B.3 Parameter Table
C2: S-Curve Characteristics
No.(Addr.)
Name
C2-01
S-Curve Characteristic at Accel
(20BH)
Start
C2-02
S-Curve Characteristic at Accel
(20CH)
End
C2-03
S-Curve Characteristic at Decel
(20DH)
Start
C2-04
S-Curve Characteristic at Decel
(20EH)
End
<10> Default setting is determined by the control mode (A1-02).
C3: Slip Compensation
No.(Addr.)
Name
C3-01
(20FH)
Slip Compensation Gain
C3-02
(210H)
Slip Compensation Primary Delay
Time
C3-03
Slip Compensation Limit
(211H)
C3-04
Slip Compensation Selection
(212H)
during Regeneration
C3-05
Output Voltage Limit Operation
(213H)
Selection
Output Voltage Limit Operation
C3-16
Start Level (Percentage
(261H)
Modulation)
C3-17
Maximum Output Voltage Limit
(262H)
Level (Percentage Modulation)
C3-18
Output Voltage Limit Level
(263H)
C3-21
(33EH)
Motor 2 Slip Compensation Gain
C3-22
(241H)
Motor 2 Slip Compensation
Primary Delay Time
C3-23
Motor 2 Slip Compensation Limit
(242H)
462
All Modes
The S-curve can be controlled at the four points shown below.
Run Command
Output Frequency
V/f
V/f w/PG
OLV/PM
AOLV/PM
Sets the gain for the motor slip compensation function used for motor 1.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Adjusts the slip compensation function delay time used for motor 1.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Sets an upper limit for the slip compensation function as a percentage of motor rated slip for
motor 1 (E2-02).
V/f
V/f w/PG
OLV/PM
AOLV/PM
0: Disabled.
1: Enabled above 6 Hz.
2: Enabled whenever slip compensation is possible.
V/f
V/f w/PG
OLV/PM
AOLV/PM
0: Disabled.
1: Enabled. Automatically decreases motor flux when output voltage saturation is reached.
Note: Available control mode for parameter C3-05 varies by drive model:
CIMR-A2A0004 to 2A0415 and 4A0002 to 4A0675: Available when A1-02 = 2, 3
CIMR-A4A0930 and 4A1200: Available when A1-02 = 2, 3, 6, 7
V/f
V/f w/PG
OLV/PM
AOLV/PM
Sets the output voltage limit operation start level (percentage modulation) when C3-05 is
enabled.
Note: This parameter is available in models CIMR-A4A0930 and 4A1200.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Sets the output voltage limit operation determined by C3-18 (percentage modulation) when
C3-05 is enabled.
Note: This parameter is available in models CIMR-A4A0930 and 4A1200.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Sets the maximum percentage of output voltage reduction when parameter C3-05 is enabled.
Note: This parameter is available in models CIMR-A4A0930 and 4A1200.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Sets the slip compensation gain used for motor 2.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Sets the slip compensation delay time used for motor 2.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Sets the upper limit for the slip compensation function for motor 2. Set as a percentage of the
motor rated slip (E4-02).
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
Description
ON
OFF
C2-02
C2-03
C2-01
C2-04
Time
Description
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
Setting
Page
Default: 0.20 s
<10>
Min: 0.00 s
185
Max: 10.00 s
Default: 0.20 s
Min: 0.00 s
185
Max: 10.00 s
Default: 0.20 s
Min: 0.00 s
185
Max: 10.00 s
Default: 0.00 s
Min: 0.00 s
185
Max: 10.00 s
Setting
Page
Default:
<10>
Min: 0.0
186
Max: 2.5
Default:
<10>
Min: 0 ms
186
Max: 10000 ms
Default: 200%
Min: 0%
186
Max: 250%
Default: 0
Min: 0
186
Max: 2
Default: 0
Min: 0
187
Max: 1
Default: 85.0%
Min: 70.0%
187
Max: 90.0%
Default: 90.0%
Min: 85.0%
187
Max: 100.0%
Default: 90.0%
Min: 30.0%
187
Max: 100.0%
Default:
<15>
Min: 0.0
187
Max: 2.5
Default:
<15>
Min: 0 ms
188
Max: 10000 ms
Default: 200%
Min: 0%
188
Max: 250%