Trial Operation and Debugging
10-2-3 Online Editing
Precautions
Online Editing from the CX-Programmer
1,2,3...
568
The Online Editing function is used to add to or change part of a program in a
CPU Unit directly from the CX-Programmer when the CPU Unit is in MONI-
TOR or PROGRAM mode. This function is designed for minor program
changes without stopping the CPU Unit.
Online editing is possible simultaneously from more than one computer run-
ning the CX-Programmer as long as different tasks are edited.
Operating in
MONITOR mode.
The cycle time will be increased by from one to several cycle times if the pro-
gram in the CPU Unit is edited online in MONITOR mode. The cycle time will
also be increased to back up data in the flash memory after online editing.
The BKUP indicator will be lit during this period and the progress of the
backup will be displayed on the CX-Programmer. The increases per cycle are
listed in the following table.
CPU Unit
CP1H CPU Units
There is a limit to the number of edits that can be made consecutively. The
actual number depends on the type of editing that is performed, but 40 edits
should be used as a guideline. A message will be displayed on the CX-Pro-
grammer if the limit is exceeded, and further editing will not be possible until
the CPU Unit has completed backing up the data.
The length of time that the cycle time is extended due to online editing is
almost unaffected by the size of the task program being edited.
The cycle time will be longer than normal when a program is overwritten using
Online Editing in MONITOR mode, so make sure that the amount of time that
it is extended will not exceed the cycle monitoring time set in the PLC Setup. If
it does exceed the monitoring time, then a Cycle Time Over error will occur,
and the CPU Unit will stop. Restart the CPU Unit by selecting PROGRAM
mode first before changing to RUN or MONITOR mode.
Note If the task being edited online contains a block program, then previous execu-
tion information, such as Standby (WAIT) or Pause status, will be cleared by
online editing, and the next execution will be from the beginning.
1. Display the program section that will be edited.
2. Select the instructions to be edited.
3. Select Program - Online Edit - Begin.
Online Editing
CX-Programmer
Program section changed
Increase in cycle time
Online editing
26 ms max.
4% of cycle time
Section 10-2
Backup to flash memory