No. (Addr.)
Name
n8-69
Speed Calculation Gain
(65DH)
n8-72
Speed Estimation Method
(655H)
Selection
n8-84
Polarity Judge Current
(2D3H)
<14> Default setting value is dependent on the motor code set to E5-01.
<17> Default setting is dependent on the speed estimation method selection (n8-72) as follows:
50.0 when n8-72 = 0
150.0 when n8-72 = 1
<18> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
 o: Operator Related Settings
The o parameters are used to set up the digital operator displays.
o1: Digital Operator Display Selection
No. (Addr.)
Name
o1-01
(500H)
Drive Mode Unit Monitor
Selection
o1-02
(501H)
User Monitor Selection after
Power Up
o1-03
Digital Operator Display Selection
(502H)
o1-04
V/f Pattern Display Unit
(503H)
o1-05
(504H)
LCD Contrast Control
o1-10
User-Set Display Units Maximum
(520H)
Value
o1-11
User-Set Display Units Decimal
(521H)
Display
<10> Default setting is determined by the control mode (A1-02).
<36> Default setting value is determined by the digital operator display selection (o1-03).
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
V/f
V/f w/PG
OLV/PM
AOLV/PM
There is normally no need to change this parameter from the default value.
Sets the proportional gain for Speed Estimation.
V/f
V/f w/PG
OLV/PM
AOLV/PM
There is normally no need to change this parameter from the default value.
Sets the method to be used for estimating the speed.
0: Conventional method
1: A1000 method
Note: This parameter is not available with models CIMR-A4A0930 and 4A1200.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Sets the current to determine polarity for the initial polarity calculation as a percentage of the
motor rated current.
100% = Motor rated current
Note: If an "Si" value is listed on the nameplate for a YASKAWA motor, n8-84 should be set to
"Si" value  2.
All Modes
Switches the display after the power has been turned on. When using an LED operator, pressing
the up arrow key will display the following data: frequency reference  rotational direction 
output frequency  output current  output voltage  U1-.
(This is done by entering the 1 part of U1-. Certain monitors are not available in some
control modes.)
All Modes
o1-02 selects the information that is displayed when the power is turned on.
1: Frequency reference (U1-01)
2: Direction
3: Output frequency (U1-02)
4: Output current (U1-03)
5: User-selected monitor (set by o1-01)
All Modes
Sets the units the drive should use to display the frequency reference and motor speed monitors.
0: 0.01 Hz
1: 0.01% (100% = E1-04)
-1
2: min
(calculated using the number of motor poles setting in E2-04, E4-04, or E5-04)
3: User-selected units (set by o1-10 and o1-11)
V/f
V/f w/PG
OLV/PM
AOLV/PM
0: Hz
-1
1: min
All Modes
Sets the brightness of the LCD operator (option).
All Modes
These settings define the display values when o1-03 is set to 3.
o1-10 sets the display value that is equal to the maximum output frequency.
o1-11 sets the position of the decimal position.
Description
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
Description
OLV
CLV
CLV/PM
B.3 Parameter Table
Setting
Page
Default: 1.00
Min: 0.00
312
Max: 20.00
Default: 1
Min: 0
313
Max: 1
Default: 100%
Min: 0%
313
Max: 150%
Setting
Page
Default: 106 (Monitor
U1-06)
314
Min: 104
Max: 813
Default: 1
Min: 1
314
Max: 5
Default:
<10>
Min: 0
314
Max: 3
Default:
<10>
Min: 0
315
Max: 1
Default: 3
Min: 0
315
Max: 5
Default:
<36>
Min: 1
315
Max: 60000
Default:
<36>
Min: 0
315
Max: 3
505