3
SEQUENCE PROGRAM CONFIGURATION AND
EXECUTION CONDITIONS
(4) CPU module operation processing by switch operation
RUN/STOP status
Executes up to
the END
RUN
STOP
instruction and
stops.
STOP
RUN
Starts at step 0.
POINT
Table3.6 Operation processing by switch operation
Sequence
program
External output
operation
processing
Saves the output (Y)
status immediately before
switching to the STOP
status, and turns all points
OFF.
Determined by the
"STOP
RUN-time output
mode" in the PLC
parameter dialog box.
* 1: Since the Basic model QCPU cannot execute multiple programs, it cannot use subroutine
programs in the other programs.
The CPU module performs the following in any of RUN, STOP, and PAUSE
status:
• I/O module refresh processing
• Network module refresh processing
• Automatic refresh processing of intelligent function module
• Self-diagnostic processing
• Communication processing with external device such as GX Developer
• Processing of instructions dedicated to intelligent function modules
(completion processing only)
• Operation processing of Multiple CPU high speed transmission function
(Universal model QCPU only)
Even if the CPU module is in STOP or PAUSE status, the following operations can
be executed.
• I/O monitor or test operation using GX Developer
• Read/write from/to the external device using the MC protocol
• Communication with other stations using CC-Link IE controller network
and MELSECNET/H
• Communication with CC-Link remote stations
3.5 RUN, STOP, PAUSE Operation Processing
CPU module operation processing
M,L,S,T,C,D
Saves the device memory status
immediately before switching to
the STOP status.
Saves the device memory status
immediately before switching to
the STOP status.
However, when the initial device
values have been set, the values
are used.
Clears the local devices
Device memory
Y
Saves the output (Y)
status immediately
before switching to the
STOP status, and turns
all points OFF.
Determined by the
"STOP
RUN-time
output mode" in the
PLC parameter dialog
box.
(
Section 6.4)
*1
.
3
1
2
3
4
5
6
7
8
- 67