Mitsubishi Q00JCPU User Manual page 691

Hide thumbs Also See for Q00JCPU:
Table of Contents

Advertisement

10
DEVICE EXPLANATION
(b) Use the same file name as the program
This setting should be selected when the file registers having the same file name
as the sequence program are to be used.
1) Operation performed when program is changed
If the program is changed, the file registers are automatically changed to
conform to the new program name.
There are also cases where it is convenient to use the file registers as local
devices which can only be used with the program currently being executed.
2) Setting of file register points
Choose [Online]
available file register points.
Example
When file registers (A to C) having the same name as the programs (A to C) are to be used,
operation is as shown below.
At program A is execution
At program B is execution
At program C is execution
Program A execution
Program B execution
Program C execution
Figure 10.72 File register when program is changed
POINT
File registers dedicated to each program may not be designated with some
instructions.
Refer to the allowable device in the programming manual of each instruction for
details.
[Write to PLC] on GX Developer to set the number of
File register A is accessed.
File register B is accessed.
File register C is accessed.
Synchronized
Synchronized
Synchronized
10.7 File Register (R)
10.7.4 File register registration procedure
R0
File register A
R0
File register B
R0
File register C
10
- 76
9
10
11
12

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents