Carrier Frequency Derating - YASKAWA A1000 Technical Manual

High performance vector control drive type: cimr-a series models: 200 v class: 0.55 to 110 kw, 400 v class: 0.55 to 630 kw
Hide thumbs Also See for A1000:
Table of Contents

Advertisement

A.6 Drive Derating Data
 Carrier Frequency Derating
As the carrier frequency of the drive is increased above the factory default setting, the drive's rated output current must
be derated according to
Figure A.1
Figure A.1
Figure A.2
Figure A.3
Figure A.4
446
to
Figure
A.6.
Normal Duty
Heavy Duty
80% of HD
70% of HD
0
2 kHz
Figure A.1 Carrier Frequency Derating (CIMR-A2A0004 to 2A0138)
Normal Duty
Heavy Duty
80% of HD
0
2 kHz
Figure A.2 Carrier Frequency Derating (CIMR-A2A0169 to 2A0415)
Normal Duty
Heavy Duty
60% of HD
0
2 kHz
Figure A.3 Carrier Frequency Derating (CIMR-A4A0002 to 4A0103)
Normal Duty
Heavy Duty
70% of HD
0
2 kHz
Figure A.4 Carrier Frequency Derating (CIMR-A4A0139 to 4A0414)
2A0004 to 2A0069
2A0081 to 2A0138
8 kHz
15 kHz
2A0169 to 2A0415
5 kHz
10 kHz
4A0002 to
4A0103
8 kHz
15 kHz
4A0139 to 4A0414
5 kHz
10 kHz
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual