6
FUNCTIONS
(a) Setting time condition
Constant
scan
Sequence
program
As the constant scan time, set a value that satisfies the following relational
expression.
(WDT Set Time) > (Constant Scan Set Time)
> (Sequence Program maximum Scan Time)
If the sequence program scan time is longer than the constant scan setting time,
the CPU module detects PRG. TIME OVER (error code: 5010).
In this case, the constant scan setting is ignored and the sequence program is
executed based on its scan time.
Constant scan setting
(Setting time: 4ms)
0
1
2
3
4
0
END
0
3.5ms
4ms
Scan where the constant scan is not normal
Figure 6.3 Operation when the Scan Time is longer than the Constant Scan
If the sequence program scan time is longer than the WDT setting time, the CPU
module detects a WDT error.
In this case, the program execution is stopped.
1
2
3
4
5
1
END 0
0.5ms
3.5ms
5.3ms
4ms
6.2 Constant scan
ms
2
3
4
1
2
3
4
END
0
END
0
0.5ms
3.4ms
0.6ms
4ms
6
1
2
3
4
5
6
7
8
- 7