Mitsubishi Q00JCPU User Manual page 533

Hide thumbs Also See for Q00JCPU:
Table of Contents

Advertisement

7
COMMUNICATION
PORTS OF CPU MODULE
(5) Error codes for communication using MC protocol
Error code
No.
(Hexadecimal)
CPU detected error (Error that occurred in other than
4000
to 4FFF
1
H
H
communication using the MC protocol)
When the setting for online change is disabled on the Built-in
0055
2
Ethernet port tab of PLC parameter in GX Developer, an external
H
device requested online change to the CPU module.
When the communication data code setting is set to ASCII code in
C050
3
the QnUDE(H)CPU, ASCII code data that cannot be converted to
H
binary code was received.
The number of device points for reading/writing is outside the
C051
to C054
4
H
H
allowable range.
C056
5
The read/write request data exceeds the allowable address range.
H
The request data length after the ASCII to binary conversion does
C058
6
H
not match the data size of the character area (a part of text data).
• The command and/or subcommand are specified incorrectly.
C059
7
• The command and/or subcommand not supported in the
H
QnUDE(H)CPU are specified.
The QnUDE(H)CPU cannot read/write data from/to the specified
C05B
8
H
device.
The request data is incorrect. (ex. specifying data in units of bits for
C05C
9
H
reading/writing of word devices)
10
C05D
Monitor registration is not performed.
H
The external device sent a request that cannot be executed in the
C05F
11
H
target CPU module.
The request data is incorrect. (ex. incorrect specification of data for
C060
12
H
bit devices)
The request data length does not match the data size of the
C061
13
H
character area (a part of text data)
The CPU module received a request message in ASCII when the
communication data code setting is set to binary code, or received
a request message in binary when the data code setting is set to
C06F
14
H
ASCII code.
(As for this error code, only error history is registered. The error
response message is not returned.)
The device memory extension cannot be specified for the target
C070
15
H
station.
Data that cannot communicate in the CPU module or Ethernet
C0B5
16
H
module is specified.
C200
17
The remote password is incorrect.
H
The communication target port is in the remote password locked
status.
C201
18
Or, when the communication data code setting is set to ASCII
H
code, any data of subcommands and later cannot be converted to
binary code since the remote password is locked.
The external device is different from the one that quested remote
C204
19
H
password unlock processing.
USING
Table7.6 shows the error codes, error descriptions, and corrective actions that will be
sent from the CPU module to an external device when an error occurs during
communication using the MC protocol.
Table7.6 List of available devices in QnUDE(H)CPU
Description
BUILT-IN
ETHERNET
Corrective action
Refer to the QCPU User's Manual (Hardware Design,
Maintenance and Inspection) and take corrective action.
• Enable the online change setting on the Built-in Ethernet port
tab of PLC parameter in GX Developer and write data to the
CPU module.
• Change the status of the CPU module to STOP and write data.
• Set the communication data code to binary code and restart the
QnUDE(H)CPU for communication.
• Correct the send data on the external device side and resend
the data.
Correct the number of device points for reading/writing and resend
the data to the QnUDE(H)CPU.
Correct the start address or the number of device points for
reading/writing, and resend the data to the QnUDE(H)CPU.
(Do not exceed the allowable address range.)
Check and correct the text data or the request data length of the
header data, and resend the data to the QnUDE(H)CPU.
• Check the request data.
• Use commands and/or subcommands supported in the
QnUDE(H)CPU.
Check the device for reading/writing data.
Correct the request data (such as subcommand correction) and
resend the data to the QnUDE(H)CPU.
Perform the monitor registration before monitor operation.
• Correct the network number, PC number, request destination
module I/O number, and request destination module station
number.
• Correct the read/write request data.
Correct the request data and resend the data to the
QnUDE(H)CPU.
Check and correct the text data or the request data length of the
header data, and resend the data to the QnUDE(H)CPU.
• Send request messages corresponding to the communication
data code setting.
• Set the communication data code corresponding to the request
message.
Read/Write data to the device memory without specifying the
extension.
• Check the request data.
• Stop the current request.
Check the remote password and perform unlock/lock processing
again.
Perform remote password unlock processing before
communication.
Have the same external device which has requested unlock
processing request remote password lock processing.
7.4 MC Protocol Communication
1
2
3
4
5
6
7
8
7
- 19