Analog I/O Units
Analog Output Signal
Ranges
−10 to 10 V
The hexadecimal values F448 to 0BB8 (−3000 to 3000) correspond to an ana-
log voltage range of −10 to 10 V. The entire output range is −11 to 11 V. Spec-
ify a negative voltage as a two's complement.
11 V
10 V
F31C
F448
8000
(−3300)
(−3000)
0000 (0)
0 to 10 V
The hexadecimal values 0000 to 1770 (0 to 6000) correspond to an analog
voltage range of 0 to 10 V. The entire output range is −0.5 to 10.5 V. Specify a
negative voltage as a two's complement.
10.5 V
10 V
FED4
8000
(−300)
0000 (0)
1 to 5 V
The hexadecimal values 0000 to 1770 (0 to 6000) correspond to an analog
voltage range of 1 to 5 V. The entire output range is 0.8 to 5.2 V.
5.2 V
1 V
8000
FED4
(−300)
0 V
0CE4
0BB8
(3300)
(3000)
−10 V
−11 V
0 V
1770
189C
(6000)
(6300)
−0.5 V
5 V
0.8 V
1770
189C
0 V
(6000)
(6300)
Section 7-4
Conversion Data
7FFF
Hexadecimal (Decimal)
Conversion Data
7FFF
Hexadecimal (Decimal)
Conversion Data
7FFF
Hexadecimal (Decimal)