F6-08: Reset Communication Parameters
Determines whether communication-related parameters (F6-/F7-) are reset when the drive is initialized using
parameter A1-03.
No.
F6-08
Setting 0: Do not reset parameters F6-/F7- when the drive is initialized with A1-03
Setting 1: Reset F6-/F7- when the drive is initialized with A1-03
Note: F6-08 is not reset when the drive is initialized.
F6-14: bUS Error Auto Reset
Selects whether a bUS error can be automatically reset if automatic fault retry is enabled.
No.
F6-14
Setting 0: Disabled, Auto Reset Not Possible
Setting 1: Enabled, Auto Reset Possible
F7-16: Communication Loss Time Out
Sets the time-out value for communication loss detection in tenths of a second. A value of 0.0 disables the connection
timeout.
Example: A value of "100" represents 10.0 seconds.
No.
F7-16
CC-Link Parameters
Parameters F6-04, F6-10, and F6-11 set up the drive to operate on a CC-Link network.
For details on parameter settings, refer to the YASKAWA AC Drive 1000-Series Option CC-Link Installation Manual
and Technical Manual.
MECHATROLINK-II Parameters
Parameters F6-20 through F6-26 set up the drive to operate on a MECHATROLINK-II network.
For details on parameter settings, refer to the YASKAWA AC Drive 1000-Series Option MECHATROLINK-II
Installation Manual and Technical Manual.
MECHATROLINK-III Parameters
Parameters F6-20, F6-21, F6-23 through F6-26 set up the drive to operate on a MECHATROLINK-III network.
For details on parameter settings, refer to the YASKAWA AC Drive 1000-Series Option MECHATROLINK-III
Installation Manual and Technical Manual.
PROFIBUS-DP Parameters
Parameters F6-30 through F6-32 and F7-60 through F7-79 set up the drive to operate on a PROFIBUS-DP network.
For details on parameter settings, refer to the YASKAWA AC Drive 1000-Series Option PROFIBUS-DP Installation
Manual and Technical Manual.
CANopen Parameters
Parameters F6-35 and F6-36 set up the drive to operate on a CANopen network.
For details on parameter settings, refer to the YASKAWA AC Drive 1000-Series Option CANopen Installation Manual
and Technical Manual.
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
Parameter Name
Reset Communication Parameters
Parameter Name
bUS Error Auto Reset
Parameter Name
Communication Loss Time Out
5.6 F: Option Settings
Setting Range
Default
0, 1
Setting Range
Default
0, 1
Setting Range
Default
0.0 to 30.0 s
0
0
0.0 s
5
233