Mitsubishi Q00JCPU User Manual page 530

Hide thumbs Also See for Q00JCPU:
Table of Contents

Advertisement

7
COMMUNICATION
PORTS OF CPU MODULE
(3) Available devices
Classification
Internal system
Special relay
device
Special register
Input
Output
Internal relay
Latch relay
Annunciator
Edge relay
Link relay
Data register
Link register
Timer
internal user
device
Retentive timer
Counter
Link special relay
Link special register
Step relay
Direct input
Direct output
Index register
Index register
File register
File register
Extended data
Extended data register
register
Extended link
Extended link register
register
7
- 16
7.4 MC Protocol Communication
USING
Table7.4 lists the devices available in commands used in the MC protocol
communication function.
Table7.4 List of available devices in Built-in Ethernet port QCPU
Device
Device code
SM
SD
X
Y
M
L
F
V
B
D
W
Contact
TS
Coil
TC
Current value
TN
Contact
SS
Coil
SC
Current value
SN
Contact
CS
Coil
CC
Current value
CN
SB
SW
S
DX
DY
Z
R
ZR
D
W
* 1 : Devices of DX/DY1000 or later are not available. Use X/Y devices to access devices of X/Y1000
or later.
BUILT-IN
ETHERNET
Device number range
(Default)
000000 to 002047
Decimal
000000 to 002047
Decimal
000000 to 001FFF
Hexadecimal
000000 to 001FFF
Hexadecimal
000000 to 008191
Decimal
000000 to 008191
Decimal
000000 to 002047
Decimal
000000 to 002047
Decimal
000000 to 001FFF
Hexadecimal
000000 to 012287
Decimal
000000 to 001FFF
Hexadecimal
000000 to 002047
Decimal
000000 to 002047
Decimal
000000 to 001023
Decimal
000000 to 007FFF
Hexadecimal
000000 to 007FFF
Hexadecimal
000000 to 008191
Decimal
000000 to 000FFF
Hexadecimal
000000 to 000FFF
Hexadecimal
000000 to 000019
Decimal
000000 to 032767
Decimal
000000 to 3FD7FF
Hexadecimal
• Binary:
000000 to 4184063
(4086k points
maximum)
Decimal
• ASCII:
000000 to 999999
(976.6k points
maximum)
000000 to 3FD7FF
Hexadecimal
(4086k points maximum)
Remarks
---
• When the device
number range is
changed, access is
possible up to the
largest device number
after the change.
• Local devices cannot
be accessed.
*1
---
If the number of points is
set on the PLC file tab of
PLC parameter, access
is possible up to the
largest device number
after the setting.
However, in the ASCII
code communication, the
number of points
described on the left is
the access limit.
If the number of points is
set on the PLC file tab of
PLC parameter, access
is possible up to the
largest device number
after the setting.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents