Dm Area Allocation - Omron CP1H CPU Operation Manual

Cp1h cpu unit
Hide thumbs Also See for CP1H CPU:
Table of Contents

Advertisement

Memory Allocations
9-9-2

DM Area Allocation

The memory allocation about system setup is shown as the following diagram.
These data will be allocated to the DM area of PLC. The beginning DM chan-
nel n is calculated by the following equation.
Note 1. DM area from n to n+154 can only display all of the settings stared in the
unit. Modification in this area is invalid to the CP1W-CIF41 Ethernet Option
Board.
2. DM area n+155 and n+156 will display the IP address used by the CP1W-
CIF41 when the power is turned ON.
3. When the IP address is illegal, such as using CLASS D, CLASS E IP
address, the values in words n+3 and n+155 will be different, and the
CP1W-CIF41 will temporarily use the default IP address (192.168.250.1).
Use this IP address to modify the IP address settings through Web
browser.
n = DM32000 + 300×(0xFD - Unit Address)
Offset
D15
n
Mode setting (2 bytes)
n+1
FINS/TCP port number (2 bytes)
n+2
FINS/UDP port number (2 bytes)
n+3
IP address (4 bytes)
n+5
Subnet mask (4 bytes)
n+7
Reserved (2 bytes)
n+8
IP address table (194 bytes)
n+105
IP router table (66 bytes)
n+138
FINS/TCP connection setup (22 bytes)
n+149
HTTP server setup (10 bytes)
n+154
FINS node address (2 bytes)
n+155
Using IP Address Display/Setting Area (4 bytes)
The following table describes the unit address for each option port.
Option Port No.
Option port 1
Option port 2
I/O Capacity
Unit Address
14/20
0xFC
30/40/60
0xFD
30/40/60
0xFC
Section 9-9
D0
Range of Status Area
DM32300 to DM32456
DM32000 to DM32156
DM32300 to DM32456
539