Pulse Outputs
Pulse output
Error Counter
Reset Output
Positioning
Completed
Signal
Origin Search Operation
Setting
Origin Detection Method
Operating Mode 2 (with Error Counter Reset Output, with Positioning
Completed Input)
This operating mode is the same as mode 1, except the Positioning Com-
pleted Signal (INP) from the Servo Driver is used. Connect the Positioning
Completed Signal from the Servo Driver to a normal input (origin search 0 to 3
input).
If origin compensation is not being applied, the Positioning Completed Signal
is checked after the Error Counter Reset Output. If origin compensation is
being applied, the Positioning Completed Signal is checked after the compen-
sation operation is completed.
1
0
1
0
Select either of the following two reverse modes for the origin search opera-
tion pattern.
Setting
0: Reversal mode 1
1: Reversal mode 2
The origin detection method depends on the Origin Proximity Input Signal set-
tings. Select one of the following three methods in each port's parameters.
Setting
0: Origin Proximity Input Signal
reversal required.
1: Origin Proximity Input Signal
reversal not required.
2: Origin Proximity Input Signal not
used.
Stop
Description
When the limit input signal is received in the origin search
direction, reverse and continue operation.
When the limit input signal is received in the origin search
direction, generate an error and stop operation.
Reads the first Origin Input Signal after the Ori-
gin Proximity Input Signal goes
OFF→ON→OFF.
Reads the first Origin Input Signal after the Ori-
gin Proximity Input Signal goes OFF→ON.
Just read the Origin Input Signal without using
the Origin Proximity Input Signal.
Section 5-3
Time
Description
261