Appendix 5 Method Of Replacing High Performance Model Qcpu With Universal Model Qcpu; Appendix 5.1 Precautions For Replacement - Mitsubishi Q00JCPU User Manual

Hide thumbs Also See for Q00JCPU:
Table of Contents

Advertisement

APPENDICES
Appendix 5 Method of replacing High Performance model QCPU with
Universal model QCPU

Appendix 5.1 PRECAUTIONS FOR REPLACEMENT

This chapter describes the precautions for replacing the High Performance model QCPU
with the Universal model QCPU and the replacement methods.
(1) System configuration
TableApp.48 Precautions for replacement and replacement methods (System configuration)
Item
Use of AnS/A series
AnS/A series modules are not supported.
module
GOT
GOT900 series cannot be connected.
Applicable USB cables are different.
• High Performance model QCPU
Programming tool
... A-B type
connection
• Universal model QCPU
... A-miniB type
Applicable device and
Devices and softwares compatible with the
software
Universal model QCPU shall be used.
To configure a multiple CPU system, CPU
modules compatible with the Universal
model QCPU shall be used.
Multiple CPU system
In a multiple CPU system using the Motion
CPU, an existing auto refresh area and
user setting area cannot be used for data
communication with the Motion CPU.
In a redundant power supply system using
the Q38RB redundant power supply main
base unit and the Q68RB redundant
power supply extension base unit, the
Redundant power
status of the power supply module cannot
*1
supply system
be stored in the special relays and special
registers (SM1780 to SM1783/SD1780 to
SD1783). The status neither can be
displayed on the system monitor.
The simple dual-structured network
MELSECNET/H
function is not supported.

Appendix 5 Method of replacing High Performance model QCPU with Universal model QCPU

Precautions
* 1: The Universal model QCPU whose serial number (first five digits) is "10041" or earlier is targeted.
Replacement method
Use Q series modules.
Use GOT1000 series.
Use USB cables of A-miniB type. Or, use
USB conversion adapters of B-miniB type.
Devices need to be replaced for the
compatibility with the Universal model
QCPU and software need to be upgraded
for the communication with the Universal
model QCPU are described in Appendix
5.2.
CPU modules compatible with the
Universal model QCPU are described in
Appendix 5.2.
For data communication with the Motion
CPU, use an auto refresh area and user
setting area in the multiple CPU high-
speed transmission area.
Check the status of the power supply
module by the LED on the front of the
module.
---
9
10
11
Reference
---
---
12
---
Appendix 5.2
Appendix 5.2
Chapter 4 in the "QCPU
User's Manual (Multiple
CPU System)"
Section 5.3 in the
"QCPU User's Manual
(Hardware Design,
Maintenance and
Inspection)"
Section 7.7 in the "Q
Corresponding
MELSECNET/H
Network System
Reference Manual (PLC
to PLC network)"
App
- 112