 C5: Automatic Speed Regulator (ASR)
The ASR is used for controlling the motor speed in V/f w/PG, CLV, AOLV/PM, and CLV/PM control modes. It adjusts
the output frequency (V/f w/PG) or torque reference (CLV, AOLV/PM, CLV/PM) in order to minimize the difference
between frequency reference and actual motor speed.
Figure 5.38
and
Figure 5.39
Figure 5.38
Frequency
reference
Detected speed
Figure 5.39
Frequency
reference
Detected speed
<1>
Advanced Open Loop Vector Control for PM motors estimates the speed using the motor model and does not require an encoder
feedback signal.
Adjusting the ASR Parameters
Before adjusting ASR parameters make sure all motor data have been set up correctly or Auto-Tuning has been
performed.
Analog output signals should be used to monitor the frequency reference after softstarter (U1-16) and the motor speed
(U1-05) when adjusting the ASR. Refer to
analog output functions.
Generally when tuning the ASR, first optimize the ASR gain, then adjust the integral time settings. Always make
adjustments with the load connected to the motor.
Adjusting the ASR Parameters in V/f Control with PG
In V/f Control with PG, the ASR settings change between two sets of parameters depending on the motor speed as
described in
C5-01, C5-03/C5-02, C5-04: ASR Proportional Gain 1, 2 / ASR Integral Time 1, 2 on page
Perform the following steps for adjusting ASR parameters:
1.
Run the motor at minimum speed and increase ASR gain 2 (C5-03) as much as possible without oscillation.
2.
Run the motor at minimum speed and decrease ASR integral time 2 (C5-04) as much as possible without
oscillation.
3.
Check the output current monitor to make sure that the output current is less than 50% of the drive rated current.
If the value is higher than 50%, decrease C5-03 and increase C5-04.
4.
Run the motor at maximum speed and increase ASR gain 1 (C5-01) as much as possible without oscillations.
190
Parameter Name
Motor 2 Torque Compensation Gain
illustrate how ASR works.
+
-
Change
rate
limiter
Figure 5.38 Speed Control Block Diagram for V/f Control with PG
C5-01, C5-03
+
P
-
I
C5-02, C5-04
<1>
Figure 5.39 Speed Control Block Diagram for CLV, AOLV/PM and CLV/PM
H4: Multi-Function Analog Outputs on page 262
for details on adjusting this parameter.
Setting Range
0.00 to 2.50
+
P
+
I
C5-01
C5-03
C5-02, C5-04
+
Primary
filter
+
I
C5-06
limit
C5-08
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
Output frequency
+
+
ASR limit
C5-05
Torque limits
Torque reference
L7-01 to L7-04
for details on setting up
Default
1.00
192.