4.7 Auto-Tuning
Enter Data from the Motor Nameplate
After selecting the type of Auto-Tuning, enter the data required from the motor nameplate.
Note: These instructions continue from Step 6 in "Selecting the Type of Auto-Tuning".
1.
Press
to access the motor output power parameter T1-02.
2.
Press
to view the default setting.
Press
,
,
F1
F2
3.
left
right
4.
Press
to save the setting.
5.
The display automatically returns to the display in Step 1.
Repeat Steps 1 through 5 to set the following parameters:
• T1-03, Motor Rated Voltage
• T1-04, Motor Rated Current
• T1-05, Motor Base Frequency
6.
• T1-06, Number of Motor Poles
• T1-07, Motor Base Frequency
• T1-09, Motor No-Load Current (Stationary Auto-Tuning 1 or 2 only)
• T1-10, Motor Rated Slip (Stationary Auto-Tuning 2 only)
Note: 1. For details on each setting,
2. To execute Stationary Auto-Tuning for line-to-line resistance only, set parameters T1-02 and T1-04.
126
Step
,
and
to enter the motor power nameplate data in kW.
Refer to Parameter Settings during Induction Motor Auto-Tuning: T1 on page
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
Display/Result
- A.TUNE -
PRG
Mtr Rated Power
T1-02= 0.75kW
(0.00 ~ 650.00)
"0.75kW"
ESC
FWD
DATA
- A.TUNE -
PRG
Mtr Rated Power
T1-02= 000.75kW
(0.00 ~ 650.00)
"0.75kW"
FWD
- A.TUNE -
PRG
Mtr Rated Power
T1-02= 000.40kW
(0.00 ~ 650.00)
"0.75kW"
FWD
Entry Accepted
- A.TUNE -
PRG
Mtr Rated Power
T1-02= 0.40kW
(0.00 ~ 650.00)
"0.75kW"
ESC
FWD
DATA
- A.TUNE -
PRG
Rated Voltage
T1-03= 200.0VAC
(0.0 ~ 255.0)
"200.0VAC"
ESC
FWD
DATA
- A.TUNE -
PRG
Mtr Rated Slip
T1-10= X.XX Hz
(0.00 ~ 20.00)
"X.XX Hz"
ESC
FWD
DATA
127.