YASKAWA A1000 Technical Manual page 104

High performance vector control drive type: cimr-a series models: 200 v class: 0.55 to 110 kw, 400 v class: 0.55 to 630 kw
Hide thumbs Also See for A1000:
Table of Contents

Advertisement

4.3 The Drive and Programming Modes
Mode
Contents
Drive Mode
Frequency Reference
Drive Mode Details
The following actions are possible in the Drive Mode:
• Run and stop the drive
• Monitor the operation status of the drive (frequency reference, output frequency, output current, output voltage, etc.)
• View information on an alarm
• View a history of alarms that have occurred
Figure 4.6
illustrates how to change the frequency reference from F 0.00 (0 Hz) to F 6.00 (6 Hz) while in the Drive
Mode. This example assumes the drive is set to LOCAL.
Figure 4.6
Frequency reference
display at power up
- MODE -
FREF (OPR)
U1-01= 0.00Hz
U1-02= 0.00Hz
U1-03= 0.00A
JOG
FWD
-MONITR-
FREF (d1-01)
U1-01= 006.00Hz
0.00 50.00
Note: The drive will not accept a change to the frequency reference until the ENTER key is pressed after the frequency reference is
entered. This feature prevents accidental setting of the frequency reference. To have the drive accept changes to the frequency
reference as soon as changes are made without requiring the ENTER key, set o2-05 to 1.
Programming Mode Details
The following actions are possible in the Programming Mode:
• Parameter Setting Mode: Access and edit all parameter settings
• Verify Menu: Check a list of parameters that have been changed from their original default values
• Setup Group: Access a list of commonly used parameters to simplify setup (see
Group on page
107)
• Auto-Tuning Mode: Automatically calculates and sets motor parameters to optimize drive performance
104
Operator Display
- MODE -
DRV
Rdy
FREF (OPR)
U1-01= 0.00Hz
Returns to the frequency reference display screen.
U1-02= 0.00Hz
LSEQ
U1-03= 0.00A
LREF
JOG
FWD
FWD/REV
DRV
Rdy
LSEQ
LREF
FWD/REV
Press to select LOCAL
DRV
Rdy
0.00Hz
FWD
Figure 4.6 Setting the Frequency Reference while in the Drive Mode
-MONITR-
DRV
Rdy
FREF (d1-01)
U1-01= 000.00Hz
0.00 50.00
0.00Hz
FWD
-MONITR-
DRV
Rdy
FREF (d1-01)
U1-01= 006.00Hz
0.00 50.00
Entry Accepted
0.00Hz
FWD
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
Description
F1
F2
left
right
Press until the frequency
reference changes to 006.00 Hz
- MODE -
DRV
Rdy
FREF (OPR)
U1-01= 6.00Hz
ESC
U1-02= 0.00Hz
LSEQ
U1-03= 0.00A
LREF
JOG
FWD
FWD/REV
Simplified Setup Using the Setup

Hide quick links:

Advertisement

Table of Contents