9
PARAMETERS
(2) PLC system
Item
Parameter No.
Low speed
Timer limit
1000
setting
High speed
RUN X
RUN-
PAUSE
1001
contact
PAUSE X
Remote reset
1002
Output mode at STOP to
1003
Run
Intelligent function
module setting (interrupt
100A
pointer setting)
Points occupied by empty
1007
slot
Make the settings necessary to use the CPU module.
The parameters may be the default values to perform control.
Table9.2 PLC system setting list
Description
Set the time limit of the low
H
speed timer/high speed timer.
Set the contact that controls
RUN/PAUSE of the CPU
module. Setting of only the
PAUSE contact is not allowed.
H
(The RUN contact or RUN
contact and PAUSE contact can
be set.)
Set enable/disable of remote
reset operation from GX
H
Developer.
Set the output (Y) status when
the STOP status is switched to
H
the RUN status.
Set the assignment of the
interrupt pointers (I50 to 127)
and the start I/O No. and start SI
H
No. of the intelligent function
module.
Set the number of empty slots on
the main base unit/extension
H
base unit.
Figure 9.2 PLC system
Setting range
1ms to 1000ms (1ms unit)
100ms
0.1ms to 100.0ms (0.1ms unit)
10.0ms
X0 to 7FF
No setting
Enable/Disable
Disable
Provide output (Y) status before
Provide output (Y)
STOP/Clear output (Y) (output
status before STOP
one scan later)
Start I/O No.
Start SI No.
No setting
I50 to 127
[ Q00JCPU ]
0 points/16 points/32 points/64
points/128 points/256 points
16 points
[ Q00CPU, Q01CPU ]
0 points/16 points/32 points/64
points/128 points/256 points/512
points/1024 points
9.1 PLC Parameters
9.1.1 Basic model QCPU
Default value
Reference
Section 10.2.10
Section 10.2.10
Section 6.6.1
Section 6.6.2
Section 6.6.3
Section 6.4
Section 10.11
Section 4.6.1(5)
(Continued on next page)
9
9
10
11
12
- 3