Omron CP1H CPU Operation Manual page 688

Cp1h cpu unit
Hide thumbs Also See for CP1H CPU:
Table of Contents

Advertisement

Auxiliary Area Allocations by Address
Address
Name
Words
Bits
A322
All
Pulse Output
and
2 PV
A323
A324
All
Pulse Output
and
3 PV
A325
A326
A326.00 Pulse Output
2 Accel/Decel
Flag
A326.01 Pulse Output
2
Overflow/
Underflow
Flag
A326.02 Pulse Output
2 Output
Amount Set
Flag
A326.03 Pulse Output
2 Output
Completed
Flag
654
Function
Contain the number of pulses output
from the corresponding pulse output
port.
PV range: 80000000 to 7FFFFFFF
hex
(-2,147,483,648 to 2,147,483,647)
When pulses are being output in the
CW direction, the PV is incremented
by 1 for each pulse.
When pulses are being output in the
CCW direction, the PV is decre-
mented by 1 for each pulse.
PV after overflow: 7FFFFFFF hex
PV after underflow: 80000000 hex
A323 contains the leftmost 4 digits
and A322 contains the rightmost 4
digits of the pulse output 2 PV.
A325 contains the leftmost 4 digits
and A324 contains the rightmost 4
digits of the pulse output 3 PV.
Cleared when operation starts.
Note
If the coordinate system is
relative coordinates (unde-
fined origin), the PV will be
cleared to 0 when a pulse
output starts, i.e. when a
pulse
output
instruction
(SPED(885), ACC(888), or
PLS2(887)) is executed.
This flag will be ON when pulses are
being output from pulse output 2
according to an ACC(888) or
PLS2(887) instruction and the output
frequency is being changed in steps
(accelerating or decelerating).
Cleared when operation starts or
stops.
OFF: Constant speed
ON: Accelerating or decelerating
This flag indicates when an overflow
or underflow has occurred in the
pulse output 2 PV.
Cleared when operation starts.
OFF: Normal
ON: Overflow or underflow
ON when the number of output
pulses for pulse output 2 has been
set with the PULS(886) instruction.
Cleared when operation starts or
stops.
OFF: No setting
ON: Setting made
ON when the number of output
pulses set with the PULS(886) or
PLS2(887) instruction has been out-
put through pulse output 2.
Cleared when operation starts or
stops.
OFF: Output not completed.
ON: Output completed.
Settings
Status
Status
after
at star-
mode
change
---
---
Cleared
Cleared
---
---
Cleared
---
---
Cleared
---
---
Cleared
---
---
Cleared
Appendix D
Write
Related
timing
flags, set-
tup
tings
Refreshed
---
each cycle
during
oversee
---
process.
Refreshed
when the
INI(880)
instruction
is exe-
cuted (PV
change).
Refreshed
---
each cycle
during
oversee
process.
Cleared
---
when the
PV is
changed
by the
INI(880)
instruction.
Refreshed
when an
overflow or
underflow
occurs.
Refreshed
---
when the
PULS(886)
instruction
is exe-
cuted.
Refreshed
when pulse
output
stops.
Refreshed
---
at the start
or comple-
tion of
pulse out-
put in inde-
pendent
mode.