YASKAWA A1000 Technical Manual page 61

High performance vector control drive type: cimr-a series models: 200 v class: 0.55 to 110 kw, 400 v class: 0.55 to 630 kw
Hide thumbs Also See for A1000:
Table of Contents

Advertisement

Figure 3.2
Terminals -, +1, +2, B1, B2 are
for connection options. Never
connect power supply lines to
these terminals
Main
Fuse
Switch
Three-phase
R/L1
power supply
S/L2
200 to 400 V
T/L3
50/60 Hz
Models CIMR-A 4A0930 and 4A1200 are
compatible for operation with 12-phase rectification.
Refer to 12-Phase Rectification on page
Multi-function
digtial inputs
(default setting)
Sink / Source mode
selection wire link
(default: Sink)
2 k Ω
Multi-function
analog/ pulse
train inputs
MEMOBUS/Modbus
comm. RS-422/RS-485
max. 115.2 kBps
Safety
Switch
S 2
S 1
Open
Safety relay /
controller
Figure 3.1 Drive Standard Connection Diagram (example: CIMR-A2A0040)
<1> Remove the jumper when installing a DC reactor. Models CIMR-A2A0110 through 2A0415 and 4A0058 through 4A1200 come with a
built-in DC reactor.
<2> When installing a dynamic braking option, a thermal relay sequence should also be set up to shut off power to the drive in case overheat
occurs.
<3> The drive's protection function for the internal braking transistor needs to be disabled (L8-55 = 0) if using a regen unit such as a regen
converter or some type of dynamic braking options (and therefore not the internal braking transistor). If left enabled, a braking resistor fault
(rF) may result. Make sure Stall Prevention is disabled (L3-04 = 0) whenever using a regenerative converter, a regenerative unit or a dynamic
braking option. If left enabled, the drive may not stop within the specified deceleration time.
<4> Supplying power to the control circuit separately from the main circuit requires a 24 V power supply (option).
<5> This figure shows an example of a sequence input to S1 through S8 using a non-powered relay or an NPN transistor. Install the wire link
between terminals SC-SP for Sink mode and SC-SN for Source mode. Leave it out for external power supply. Never short terminals SP and
SN as doing so will damage the drive. (see
<6> The maximum current supplied by this voltage source is 150 mA if no digital input option card DI-A3 is used.
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
DC reactor
(option)
U
U
Jumper
+
+
+
+
2
R/L1
EMC
S/L2
Main Circuit
Filter
T/L3
64.
Control Circuit
Forward Run / Stop
S 1
Reverse Run / Stop
S 2
External fault
S 3
S 4
Fault reset
Multi-speed step 1
S 5
Multi-speed step 2
S 6
Jog speed
S 7
External Baseblock
S 8
SN
SC
SP
<5>
+ 24
V
<6>
Shield ground terminal
RP
Pulse Train Input (max 32 kHz)
<8>
+
V
Power supply +10.5 Vdc, max. 20 mA
A 1
Analog Input 1 (Frequency Reference Bias)
-10 to +10 Vdc (20 kΩ)
<9>
A 2
Analog Input 2 (Frequency Reference Bias)
-10 to +10 Vdc (20 kΩ)
0 or 4 to 20 mA (250 Ω)
Analog Input 3 / PTC Input (Aux. frequency
A 3
reference)
-10 to +10 Vdc (20 kΩ)
<10>
AC
0 V
<8>
V
Power supply, -10.5 Vdc, max. 20 mA
Termination resistor
(120 Ω, 1/2 W)
DIP
Switch S2
+
+
R
R
+
+
S
S
IG
<12>
H 1
Safe Disable inputs
H 2
Wire
jumper
<13>
HC
Sinking/Sourcing Mode for Digital Inputs on page
<1>
X
X
Braking resistor
(option)
<2><3>
B 2
1
B 1
U/T 1
V/T 2
Drive
W/T
3
<4>
Option card connectors
CN5-C
CN5-B
CN5-A
Terminal board
jumpers and switches
DIP Switch S1
I
V
A2 Volt/Curr. Sel
DIP Switch S2
Off
On
Term. Res. On/Off
Jumper S3
H1, H2
Sink/Source Sel.
PTC
DIP Switch S4
A3 Analog/PTC
Input Sel
AI
Jumper S5
V
AM/FM Volt./Curr.
Selection
I
FM
AM
N.O.
Slide Switch S6
DM+,DM-
N.C./N.O. Selection
<7>
N.C.
MA
MB
MC
M 1
M 2
M 3
M 4
M 5
M 6
MP
AC
0 V
<11>
FM
<15>
AM
AC
0 V
E (G)
+
+
DM
<16>
DM
3.2 Standard Connection Diagram
U
Motor
V
M
W
Shielded
Cable
Ground
Fault relay output
250 Vac, max. 1 A
30 Vdc, max 1 A
(min. 5 Vdc, 10 mA)
Multi-function relay output (During Run)
250 Vac, max. 1 A
30 Vdc, max 1 A
(min. 5 Vdc, 10 mA)
Multi-function relay output (Zero Speed)
250 Vac, max. 1 A
30 Vdc, max 1 A
(min. 5 Vdc, 10 mA)
Multi-function relay output (Speed Agree 1)
250 Vac, max. 1 A
30 Vdc, max 1 A
(min. 5 Vdc, 10 mA)
Multi-function pulse train output
(Output frequency)
0 to 32 kHz (2.2 kΩ)
Multi-function analog output 1
+
(Output frequency)
FM
-10 to +10 Vdc (2mA) or 4 to 20 mA
<14>
Multi-function analog output 2
+
(Output current)
AM
-10 to +10 Vdc (2mA) or 4 to 20 mA
<14>
EDM (Safety Electronic Device Monitor)
shielded line
twisted-pair shielded line
control circuit terminal
main circuit terminal
88)
3
61

Hide quick links: