D.3 UL Standards
 Installing Input Fuses
NOTICE: If a fuse is blown or equipment for residual current monitoring/detection (RCM/RCD) is tripped, check the wiring and the
selection of the peripheral devices. Check the wiring and the selection of peripheral devices to identify the cause. Contact YASKAWA
before restarting the drive or the peripheral devices if the cause cannot be identified.
Factory Recommended Branch Circuit Protection
YASKAWA recommends installing one of the following types of branch circuit protection to maintain compliance with
UL508C. Semiconductor protective type fuses are preferred. Alternate branch circuit protection devices are also listed in
Table D.8
and
Table
D.9.
Table D.8 Factory Recommended A1000 AC Drive Branch Circuit Protection (Normal Duty)
Drive Model
AC Drive Input Amps
2A0004
2A0006
2A0010
2A0012
2A0021
2A0030
2A0040
2A0056
2A0069
2A0081
2A0110
2A0138
2A0169
2A0211
2A0250
2A0312
2A0360
2A0415
4A0002
4A0004
4A0005
4A0007
4A0009
4A0011
4A0018
4A0023
4A0031
4A0038
4A0044
4A0058
4A0072
4A0088
4A0103
4A0139
4A0165
4A0208
4A0250
4A0296
4A0362
4A0414
4A0515
4A0675
4A0930
4A1200
<1> Maximum MCCB Rating is 15 A, or 200% of drive input current rating, whichever is larger. MCCB voltage rating must be 600 VAC or greater.
<2> Maximum Time Delay fuse is 175% of drive input current rating. This covers any Class CC, J or T class fuse.
<3> Maximum Non-time Delay fuse is 300% of drive input current rating. This covers any CC, J or T class fuse.
<4> When using semiconductor fuses, Bussmann FWH is required for UL compliance.
<5> This covers Class L fuse.
594
MCCB Rating Amps
Three-Phase 200 V Class
3.9
15
7.3
15
10.8
20
13.9
25
24
45
37
60
52
100
68
125
80
150
96
175
111
200
136
250
164
300
200
400
271
500
324
600
394
700
471
900
Three-Phase 400 V Class
2.1
15
4.3
15
5.9
15
8.1
15
9.4
15
14
25
20
40
24
45
38
75
44
75
52
100
58
100
71
125
86
150
105
200
142
250
170
300
207
400
248
450
300
600
346
600
410
800
465
900
657
1200
922
1158
A1000 in Normal Duty Mode (C6-01 = 1)
Time Delay Fuse Rating
<1>
Amps
<2>
6.25
12
17.5
20
40
60
90
110
125
150
175
225
250
350
450
500
600
800
3.5
7.5
10
12
15
20
35
40
60
75
90
100
110
150
175
225
250
350
400
500
600
700
800
1100
<5>
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
Bussmann
Non-time Delay Fuse
Semiconductor Fuse
Rating Amps
<3>
Rating (Fuse Ampere)
10
FWH-70B (70)
20
FWH-70B (70)
30
FWH-70B (70)
40
FWH-70B (70)
70
FWH-90B (90)
110
FWH-100B (100)
150
FWH-200B (200)
200
FWH-200B (200)
225
FWH-200B (200)
275
FWH-300A (300)
300
FWH-300A (300)
400
FWH-350A (350)
450
FWH-400A (400)
600
FWH-400A (400)
800
FWH-600A (600)
800
FWH-700A (700)
1000
FWH-800A (800)
<5>
1400
FWH-1000A (1000)
<5>
6
FWH-40B (40)
12
FWH-50B (50)
17.5
FWH-70B (70)
20
FWH-70B (70)
25
FWH-90B (90)
40
FWH-90B (90)
60
FWH-80B (80)
70
FWH-100B (100)
110
FWH-125B (125)
125
FWH-200B (200)
150
FWH-250A (250)
150
FWH-250A (250)
200
FWH-250A (250)
250
FWH-250A (250)
300
FWH-250A (250)
400
FWH-350A (350)
500
FWH-400A (400)
600
FWH-500A (500)
700
FWH-600A (600)
800
FWH-700A (700)
1000
FWH-800A (800)
<5>
1200
FWH-800A (800)
<5>
1350
FWH-1000A (1000)
<5>
1800
FWH-1200A (1200)
<5>
FWH-1200A (1200)
FWH-1600A (1600)
<4>

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents