B.3 Parameter Table
T3: ASR and Inertia Tuning
No. (Addr.)
Name
T3-01
Test Signal Frequency
(760H)
T3-02
Test Signal Amplitude
(761H)
T3-03
Motor Inertia
(762H)
T3-04
(763H)
System Response Frequency
<40>
<9> Default setting value is dependent on the drive model (o2-04) and the Drive Duty (C6-01).
<14> Default setting value is dependent on the motor code set to E5-01.
<40> Displayed only when performing Inertia Tuning or ASR Gain Auto-Tuning (T1-01 = 9 or T2-01 = 9).
 U: Monitors
Monitor parameters allow the user to view drive status, fault information, and other data concerning drive operation.
U1: Operation Status Monitors
No. (Addr.)
Name
U1-01
Frequency Reference
(40H)
U1-02
Output Frequency
(41H)
U1-03
Output Current
(42H)
U1-04
Control Method
(43H)
U1-05
Motor Speed
(44H)
U1-06
Output Voltage Reference
(45H)
U1-07
DC Bus Voltage
(46H)
U1-08
Output Power
(47H)
U1-09
Torque Reference
(48H)
510
V/f
V/f w/PG
OLV/PM
AOLV/PM
Sets the frequency of the test signal used during Inertia Tuning and ASR Gain Auto-Tuning.
Reduce this value if the inertia is large or if a fault occurs.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Sets the amplitude of the test signal used during Inertia and ASR Gain Auto-Tuning. Reduce
this value if the inertia is too large or if a fault occurs.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Sets the motor inertia. Default setting is the inertia of a YASKAWA motor.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Sets the response frequency of the mechanical system connected to the motor. Oscillation may
result if set too high.
All Modes
Monitors the frequency reference. Display units are determined by o1-03.
All Modes
Displays the output frequency. Display units are determined by o1-03.
All Modes
Displays the output current.
Note: The unit is expressed in 1 A for models CIMR-A4A0930 and 4A1200.
All Modes
0: V/f Control
1: V/f Control with PG
2: Open Loop Vector Control
3: Closed Loop Vector Control
5: Open Loop Vector Control for PM
6: Advanced Open Loop Vector Control for PM
7: Closed Loop Vector Control for PM
V/f
V/f w/PG
OLV/PM
AOLV/PM
Displays the motor speed feedback. Display units are determined by o1-03.
All Modes
Displays the output voltage.
All Modes
Displays the DC bus voltage.
All Modes
Displays the output power (this value is calculated internally).
V/f
V/f w/PG
OLV/PM
AOLV/PM
Monitors the internal torque reference.
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
Description
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
Description
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
Setting
Page
Default: 3.0 Hz
Min: 0.1 Hz
133
Max: 20.0 Hz
Default: 0.5 rad
Min: 0.1 rad
133
Max: 10.0 rad
Default:
<9> <14>
2
Min: 0.0001 kgm
133
Max: 600.00 kgm
2
Default: 10.0 Hz
Min: 0.1 Hz
133
Max: 50.0 Hz
Analog Output
Unit
Page
Level
10 V: Max frequency 
0.01 Hz
(-10 to +10 V)
10 V: Max frequency
0.01 Hz
(-10 to +10 V)
10 V: Drive rated
<19> <23>
current
No signal output
available
10 V: Max Frequency 
0.01 Hz
(-10 to +10 V)
10 V: 200 Vrms
0.1 Vac
<18>
10 V: 400 V
1 Vdc
<18>
10 V: Drive rated
power (kW)
<60>
<22>
(-10 to +10 V)
10 V: Motor rated
torque 
0.1%
(-10 to +10 V)