5.6 F: Option Settings
F6-01: Communications Error Operation Selection
Determines drive operation if a communication error occurs.
No.
F6-01
Setting 0: Ramp to stop (uses the deceleration time set to C1-02)
Setting 1: Coast to stop
Setting 2: Fast Stop (uses the Fast Stop time set to C1-09)
Setting 3: Alarm only (continue operation)
Setting 4: Alarm and Run at d1-04
Setting 5: Alarm and Ramp to stop (automatic recovery)
<1> Take proper safety measures, such as installing an emergency stop switch, when setting F6-01 to 3 or 4.
F6-02: External Fault from Comm. Option Detection Selection
Determines the detection method of an external fault initiated by a communication option (EF0).
No.
F6-02
Setting 0: Always detected
Setting 1: Detection during run only
F6-03: External Fault from Comm. Option Operation Selection
Determines the operation when an external fault is initiated by a communication option (EF0).
No.
F6-03
Setting 0: Ramp to stop
Setting 1: Coast to stop
Setting 2: Fast Stop
Setting 3: Alarm only (continue operation)
F6-06: Torque Reference/Torque Limit Selection from Comm. Option
Used to select if torque reference and torque limit values are assigned to the drive from the network.
No.
F6-06
Setting 0: Disabled
Setting 1: Enabled
F6-07: Multi-Step Speed Enable/Disable when NetRef/ComRef is Selected
Selects how multi-step speed inputs are treated when the NetRef command is set.
No.
F6-07
Setting 0: Multi-step speed operation disabled
If the NetRef command is selected, multi-step speed input frequency references are disabled.
Setting 1: Multi-step speed operation enabled
Even if the NetRef command is selected, multi-step speed inputs are still active and can override the frequency reference
from the communications option.
232
Parameter Name
Communications Error Operation Selection
<1>
<1>
Parameter Name
External Fault from Comm. Option Detection Selection
Parameter Name
External Fault from Comm. Option Operation Selection
Parameter Name
Torque Reference/Torque Limit Selection from Comm. Option
Parameter Name
NetRef/ComRef Function Selection
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
Setting Range
0 to 5
Setting Range
0 or 1
Setting Range
0 to 3
Setting Range
0, 1
Setting Range
0, 1
Default
1
Default
0
Default
1
Default
0
Default
0