YASKAWA A1000 Technical Manual page 488

High performance vector control drive type: cimr-a series models: 200 v class: 0.55 to 110 kw, 400 v class: 0.55 to 630 kw
Hide thumbs Also See for A1000:
Table of Contents

Advertisement

B.3 Parameter Table
H2-
Function
Setting
17
Torque Detection 1 (N.C.)
18
Torque Detection 2 (N.O.)
19
Torque Detection 2 (N.C.)
1A
During Reverse
1B
During Baseblock (N.C.)
1C
Motor 2 Selection
1D
During Regeneration
1E
Restart Enabled
1F
Motor Overload Alarm (oL1)
20
Drive Overheat Pre-alarm (oH)
22
Mechanical Weakening Detection
2F
Maintenance Period
30
During Torque Limit
31
During Speed Limit
During Speed Limit in Torque
32
Control
33
Zero Servo Complete
37
During Frequency Output
38
Drive Enabled
39
Watt Hour Pulse Output
3C
LOCAL/REMOTE Status
3D
During Speed Search
3E
PID Feedback Low
488
H2 Multi-Function Digital Output Settings
All Modes
Open: Overtorque or undertorque has been detected.
All Modes
Closed: Overtorque or undertorque has been detected.
All Modes
Open: Overtorque or undertorque has been detected.
All Modes
Closed: Drive is running in the reverse direction.
All Modes
Open: Drive has entered the baseblock state (no output voltage).
V/f
V/f w/PG
OLV/PM
AOLV/PM
Closed: Motor 2 is selected by a digital input (H1- = 16)
V/f
V/f w/PG
OLV/PM
AOLV/PM
Closed: Motor is regenerating energy into the drive.
All Modes
Closed: An automatic restart is performed
All Modes
Closed: oL1 is at 90% of its trip point or greater. An oH3 situation also triggers this alarm.
All Modes
Closed: Heatsink temperature exceeds the parameter L8-02 value.
All Modes
Closed: Mechanical weakening detected.
All Modes
Closed: Cooling fan, electrolytic capacitors, IGBTs, or the soft charge bypass relay may require maintenance.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Closed: When the torque limit has been reached.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Closed: Speed limit has been reached.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Closed: Speed limit has been reached while using Torque Control.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Closed: Zero Servo operation has finished.
All Modes
Open: No frequency output from drive if stopped, with baseblock, with DC injection braking during initial excitation,
or with short-circuit braking.
Closed: Drive is outputting a frequency.
All Modes
Closed: Multi-function input set for "Drive enable" is closed (H1- = 6A)
All Modes
Output units are determined by H2-06. Outputs a pulse every 200 ms to indicate the kWh count.
All Modes
Open: REMOTE
Closed: LOCAL
All Modes
Closed: Speed Search is being executed.
All Modes
Closed: PID feedback level is too low.
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
Description
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
Page
250
250
250
253
253
253
253
253
253
253
253
254
254
254
254
254
254
254
254
255
255
255