B.3 Parameter Table
A2: User Parameters
No.(Addr.)
Name
A2-01 to
A2-32
User Parameters 1 to 32
(106 to 125H)
A2-33
User Parameter Automatic
(126H)
Selection
<1> Default setting value is dependent on parameter A1-06. This setting value is 0 when A1-06 = 0, and 1 when A1-06 does not equal 0.
<2> Default setting value is determined by the Application Preset selected with parameter A1-06.
 b: Application
Application parameters configure the source of the Run command, DC Injection Braking, Speed Search, timer functions,
PID control, the Dwell function, Energy Savings, and a variety of other application-related settings.
b1: Operation Mode Selection
No.(Addr.)
Name
b1-01
Frequency Reference Selection 1
(180H)
b1-02
Run Command Selection 1
(181H)
b1-03
Stopping Method Selection
(182H)
b1-04
Reverse Operation Selection
(183H)
b1-05
Action Selection below Minimum
(184H)
Output Frequency
b1-06
Digital Input Reading
(185H)
b1-07
LOCAL/REMOTE Run Selection
(186H)
b1-08
Run Command Selection while in
(187H)
Programming Mode
b1-14
Phase Order Selection
(1C3H)
454
All Modes
Parameters that were recently edited are listed here. The user can also select parameters to
appear here for quick access.
All Modes
0: Parameters A2-01 through A2-32 are reserved for the user to create a list of User Parameters.
1: Save history of recently viewed parameters. Recently edited parameters will be saved to
A2-17 through A2-32 for quick access.
All Modes
0: Digital operator
1: Analog input terminals
2: MEMOBUS/Modbus communications
3: Option Card
4: Pulse input (terminal RP)
All Modes
0: Digital operator
1: Digital input terminals
2: MEMOBUS/Modbus communications
3: Option Card
All Modes
0: Ramp to stop
1: Coast to stop
2: DC Injection Braking to stop
3: Coast with timer
9: Simple Positioning
All Modes
0: Reverse enabled.
1: Reverse disabled.
V/f
V/f w/PG
OLV/PM
AOLV/PM
0: Operates according to frequency reference (E1-09 is disabled).
1: Output shuts off (coast to stop if less than E1-09).
2: Operates according to E1-09 (frequency reference set to E1-09).
3: Zero speed (frequency reference becomes zero when less than E1-09).
All Modes
0: Input status is read once and processed immediately (for quick response)
1: Input is read twice and processed only if the status is the same in both readings (robust
against noisy signals)
All Modes
0: An external Run command has to be cycled at the new source to be activated.
1: An external Run command at new source is accepted immediately.
All Modes
0: Run command is not accepted while in the Programming Mode.
1: Run command is accepted while in the Programming Mode.
2: Prohibit entering Programming Mode during run.
V/f
V/f w/PG
OLV/PM
AOLV/PM
0: Standard
1: Switch phase order (reverses the direction of the motor)
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
Description
Description
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
Setting
Page
Default:
<2>
Min: A1-00
147
Max: o4-13
Default: 1
<1>
Min: 0
147
Max: 1
Setting
Page
Default: 1
Min: 0
148
Max: 4
Default: 1
Min: 0
150
Max: 3
Default: 0
Min: 0
150
Max: 9
<11>
Default: 0
Min: 0
154
Max: 1
Default: 0
Min: 0
154
Max: 3
Default: 1
Min: 0
155
Max: 1
Default: 0
Min: 0
156
Max: 1
Default: 0
Min: 0
156
Max: 2
Default: 0
Min: 0
156
Max: 1