8.3 Connecting Peripheral Devices

8.3
Connecting Peripheral Devices
Figure 8.1
illustrates how to configure the drive and motor to operate with various peripheral devices.
For more detailed instructions on how to install each device shown below, refer to the specific manual for that device.
Figure 8.1
Power
Supply
Line
Breaker
(MCCB)
and/or
Leakage
Breaker
Magnetic
Contactor
(MC)
AC Reactor
Zero-phase
Reactor
Fuse
Input Side
Noise Filter
<1>
Terminals +1 and +2 for connecting a DC choke are available only in units CIMR-A2A0004 to 0081 and CIMR-A40002 to 0044.
Drives above have built in DC chokes.
<2>
Terminals B1 and B2 for connecting a braking resistor are available only in units CIMR-A2A0004 to 0138 and CIMR-A40002 to
0072.
<3>
When using an external braking chopper in drives from CIMR-A2A0004 to 0138 and CIMR-A40002 to 0072 connect the
chopper to drive terminals B1 and -. When using larger drives connect the chopper to terminals +3 and -.
416
LED Operator/LCD Operator
Drive
+2
+1
DC Reactor
<1>
Ground
R/L1 S/L2
T/L3
U/T1V/T2W/T3
24 V control
power supply
unit
Figure 8.1 Connecting Peripheral Devices
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
USB Cable
USB Copy unit
(Type-AB)
PC
USB Cable
(Type-AB, sold separately)
<2>
B1 B2
Thermal Relay
Braking Resistor
or
Braking Resistor Unit
Output Side
Noise Filter
Motor
Magnetic
Zero-phase
Contactor
Reactor
(switches to
line power)
Ground
Engineering Software Tools
DriveWizard
DriveWorksEZ
<3>
+3(B1)
Braking Unit