6
FUNCTIONS
(3) Operation when changing from STOP status to RUN status
6
- 16
6.4 Setting Output (Y) Status when Changing between STOP and RUN
(a) Output (Y) status prior to STOP is output (Default)
After the output (Y) status before the STOP status is output, the sequence
program calculations are performed.
(b) Output (Y) is cleared
The output (Y) is OFF status.
The output (Y) will be output after the sequence program operation is executed.
Refer to (5) for the operation when forcibly turning ON the output (Y) in STOP
status.
STOP status
Is "Previous state" set?
YES (Set "Previous state". (default))
Output the output (Y) status right
before changing to STOP status.
Execute the sequence
program calculations.
Figure 6.9 Operation when Change from STOP Status to RUN Status
RUN status
NO (Set "Recalculate".)
Clear the output (Y) status.