Connections to Serial Communications Option Boards
Recommended RS-422A/485 Wiring Examples
Use the following wiring methods for RS-422A/485 to maintain transmission quality.
1. Always use shielded twisted-pair cables as communications cables.
Model
CO-HC-ESV-3Px7/0.2
2. Connect the shield of the communications cable to the FG terminal on the RS-422A/485 Option Board. At
the same time, ground the ground (GR) terminal of the CPU Unit to 100 Ω or less.
Note Always ground the shield only at the RS-422A/485 Option Board end. Grounding both ends of the shield
may damage the device due to the potential difference between the ground terminals.
Connection examples are shown below.