YASKAWA A1000 Technical Manual page 362

High performance vector control drive type: cimr-a series models: 200 v class: 0.55 to 110 kw, 400 v class: 0.55 to 630 kw
Hide thumbs Also See for A1000:
Table of Contents

Advertisement

6.7 Auto-Tuning Fault Detection
Digital Operator Display
Cause
Torque reference is too high.
Digital Operator Display
Cause
One of the motor phases is missing: 
(U/T1, V/T2, W/T3).
Current exceeded the current rating of the drive.
The current is too low.
Attempted Auto-Tuning without motor connected to
the drive.
Current detection signal error.
Digital Operator Display
Cause
Drive was unable to complete tuning for leakage
inductance within 300 seconds.
Digital Operator Display
Cause
The motor speed exceeded twice the amplitude of
speed reference during Inertia Tuning.
Digital Operator Display
Cause
The output torque reached the torque limit set in
L7-01 through L7-04 during Inertia Tuning.
Digital Operator Display
Cause
The inertia identified by the drive was abnormally
small or abnormally large during Inertia Tuning.
Digital Operator Display
Cause
Drive is prohibited from rotating the motor in
reverse while attempting to perform Inertia Tuning.
Digital Operator Display
Cause
The result of Back EMF Constant Tuning (induced
voltage) exceeds the allowable setting range.
Digital Operator Display
Cause
The induced voltage constant inductance values set
to E5-08 or E5-09 exceed the allowable range.
Digital Operator Display
Cause
Stator resistance tuning attempted to set a value to
E5-06 that is outside the allowable setting range.
362
Er-11
Motor Speed Fault
• Increase the acceleration time (C1-01).
• Disconnect the machine from the motor, if possible.
Er-12
Current Detection Error
Check motor wiring and correct any problems.
• Check the motor wiring for a short between motor lines.
• If a magnetic contactor is used between motors, make sure it is closed.
• Replace either the control board or the entire drive. For instructions on replacing the control board, contact YASKAWA or your
nearest sales representative.
Connect the motor and perform Auto-Tuning.
Replace either the control board or the entire drive. For instructions on replacing the control board, contact YASKAWA or your
nearest sales representative.
Er-13
Leakage Inductance Error
• Check all wiring and correct any mistakes.
• Double check the motor rated current value that was entered to T1-04 for Auto-Tuning.
• Check the motor rated current value written on the motor nameplate and enter the correct value.
Er-14
Motor Speed Error 2
Reduce the ASR gain set to C5-01.
Er-15
Torque Saturation Error
• Increase the torque limits in L7-01 through L7-04 (but keep them within reasonable limits).
• First try reducing the test signal amplitude in T3-01 and repeat the tuning. If necessary, then try reducing the test signal frequency
(T3-02) and repeat the tuning.
Er-16
Inertia Detection Error
• First try reducing the test signal amplitude in T3-01 and repeat the tuning. If necessary, then try reducing the test signal frequency
(T3-02) and repeat the tuning.
• Check the basic motor inertia value entered to T3-03.
Er-17
Reverse Prohibited Error
• Inertia Auto-Tuning cannot be performed if the drive is restricted from rotating in reverse.
• Assuming it is acceptable for the application to rotate in reverse, set b1-04 to 0 and then execute Inertia Tuning.
Er-18
Induction Voltage Error
Double check the data that was entered to the T2- parameters, and perform Auto-Tuning again.
Er-19
PM Inductance Error
Double check the data that was entered to the T2- parameters, and perform Auto-Tuning again.
Er-20
Stator Resistance Error
Double check the data that was entered to the T2- parameters, and perform Auto-Tuning again.
Error Name
Possible Solutions
Error Name
Possible Solutions
Error Name
Possible Solutions
Error Name
Possible Solutions
Error Name
Possible Solutions
Error Name
Possible Solutions
Error Name
Possible Solutions
Error Name
Possible Solutions
Error Name
Possible Solutions
Error Name
Possible Solutions
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents