Omron CP1H CPU Operation Manual page 480

Cp1h cpu unit
Hide thumbs Also See for CP1H CPU:
Table of Contents

Advertisement

CompoBus/S I/O Link Units
NODE NUMBER
ON
Note: The long-distance communications
mode can be used only when one of
the following Master Units is
connected: C200HW-SRM21-V1,
CQM1-SRM21-V1, or SRM1-C0@-V2.
446
(2) DIP Switch
Used to specify the node number for the CompoBus/S I/O Link Unit.
(Refer to the following table.)
Pin labels
1
2
4
8
SW1
DR
HOLD
(3) LED Indicators
Used to show the CompoBus/S communications status.
Indicator
Name
COMM
Communications
indicator
ERR
Error indicator
(4) Expansion I/O Connecting Cable
Connected to the expansion connector of a CP1H CPU Unit or a CP-
series Expansion Unit or Expansion I/O Unit. The cable is provided with
the CompoBus/S I/O Link Unit and cannot be removed.
Note Do not touch the cables during operation. Static electricity may
cause operating errors.
(5) Expansion Connector
Used to connect CP-series Expansion Units or Expansion I/O Units.
Contents
SW1
Node Number
Setting
8
4
2
0
0
0
0
1
0
0
0
2
0
0
1
3
0
0
1
4
0
1
0
5
0
1
0
6
0
1
1
7
0
1
1
8
1
0
0
9
1
0
0
10
1
0
1
11
1
0
1
12
1
1
0
13
1
1
0
14
1
1
1
15
1
1
1
1 = ON, 0 = OFF
ON
Long-distance communications mode (See note.)
OFF
High-speed communications mode
ON
Retain inputs after a communications error.
OFF
Clear inputs after a communications error.
Color
Yellow
ON: Communications in progress.
OFF: Communications stopped or error
has occurred.
Red
ON: A communications error has
occurred.
OFF: Indicates normal communications
or stand-by.
Section 7-6
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
Meaning