5.7 H: Terminal Functions
Setting 3: User-set speed agree 1 (f
Closes whenever the actual output frequency or motor speed (CLV, CLV/PM) and the frequency reference are within the
speed agree width (L4-02) of the programmed speed agree level (L4-01).
Status
Open
Output frequency or motor speed and frequency reference are not both within the range of L4-01 ±L4-02.
Closed
Output frequency or motor speed and the frequency reference are both within the range of L4-01 ±L4-02.
Note: Frequency detection works in both forward and reverse. The value of L4-01 is used as the detection level for both directions.
Figure 5.71
Frequency reference
L4-01
0 Hz
Output frequency
User Set
Speed Agree 1
Refer to L4-01, L4-02: Speed Agreement Detection Level and Detection Width on page 288
Setting 4: Frequency Detection 1
Output opens when the output frequency or motor speed (CLV, CLV/PM) rises above the detection level set in L4-01 plus
the detection width set in L4-02. The terminal remains open until the output frequency or motor speed falls below the
level set in L4-01.
Status
Open
Output frequency or motor speed exceeded L4-01 + L4-02.
Closed
Output frequency or motor speed is below L4-01 or has not exceeded L4-01 + L4-02.
Note: Frequency detection works in both forward and reverse. The value of L4-01 is used as the detection level for both directions.
Figure 5.72
Frequency
detection
<1> This is the time chart when L4-07 (Speed Agree Detection Selection) is set to 1 (detection always enabled). The default setting for L4-07 is 0
(no detection during baseblock). When L4-07 = 0, the terminal opens during baseblock.
Refer to L4-01, L4-02: Speed Agreement Detection Level and Detection Width on page 288
248
/f
Agree 1)
ref
set
During
Forward
OFF
OFF
ON
ON
Figure 5.71 User Set Speed Agree 1 Time Chart
Output Frequency
or Motor Speed
OFF
ON
1<1>
Figure 5.72 Frequency Detection 1 Time Chart
Description
Frequency reference + L4-02
L4-01 + L4-02
Frequency reference – L4-02
L4-01 – L4-02
During Reverse
ON
Description
L4-02
L4-01
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
Output frequency
–L4-01 + L4-02
–L4-01
Frequency reference + L4-02
–L4-01 – L4-02
Frequency reference
Frequency reference – L4-02
OFF
ON
for more instructions.
L4-01
L4-02
for more details.