FUNCTIONS
(2) Parameter setting
Item name
Execute the process as the
scan time proceeds.
Specify service process time.
Specify service process
execution counts.
Execute it while waiting for
constant scan setting.
6
- 190
6.25 Service Processing
6.25.2 Service processing
The service processing can be set in the PLC system tab of the PLC parameter dialog
box.
The service processing can be executed by selecting one of the parameter items in
Table6.59. Setting values for non-selected parameter items cannot be entered.
(Default: Execute the process as the scan time proceeds. =10%)
Table6.59 Parameter item list
Description
Specifies the percentage of service
processing for one scan.
Specifies the time of service processing
for one scan.
Specifies the count of service processing
for one scan.
Specifies whether to execute the service
processing while waiting for constant scan
setting.
Figure 6.110 Parameter setting screen
Setting range
• Range: 1 to 99%
• Unit: 1%
• Range: 0.2ms to 1000ms
• Unit: 0.1ms
• Range: 1 to 10 times
• Unit: 1 time
------
Remarks
Default at selection =10%
Default at selection
=0.2ms
Default at selection
=1 time
Even when the waiting
time is 0.2ms or less, the
service processing time
(0.2ms) will be added to
the scan time at service
processing execution.