Mitsubishi Q00JCPU User Manual page 361

Hide thumbs Also See for Q00JCPU:
Table of Contents

Advertisement

6
FUNCTIONS
Basic
Note6.15
Forced ON/OFF registered device
Input
Output
Note16
The Basic model QCPU does not support the forced ON/OFF registration operation from the
Basic
Forced input output registration/cancellation screen (
Note6.15
The Basic model QCPU can forcibly turns ON/OFF external I/O only by executing a device test in
GX Developer.
(d) Canceling ON/OFF registration data
The registered forced ON/OFF data can be canceled using GX Developer.
Once the registered data is canceled, the status of the forced ON/OFF registered
devices will be as follows.
Table6.19 Status of devices after forced ON/OFF registration data is canceled
Input from modules mounted
on the base unit
Input of CPU module to be
refreshed from LX of
CC-Link IE controller network
or MELSECNET/H
Input of CPU module to be
refreshed from RX of CC-Link
Input other than above
(outside of the refresh range)
Output from modules mounted
on the base unit
Output of CPU module to be
refreshed from LX of
CC-Link IE controller network
or MELSECNET/H
Output of CPU module to be
refreshed from RX of CC-Link
Output other than above
(outside of the refresh range)
Forced ON/OFF setting can be cleared by any of the following operations.
• Power supply OFF
• Reset operation using the RESET/L.CLR switch or RUN/STOP/RESET
switch of the CPU module
• Reset with remote reset operations
Note6.15
Note16
ON/OFF performed with
sequence programs
Assumes the ON/OFF status received from the module.
Assumes the refreshed ON/OFF status from CC-Link IE
controller network or MELSECNET/H.
Assumes the refreshed ON/OFF status from CC-Link.
Operation result in the
sequence program is
reflected.
Outputs the results of the
sequence program operations.
Outputs the results of the
sequence program operations.
Outputs the results of the
sequence program operations.
Assumes the result of the
sequence program operations.
ON
(3) in this section).
6.11 Monitor Function
6.11.3 Forced ON/OFF for external I/O
ON/OFF not performed with
sequence programs
Maintains the enforced ON/
OFF status.
Retains the registered ON/
OFF status.
Retains the registered ON/
OFF status.
Retains the registered ON/
OFF status.
Maintains the enforced ON/
OFF status.
6
- 61
1
2
3
4
5
6
7
8