No. (Addr.)
Name
n8-69
Speed Calculation Gain
(65DH)
n8-72
Speed Estimation Method
(655H)
Selection
n8-84
Polarity Judge Current
(2D3H)
<14> Default setting value is dependent on the motor code set to E5-01.
<17> Default setting is dependent on the speed estimation method selection (n8-72) as follows:
50.0 when n8-72 = 0
150.0 when n8-72 = 1
<18> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
o: Operator Related Settings
The o parameters are used to set up the digital operator displays.
o1: Digital Operator Display Selection
No. (Addr.)
Name
o1-01
(500H)
Drive Mode Unit Monitor
Selection
o1-02
(501H)
User Monitor Selection after
Power Up
o1-03
Digital Operator Display Selection
(502H)
o1-04
V/f Pattern Display Unit
(503H)
o1-05
(504H)
LCD Contrast Control
o1-10
User-Set Display Units Maximum
(520H)
Value
o1-11
User-Set Display Units Decimal
(521H)
Display
<10> Default setting is determined by the control mode (A1-02).
<36> Default setting value is determined by the digital operator display selection (o1-03).
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
V/f
V/f w/PG
OLV/PM
AOLV/PM
There is normally no need to change this parameter from the default value.
Sets the proportional gain for Speed Estimation.
V/f
V/f w/PG
OLV/PM
AOLV/PM
There is normally no need to change this parameter from the default value.
Sets the method to be used for estimating the speed.
0: Conventional method
1: A1000 method
Note: This parameter is not available with models CIMR-A4A0930 and 4A1200.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Sets the current to determine polarity for the initial polarity calculation as a percentage of the
motor rated current.
100% = Motor rated current
Note: If an "Si" value is listed on the nameplate for a YASKAWA motor, n8-84 should be set to
"Si" value 2.
All Modes
Switches the display after the power has been turned on. When using an LED operator, pressing
the up arrow key will display the following data: frequency reference rotational direction
output frequency output current output voltage U1-.
(This is done by entering the 1 part of U1-. Certain monitors are not available in some
control modes.)
All Modes
o1-02 selects the information that is displayed when the power is turned on.
1: Frequency reference (U1-01)
2: Direction
3: Output frequency (U1-02)
4: Output current (U1-03)
5: User-selected monitor (set by o1-01)
All Modes
Sets the units the drive should use to display the frequency reference and motor speed monitors.
0: 0.01 Hz
1: 0.01% (100% = E1-04)
-1
2: min
(calculated using the number of motor poles setting in E2-04, E4-04, or E5-04)
3: User-selected units (set by o1-10 and o1-11)
V/f
V/f w/PG
OLV/PM
AOLV/PM
0: Hz
-1
1: min
All Modes
Sets the brightness of the LCD operator (option).
All Modes
These settings define the display values when o1-03 is set to 3.
o1-10 sets the display value that is equal to the maximum output frequency.
o1-11 sets the position of the decimal position.
Description
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
Description
OLV
CLV
CLV/PM
B.3 Parameter Table
Setting
Page
Default: 1.00
Min: 0.00
312
Max: 20.00
Default: 1
Min: 0
313
Max: 1
Default: 100%
Min: 0%
313
Max: 150%
Setting
Page
Default: 106 (Monitor
U1-06)
314
Min: 104
Max: 813
Default: 1
Min: 1
314
Max: 5
Default:
<10>
Min: 0
314
Max: 3
Default:
<10>
Min: 0
315
Max: 1
Default: 3
Min: 0
315
Max: 5
Default:
<36>
Min: 1
315
Max: 60000
Default:
<36>
Min: 0
315
Max: 3
505
B