YASKAWA A1000 Technical Manual page 476

High performance vector control drive type: cimr-a series models: 200 v class: 0.55 to 110 kw, 400 v class: 0.55 to 630 kw
Hide thumbs Also See for A1000:
Table of Contents

Advertisement

B.3 Parameter Table
No.(Addr.)
Name
F1-51
PGoH Detection Level
(3D3H)
F1-52
Communication Speed of Serial
(3D4H)
Encoder Selection
<10> Default setting is determined by the control mode (A1-02).
F2: Analog Input Card (AI-A3)
No.(Addr.)
Name
F2-01
Analog Input Option Card
(38FH)
Operation Selection
F2-02
(368H)
Analog Input Option Card Gain
F2-03
(369H)
Analog Input Option Card Bias
F3: Digital Input Card (DI-A3)
No.(Addr.)
Name
F3-01
Digital Input Option Card Input
(390H)
Selection
F3-03
Digital Input Option DI-A3 Data
(3B9H)
Length Selection
F4: Analog Monitor Card (AO-A3)
No.(Addr.)
Name
F4-01
Terminal V1 Monitor Selection
(391H)
F4-02
(392H)
Terminal V1 Monitor Gain
F4-03
Terminal V2 Monitor Selection
(393H)
F4-04
(394H)
Terminal V2 Monitor Gain
476
V/f
V/f w/PG
OLV/PM
AOLV/PM
Sets the level for detecting PG Hardware Fault (PGoH). Available when F1-20 = 1
Note: This parameter is not available with models CIMR-A4A0930 and 4A1200.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Selects the communication speed between the PG-F3 option and serial encoder.
0: 1M bps/9600 bps (EnDat 2.2/22 / Hiperface)
1: 500k bps/19200 bps (EnDat 2.2/22 / Hiperface)
2: 1M bps/38400 bps (EnDat 2.2/22 / Hiperface)
3: 1M bps/38400 bps (EnDat 2.2/22 / Hiperface)
Note: This parameter is not available with models CIMR-A4A0930 and 4A1200.
All Modes
0: Option card input terminals V1, V2, and V3 replace drive input terminals A1, A2, and A3.
1: Input signals to terminals V1, V2, and V3 are added together to create the frequency
reference.
All Modes
Sets the gain for the input signal to the analog card.
All Modes
Sets the bias for the input signal to the analog card.
All Modes
0: BCD, 1% units
1: BCD, 0.1% units
2: BCD, 0.01% units
3: BCD, 1 Hz units
4: BCD, 0.1 Hz units
5: BCD, 0.01 Hz units
6: BCD customized setting (5 digit), 0.02 Hz units
7: Binary input
The unit and the setting range are determined by F3-03.
F3-03 = 0: 255/100% (-255 to+255)
F3-03 = 1: 40961/100% (-4095 to +4095)
F3-03 = 2: 30000/100% (-33000 to+33000)
When the digital operator units are set to be displayed in Hertz or user-set units (o1-03 = 2 or 3),
the units for F3-01 are determined by parameter o1-03.
All Modes
0: 8 bit
1: 12 bit
2: 16 bit
All Modes
Sets the monitor signal for output from terminal V1. Set this parameter to the last three digits of
the desired U- monitor. Some U parameters are available only in certain control modes.
All Modes
Sets the gain for voltage output via terminal V1.
All Modes
Sets the monitor signal for output from terminal V2. Set this parameter to the last three digits of
the desired U- monitor. Some U parameters are available only in certain control modes.
All Modes
Sets the gain for voltage output via terminal V2.
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
Description
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
Description
Description
Description
Setting
Page
Default: 80%
Min: 1%
228
Max: 100%
Default: 0
Min: 0
228
Max: 3
Setting
Page
Default: 0
Min: 0
228
Max: 1
Default: 100.0%
Min: -999.9%
229
Max: 999.9%
Default: 0.0%
Min: -999.9%
229
Max: 999.9%
Setting
Page
Default: 0
Min: 0
229
Max: 7
Default: 2
Min: 0
229
Max: 2
Setting
Page
Default: 102
Min: 000
230
Max: 999
Default: 100.0%
Min: -999.9%
230
Max: 999.9%
Default: 103
Min: 000
230
Max: 999
Default: 50.0%
Min: -999.9%
230
Max: 999.9%