5.2 b: Application
b5-06: PID Output Limit
Sets the maximum output possible from the entire PID controller. Set as a percentage of the maximum frequency
(E1-04).
No.
b5-06
b5-07: PID Offset Adjustment
Sets the offset added to the PID controller output. Set as a percentage of the maximum frequency.
No.
b5-07
b5-08: PID Primary Delay Time Constant
Sets the time constant for the filter applied to the output of the PID controller. Normally, change is not required.
No.
b5-08
Note: Useful when there is a fair amount of oscillation or when rigidity is low. Set to a value larger than the cycle of the resonant
frequency. Increasing this time constant may reduce the responsiveness of the drive.
b5-09: PID Output Level Selection
Normally a positive PID input (feedback smaller than setpoint) leads to positive PID output. Parameter b5-09 can be used
to reverse the sign of the PID controller output signal.
No.
b5-09
Setting 0: Normal Output
A negative PID input causes a decrease in the PID output (direct acting).
Setting 1: Reverse Output
A negative PID input causes an increase in the PID output (reverse acting).
b5-10: PID Output Gain Setting
Applies a gain to the PID output and can be helpful when the PID function is used to trim the frequency reference (b5-01
= 3 or 4).
No.
b5-10
b5-11: PID Output Reverse Selection
Determines whether a negative PID output reverses the direction of drive operation or not. When the PID function is used
to trim the frequency reference (b5-01 = 3 or 4), this parameter has no effect and the PID output will not be limited (same
as b5-11 = 1).
No.
b5-11
Setting 0: Reverse Disabled
Negative PID output will be limited to 0 and the drive output will be stopped.
Setting 1: Reverse Enabled
Negative PID output will cause the drive to run in the opposite direction.
172
Name
PID Output Limit
Name
PID Offset Adjustment
Name
PID Primary Delay Time Constant
Parameter Name
PID Output Level Selection
Name
PID Output Gain Setting
Parameter Name
PID Output Reverse Selection
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
Setting Range
0.0 to 100.0%
Setting Range
-100.0 to 100.0%
Setting Range
0.00 to 10.00 s
Setting Range
0 or 1
Setting Range
0.00 to 25.00
Setting Range
0 or 1
Default
100.0%
Default
0.0%
Default
0.00 s
Default
0
Default
1.00
Default
0