4.4 Start-up Flowcharts

4.4

Start-up Flowcharts

This section summarizes the basic steps required to start the drive. The chart is intended as a
quick reference to help familiarize the user with start-up procedures.
u

Flowchart: Basic Start-up and Motor Tuning

Figure 4.6
describes basic start-up sequence for the drive and motor system. This sequence
varies slightly depending on application. Use drive default parameter settings in simple
applications that do not require high precision.
Couple the load or machine to the motor. Run the machine and check for desired operation.
86
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
Install and wire the drive as explained in Chapters 1, 2 and 3
Apply main power on to the drive.
Adhere to safety messages concerning application of power.
Set the basic parameters:
* b1-01/02 for frequency reference and run command source selection
* h1-oo, H2-01, H3-oo, H4-oo, H5-oo for I/O terminal setting
* d1-oo for multi-speed references if used
* C1-oo and C2-oo for accel./decel. and S-curve time settings
* C6-01 for heavy/normal duty mode selection
* L3-04 if braking options are used
Run the motor without load; check the rotation direction and operation.
Verify external signal commands to the drive work as desired.
Fine tune parameters. Adjust application settings if necessary.
Check the machine operation and verify parameter settings.
Drive is ready to run the application.
Figure 4.6 Basic Start-Up and Motor Tuning