H2-
Function
Setting
3F
PID Feedback High
4A
During KEB Ride-Thru
4B
During Short-Circuit Braking
4C
During Fast Stop
4D
oH Pre-alarm Time Limit
4E
Braking Transistor Fault (rr)
4F
Braking Resistor Overheat (oH)
60
Internal Cooling Fan Alarm
61
Rotor Position Detection Complete
Memobus Regs1 (It selects it with
62
H2-07 and H2-08.)
Memobus Regs2 (It selects it with
63
H2-09 and H2-10.)
90 to 92
DriveWorksEZ Digital Outputs 1 to 3
100 to 192
Function 0 to 92 with Inverse Output
H3: Multi-Function Analog Inputs
No.(Addr.)
Name
H3-01
Terminal A1 Signal Level
(410H)
Selection
H3-02
Terminal A1 Function Selection
(434H)
H3-03
(411H)
Terminal A1 Gain Setting
H3-04
(412H)
Terminal A1 Bias Setting
H3-05
Terminal A3 Signal Level
(413H)
Selection
H3-06
Terminal A3 Function Selection
(414H)
H3-07
(415H)
Terminal A3 Gain Setting
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
H2 Multi-Function Digital Output Settings
All Modes
Closed: The PID feedback level is too high.
All Modes
Closed: KEB Ride-Thru is being performed.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Closed: Short Circuit Braking is active.
All Modes
Closed: A Fast Stop command has been entered from the operator or input terminals.
All Modes
Closed: oH pre-alarm time limit has passed.
All Modes
Closed: The built-in dynamic braking transistor failed.
Note: This set value is not available in models CIMR-A2A0169 to 2A0415, 4A0088 to 4A1200.
All Modes
Closed: The dynamic braking resistor has overheated.
Note: This set value is not available in models CIMR-A2A0169 to 2A0415, 4A0088 to 4A1200.
All Modes
Closed: Internal cooling fan alarm
V/f
V/f w/PG
OLV/PM
AOLV/PM
Closed: Drive has successfully detected the rotor position of the PM motor.
All Modes
The contact output is closed if any of the bits that are specified by H2-08 for the MEMOBUS/Modbus register address
that is set in H2-07 turns on.
Note: This set value is not available in models CIMR-A4A0930 and 4A1200.
All Modes
The contact output is closed if any of the bits that are specified by H2-10 for the MEMOBUS/Modbus register address
that is set in H2-09 turns on.
Note: This set value is not available in models CIMR-A4A0930 and 4A1200.
All Modes
Reserved for DWEZ digital output functions.
All Modes
Inverts the output switching of the multi-function output functions.
Set the last two digits of 1 to reverse the output signal of that specific function.
All Modes
0: 0 to 10 V
1: -10 to 10 V
All Modes
Sets the function of terminal A1.
All Modes
Sets the level of the input value selected in H3-02 when 10 V is input at terminal A1.
All Modes
Sets the level of the input value selected in H3-02 when 0 V is input at terminal A1.
All Modes
0: 0 to 10 V
1: -10 to 10 V
All Modes
Sets the function of terminal A3.
All Modes
Sets the level of the input value selected in H3-06 when 10 V is input at terminal A3.
Description
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
Description
B.3 Parameter Table
Page
255
255
255
255
255
255
255
255
255
255
255
255
256
Setting
Page
Default: 0
Min: 0
257
Max: 1
Default: 0
Min: 0
257
Max: 32
Default: 100.0%
Min: -999.9%
257
Max: 999.9%
Default: 0.0%
Min: -999.9%
257
Max: 999.9%
Default: 0
Min: 0
258
Max: 1
Default: 2
Min: 0
258
Max: 32
Default: 100.0%
Min: -999.9%
258
Max: 999.9%
489