YASKAWA A1000 Technical Manual page 194

High performance vector control drive type: cimr-a series models: 200 v class: 0.55 to 110 kw, 400 v class: 0.55 to 630 kw
Hide thumbs Also See for A1000:
Table of Contents

Advertisement

5.3 C: Tuning
C5-17, C5-18: Motor Inertia, Load Inertia Ratio
C5-17 and C5-18 determine the ratio of the machine inertia to the inertia of the motor being used.
Example: Setting C5-18 to 2.0 reflects a load inertia that is twice the motor inertia.
These parameters are set automatically when Inertia Tuning and ASR Tuning are performed in CLV and CLV/PM control
modes.
Refer to Auto-Tuning on page 120
No.
C5-17
C5-18
C5-21, C5-23 / C5-22, C5-24: Motor 2 ASR Proportional Gain 1, 2 / Integral Time 1, 2
These parameters function for motor 2 in the same way that C5-01 through C5-04 function for motor 1. For more details,
see
C5-01, C5-03/C5-02, C5-04: ASR Proportional Gain 1, 2 / ASR Integral Time 1, 2 on page
No.
C5-21
C5-22
C5-23
C5-24
C5-25: Motor 2 ASR Limit
Functions for motor 2 in the same way that C5-05 functions for motor 1. Sets the ASR output limit for motor 2 as a
percentage of the maximum output frequency (E4-04). For more details, see
No.
C5-25
C5-26: Motor 2 ASR Primary Delay Time Constant
Functions for motor 2 in the same way that C5-06 functions for motor 1.
Sets the filter time constant for the time from the speed loop to the torque command output. For more details, see
ASR Primary Delay Time Constant on page
Note: This parameter rarely requires adjustment.
No.
C5-26
C5-27: Motor 2 ASR Gain Switching Frequency
Functions for motor 2 in the same way that C5-07 functions for motor 1.
Sets the frequency for motor 2 to change ASR proportional gain 1 and 2 (C5-21, C5-23) as well as the integral time 1 and
2 (C5-22, C5-24). For more details, see
1, 2 on page
192.
No.
C5-27
Note: A multi-function input set for the ASR gain switch (H1- = 77) takes priority over the ASR gain switching frequency.
C5-28: Motor 2 ASR Integral Limit
Functions for motor 2 in the same way that C5-08 functions for motor 1.
Sets the upper limit for ASR as a percentage of the rated load.
No.
C5-28
194
for details on Auto-Tuning or enter the data manually.
Parameter Name
Motor Inertia
Load Inertia Ratio
Parameter Name
Motor 2 ASR Proportional Gain 1
Motor 2 ASR Integral Time 1
Motor 2 ASR Proportional Gain 2
Motor 2 ASR Integral Time 2
Parameter Name
Motor 2 ASR Limit
193.
Parameter Name
Motor 2 ASR Primary Delay Time Constant
C5-01, C5-03/C5-02, C5-04: ASR Proportional Gain 1, 2 / ASR Integral Time
Parameter Name
Motor 2 ASR Gain Switching Frequency
Parameter Name
Motor 2 ASR Integral Limit
0.0001 to 600.00 kgm
C5-05: ASR Limit on page
Setting Range
Setting Range
Setting Range
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
Setting Range
Determined by C6-01, E5-01 and
2
0.0 to 6000.0
192.
Setting Range
0.00 to 300.00
0.000 to 10.000 s
0.00 to 300.00
0.000 to 10.000 s
0.0 to 20.0%
0.000 to 0.500 s
0.0 to 400.0 Hz
Setting Range
0 to 400%
Default
o2-04
1.0
Default
Determined by E3-01
Determined by E3-01
Determined by E3-01
Determined by E3-01
193.
Default
5.0%
C5-06:
Default
Determined by E3-01
Default
0.0 Hz
Default
400%

Hide quick links: