FX Series Positioning Controllers
7.3.6
Reading / Changing the parameters
Read or change the contents of the parameters in the positioning unit. The system parameters
cannot be changed.
Buffer memory No.
#9200 to #9513
(X axis only in the FX
Section 4.)
Sequence program example
Change the acceleration/deceleration time of the X axis.
Drive
input
Data change timing
The data can be written to the buffer memories without regard to the mode (AUTO or MANU) of
the positioning unit. However, if some parameters are changed during operation, correct posi-
tioning may not be realized.
Make sure to change the parameters before starting operation (that is, before entering the start
input). The contents of the parameters are reset to those set by a peripheral unit when the
power of the positioning unit is turned OFF.
-10GM. Also, some parameters are not available. For details, refer to
2N
FNC79
K 0
K9216
[D]TO
Special
BFM
unit No.0
FNC79
K 0
K9218
[D]TO
Communication with Programmable Controller 7
Programmable
D400
K1
controller
D401, D400
Transfer
Number of
source
transfers
Programmable
D402
K1
controller
D403, D402
→
Positioning Unit No.
BFM #9217, #9216
(D9217, D9216)
→
Positioning Unit No.
BFM #9219, #9218
(D9219, D9218)
7-12