Figure D.12
Safety Relay or PLC
with safety functionality
<1> Available slide switch S6 is models ETC740310 and ETC740311.
N.O.
N.O.
N.C.
N.C.
ETC740310
ETC740311
Disabling and Enabling the Drive Output ("Safe Torque Off")
Figure D.13
illustrates the Safe Disable input operation.
Figure D.13
Frequency
Run Command
H1, H2 Input
Drive Output
Entering the "Safe Torque Off" State
Whenever either one Safe Disable input or both inputs open, the motor torque is shut off by switching off the drive
output. If the motor was running before the Safe Disable inputs opened, then the motor will coast to stop, regardless of
the stopping method set in parameter b1-03.
Notice that the "Safe Torque Off" state can only be achieved using the Safe Disable function. Removing the Run
command stops the drive and shuts the output off (baseblock), but does not create a "Safe Torque Off" status.
Note: To avoid an uncontrolled stop during normal operation, make sure that the Safe Disable inputs are opened first when the motor
has completely stopped.
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
HC
Safety
Outputs
Feedback
H1
H2
DM+
DM-
Drive
Figure D.12 Safe Disable Function Wiring Example (Source Mode)
Output
Run
ON (Safe Disable off)
OFF (Safe Disable activated)
Normal operation
Figure D.13 Safe Disable Operation
24 Vdc
Control
Circuit
Jumper S3
Setting:
SOURCE
Gate Block 1
Gate Block 2
>=1
N.O.
N.C.
Slide Switch S6
<1>
Motor coasts
to stop
Run Command must be
released to deactivate
Safe Disable
Stop
Safe Torque-Off
Baseblock (Not Safe!)
D.4 Safe Disable Input Function
Main Power
N
Power Module P
Motor
Drive is ready for
operation
D
601