FUNCTIONS
(6) Selecting error check items
High
Basic
Performance
Process
Note6.54
Note6.54
Note6.54
Redundant
Note6.54
Universal
UD
Note6.55
Note56Çñ
High
Basic
Performance
Process
Error check items, "Check device range at indexing" and "Diagnose redundant power supply
Note6.54 Note6.54 Note6.54
system", cannot be set for the Basic model QCPU, High Performance model QCPU, Process
Redundant
CPU, and Redundant CPU.
Note6.54
Note57Çñ
When setting the error check item "Diagnose redundant power supply system" in the Universal
Universal
UD
model QCPU, check the versions of CPU module and GX Developer. (
Note6.55
Whether to execute an error check or not can be set for the following items on the
PLC RAS setting tab of PLC parameter in GX Developer.
(The default of all items is set to "Execute (with a checkmark in the checkbox)".)
(a) Battery check ("Carry out battery check")
(b) Fuse blown check ("Carry out fuse blown check")
(c) Module verification ("Verify module")
(d) Device range check at index modification ("Check device range at
Note6.54
indexing")
Note56
(e) Redundant power supply system diagnostics ("Diagnose redundant power
Note6.54, Note6.55
supply system")
Note57
6.17 Self-diagnostics Function
1
2
3
4
5
6
7
8
Appendix 4.5)
6
- 131