Start-Up Flowcharts - YASKAWA A1000 Technical Manual

High performance vector control drive type: cimr-a series models: 200 v class: 0.55 to 110 kw, 400 v class: 0.55 to 630 kw
Hide thumbs Also See for A1000:
Table of Contents

Advertisement

4.4

Start-Up Flowcharts

The flowcharts in this section summarize basic steps required to start the drive. Use the flowcharts to determine the most
appropriate start-up method for a given application. The charts are intended as a quick reference to help familiarize the
user with start-up procedures.
Note: 1. Function availability differs for drive models CIMR-A4A0930 and 4A1200.

CIMR-A
2. Refer to
Application Selection on page 114
Flowchart
Subchart
A
A-1
A-2
A-3
 Flowchart A: Basic Start-up and Motor Tuning
Flowchart A in
Figure 4.8
application. Use drive default parameter settings in simple applications that do not require high precision.
Figure 4.7
Note: 1. When the motor cable length has changed for more than 50 m after Auto-Tuning has been performed (e.g., after the drive has been set
up and then later installed in a different location), execute Stationary Auto-Tuning for resistance between motor lines once the drive
is installed in its final installation location.
2. Auto-Tuning should be performed again after installing an AC reactor or other such components to the output side of the drive.
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
to set up the drive using one of the application presets.
Basic startup procedure and motor tuning
Simple motor setup using V/f mode
High-performance operation using Open Loop Vector (OLV) or Closed Loop Vector (CLV) motor control
Setting up the drive to run a permanent magnet (PM) motor
describes a basic start-up sequence. This sequence varies slightly depending on the
Install and wire the drive as explained in Chapters 1, 2, and 3
Apply main power on to the drive
Adhere to safety messages concerning application of power
Application Presets
A1-06 used ?
Set the control mode in parameter A1-02.
Set the basic parameters
C6-01 for heavy/normal duty mode selection
L3-04 if using dynamic braking options
L8-55 = 0 if using a regen converter
Control Mode
0: V/f
1: V/f w/PG
To
Flowchart A-1
Flowchart A-2
Set the parameters according to the application method.
b1-01/b1-02 for frequency reference selection and run command source selection
H1-
, H2-
, H3-
, H4-
, H6-
d1-
for using multi-speed references
C1-
and C2-
for accel/decel and S-curve time settings
Fine tune parameters. Adjust application settings (PID, ...) if necessary.
Check the machine operation and verify parameter settings.
Drive is ready to run the application.
Figure 4.8 Basic Start-up
Refer to Parameter Differences for models
for details.
Objective
START
YES
NO
A1-02 =
2: OLV
3: CLV
To
To
Flowchart A-3
From Flowchart A-1, A-2, or A-3
for I/O terminal setting
4.4 Start-Up Flowcharts
Refer to
Application
Selection section
5: OLV/PM
6: AOLV/PM
7: CLV/PM
Page
109
110
111
112
4
109