YASKAWA A1000 Technical Manual page 64

High performance vector control drive type: cimr-a series models: 200 v class: 0.55 to 110 kw, 400 v class: 0.55 to 630 kw
Hide thumbs Also See for A1000:
Table of Contents

Advertisement

3.3 Main Circuit Configurations
<1> Models CIMR-A4A0930 and 4A1200 are compatible for operation with 12-phase rectification.
for details.
 12-Phase Rectification
Removing the Jumper
Models CIMR-A4A0930 and 4A1200 are compatible for operation with 12-phase rectification. Operation with
12-phase rectification requires the user to separately prepare a 3-winding transformer for the power supply. Contact
YASKAWA or your nearest sales representative for the transformer specifications.
Notes on wiring are listed below.
WARNING! Fire Hazard. Failure to remove jumpers shorting the power supply terminals on the main circuit when operating with
12-phase rectification may cause death or serious injury by fire.
Application Notes
• Remove M5 screws and then jumpers to operate with 12-phase rectification as shown in
• Models CIMR-A4A0930 and 4A1200 are shipped from the factory with jumpers short-circuiting terminals 
R/L1-R1/L11, S/L2-S1/L21, and T/L3-T1/L31.
Figure 3.3
64
Jumper
R1/L11
R/L1
S/L2
Figure 3.2 Removing the jumper
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
Refer to 12-Phase Rectification on page 64
S1/L21
T1/L31
T/L3
Figure
3.2.