialog box will be displayed to switch from PROGRAM mode back to RUN mode. To return to RUN mode, click the Yes Button.
  • Page 376: Transferring Screen Data Through The Plc

    Note: In order to transfer screen data through the PLC, the PLC must be a CS/CJ-series PLC with a CPU lot number of 030201 (manufactured February 1, 2003) or later. In addition, the CPU Unit must be a CS1G-H, CS1H-H, CS1D-S, CJ1M, CJ1G-H, or CJ1H-H.
  • Page 377 Transferring Screen Data through the PLC 9-2-2 Procedure 3. The PLC will be connected online to the computer and the PLC’s rack configuration will be displayed in the Online Information Window. Right-click the CPU port and select Connect from the pop-up menu.
  • Page 378 • The NS-series PT system version must be 6.0 or later. If the lot number for the CPU Unit to be connected is too old, or if the PT version is too old, the following message will be displayed. IF this occurs, the network configuration will not be correctly transferred, the NS-series PT will display Unknown-HMI, and the special application will not start (in a following step below).
  • Page 379 Network Configuration Window. 10. Right-click the icon of the NS-series PT in the Network Configuration Window and select Start Special Application – Start with Settings Inherited. CX-Designer will start and a dialog box will be displayed for selecting the project.
  • Page 380 9-2-2 Procedure 12. Click the OK Button to create the new screen data. The created screen data will be created in a project file (.ipp extension) for transfer to the NS-series PT. 13. To transfer the screen data to the NS-series PT, select either Quick Transfer [To PT] or Transfer [To PT] from the PT menu.
  • Page 381 Communications Section 10 Network Testing This section explains the operations of the following network test tools: Controller Link Network Diagnostic Tool Echoback test between nodes (Ethernet, Controller Link, SYSMAC LINK, DeviceNet) Ethernet ping test...
  • Page 382: Controller Link Network Diagnostic Tool

    Controller Link network made up of computers and CS/CJ-series, CVM1/CV-series, and C-series nodes, checking for errors in the node settings, and collecting all of the nodes’ error status and error log information.
  • Page 383 (See note 2.) available for diagnosis. (If dialog box will not be displayed if there is just one Controller Link Unit in the PLC or the relay network table is not registered.) Note 3: The confirmation dialog box will be displayed Node diagnosis will be performed 4.
  • Page 384 Displays the node configuration of the Controller Link network, which was read by executing the network status diagnosis operation. The node status is indicated by the color of its bitmap icon. (6) Diagnostic results area Displays the results of the network status diagnosis.
  • Page 385: Diagnosing Network Status

    Diagnosing Network Status Description of Network Status A list of the nodes participating in the specified network is displayed to show the network status. The operating status of the CPU Unit or Controller Link Unit/Board is diagnosed and information on any detected errors is displayed.
  • Page 386 10-1-2 Diagnosing Network Status Diagnosing Network Status 1. Check that the CX-Integrator is online with the PLC connected through Controller Link ad select Tools – Controller Link tool – Network Diagnosis. 2. The Select Network Dialog Box will be displayed.
  • Page 387 Repeater Units. Main lines and branch lines can be distinguished, and line disconnections in front of Repeater Units can be easily determined. Up to two hierarchies are supported by CLK Repeater Units. If three or more T-branch hierarchies are entered, the following message will be displayed and operation will stop.
  • Page 388 T-branches, and then restart the Diagnostic Tool. For details, refer to the Controller Link Repeater Unit Operation Manual. • The background of the node icon will be displayed in red when there are errors in a Controller Link Unit or CPU Unit.
  • Page 389 Indicates terminating Name that is specified in the resistance. node file Displayed Icons The icon that is displayed depends on the model of the PLC, as shown below. Node icon Model CS Series CJ Series CVM1/CV Series...
  • Page 390 • With the Controller Link Network Diagnostic Tool, the nodes connected to a network Note can be registered in a node file. If a node file is selected, the nodes registered in the file will be compared to the nodes actually participating in the network and differences will be displayed using the background colors (blue or gray) of the node icons.
  • Page 391: Diagnosing Node Settings

    10-1-3 Diagnosing Node Settings Diagnosis Items The settings of all nodes participating in the specified network are read and the integrity of the overall network is diagnosed. The results of diagnosis are displayed in three levels: Error, warning, and information.
  • Page 392 • The settings for each node are displayed in a table. • The results of diagnosing the integrity of the overall network are displayed at the bottom. The results of diagnosis are displayed in three levels, as described in the following table.
  • Page 393 •Any items not supported for a particular model will be grayed out on the display. Note •If an item cannot be read from a node, the entire line for that node will be grayed out on the display. 10-13...
  • Page 394: Diagnosing Disconnections

    10-1-4 Diagnosing Disconnections Disconnection Diagnosis All nodes participating in the specified network are displayed in the order they are physically connected. If the cable has been disconnected, the locations of disconnections are displayed. Disconnection diagnosis can be used only for Optical-ring Units/Boards in token ring mode.
  • Page 395 Note The node display for disconnection diagnosis does not display errors that have occurred at the nodes (i.e., in Controller Link Units and CPU Units). If there are errors, the following message box will be displayed. Use the network status diagnosis to diagnose errors at the nodes (i.e., in Controller Link Units and CPU Units).
  • Page 396 • Click the Copy Button to copy the data for the disconnection counters to the clipboard. The data on the clipboard will be in CSV (text) format.
  • Page 397: Diagnosing Transmission Status

    The Time of beginning disconnection data recording is the time that recording disconnection information was started. This will be the time the power supply was turned ON to the node, the time the Unit at the node was restarted, or the time the disconnection counters were cleared.
  • Page 398: Node Status

    Active node changes are also counted when the power supply is turned ON to a node and the node joins the network. They can also be counted when transmission path errors occur (even if the power supply is not turned OFF and ON).
  • Page 399 • Click the Error Log Tab to display a log of errors that occurred in the past. • Select File – Save to save the error status and error log in a file. The data will be saved in CSV (text) format.
  • Page 400 • Click the Error Tab to display the current errors. • Click the Error Log Tab to display a log of the errors that occurred in the past. • Click the Clear All Button to clear the error log from the CPU Unit.
  • Page 401: Collecting Error Logs

    Select Diagnose – Collect All Error Logs from the Main Menu, or click the icon. The following display will appear while data is being collected. The data in the file will be in CSV (text) format. The data can be edited using an editor, word processor, or spreadsheet software.
  • Page 402: Echoback Test Between Nodes

    A specified data length (unit: bytes) is sent to a specified network and node. The data is sent back as is (echoback), and the results are compared. If the data agrees, it is judged a success. If not, it is judged a failure. This allows the communications load conditions between the computer and specified nodes to be tested.
  • Page 403: Executing An Echoback Test Between Nodes

    Executing an Echoback Test between Nodes 1. While online, open the Online Connection Information Window, right-click the target PLC or Unit, and select Echoback test between PLC nodes from the pop-up menu. The PLC Internode Echoback Test Dialog Box will be displayed.
  • Page 404 10-2 Echoback Test between Nodes 10-2-4 Executing an Echoback Test between Nodes Input (or confirm) the test configuration, and click the Start Button. The test results and response time will be displayed. To stop testing, click the Stop Button. 10-24...
  • Page 405: Ethernet Ping Test

    By executing a ping command in Ethernet, it is possible to determine whether a remote PLC is connected to the Ethernet network, and whether its setting as an Ethernet node (i.e., its IP address) is correct. Ethernet is the only network in which this test can be executed.
  • Page 406: Executing A Ping Test

    Executing a Ping Test 1. While online, open the Online Connection Information Window, right-click the target Unit, and select Ethernet tool – Ping test from the pop-up menu. The Ping Test Dialog Box will be displayed. 2. Input the target IP address, and click the Ping Button.
  • Page 407 Appendices...
  • Page 408: A-1 Cps File Management

    The definitions are provided in CPS file format (XML file format). CX-One applications use the information in these CPS files to recognize the CS/CJ-series Units. The CPS files are also used to create the Special I/O Unit and CPU Bus Unit settings.
  • Page 409 More than one file can be selected and installed at the same time. 3. The following dialog box will be displayed if the corresponding icon for the specified Unit/component does not exist in the folder where the CPS file will be installed.
  • Page 410 Administrator). 1. End all copies of the CX-Integrator that are currently running. 2. Go to Programs − OMRON − CX-One and then right-click CX-Integrator on the Windows Start Menu. 3. Select Run as Administrator from the pop-up menu. The CX-Integrator will start.
  • Page 411: A-2 Eds File Management

    If the EDS file already exists, the new EDS file will overwrite the previous one. If the EDS files are different to each other in version, the new EDS file will be added to the Hardware List as shown below.
  • Page 412: A-2-2 Creating Eds Files

    4. Set the node address of the device and click the OK Button. For the I/O connections and I/O size of the device, refer to the operation manual of the device. 5. Click the OK Button.
  • Page 413: A-2-3 Deleting Eds Files

    The following window will be displayed to specify the name of the folder where the EDS file will be saved and the name of the EDS file. 3. Input the folder and file names and click the Save Button The EDS file will be saved.
  • Page 414: A-2-5 Searching Eds Files

    1. Select the hardware (device) from the Hardware List. 2. Select EDS File and Property. The following window will be displayed. The time and date of the creation of the EDS file will be displayed along with device information on the file.
  • Page 415: A-3 Precautions When Using Windows Vista Or Windows 7

    Tools − Update DTM Catalog If the above operations are performed after starting the CX-Integrator with the normal method, the results of the above operations will not be applied for other user accounts due to the effects of user management by Windows security.
  • Page 416 A-3 Precautions When Using Windows Vista or Windows 7 A-2-6 Displaying EDS File Properties A-10...
  • Page 417 Revision History A manual revision code appears as a suffix to the catalog number on the cover of the manual. Cat. No. W464-E1-06 Revision code The following table outlines the changes made to the manual during each revision. Page numbers refer to the previous version.

Table of Contents